Loading...
BLD-2020-1690 20713 Rodrigues Ave PC 20-3625 BLDG PERMIT No. 362520 BLD-2020-1690 PLAN REVIEW No. PLAN REVIEW COMMENTS Plans and Scope of Review: This project shall comply with the following: The California Fire (CFC) & Building (CBC) Code, 2019 edition, as adopted by the City of Cupertino Municipal Code (CMC) and California Code of Regulations (CCR). The scope of this project includes the following: Proposed new 5,988 SF two-story single-family residence with attached Accessory Dwelling Unit (ADU) and attached garage. Plans Status: Plans are APPROVED with the following conditions. Plan Review Comments: 1. 1. Fire Sprinklers Required: (As noted on Sheet A1) An automatic residential fire sprinkler system shall be installed in one- and two-family dwellings and Accessory Dwelling Units (ADUs) as follows: 1. In all new one- and two-family dwellings and rebuild of existing one- and two-family dwellings as defined by the Building Official. 2. In all new basements and in existing basements that are expanded by more than 50 percent. 3. In all attached Accessory Dwelling Units and/or additions to an existing one- and two-family dwelling that have an existing fire sprinkler system. 4. In all attached Accessory Dwelling Units and/or additions to an existing non-sprinklered one- and two- family dwelling, when the building area is increased to more than 3,600 SF. Exception: One or more additions made to a building after January 1, 2011 that does not total more than 1,000 square feet of building area. 5. Detached Accessory Dwelling Units (ADUs) are not required to have fire sprinklers installed, provided that all of the following are met: a. The unit meets the definition of an Accessory Dwelling Unit as defined in the Government Code Section 65852.2. b. The existing primary residence does not have automatic fire sprinklers. c. The detached ADU does not exceed 1,200 square feet in size. d. The unit is on the same lot as the primary residence. e. The unit meets all access and water supply requirements of Chapter 5 and Appendix B and C of the 2019 California Fire Code. City Y E PLANS Y E SPECS Y E NEW Y E RMDL CONST. TYPE BY PAGE SEC/FLOOR R-3/U OCCUPANCY LOAD 5988 AREA Aditi Mukherjee ApplicantName SFR NAME OF PROJECT LOCATION Y E AS 2OF 2 1VB DATE 10/30/2020CUP Baker, Kathy PROJECT DESCRIPTION Residential Construction TABULAR FIRE FLOW REDUCTION FOR FIRE SPRINKLERS REQUIRED FIRE FLOW @ 20 PSI 2000 50%1000 PROJECT TYPE OR SYSTEM New Structure Rodrigues Ave20713 Cupertino BLDG PERMIT No. 362520 BLD-2020-1690 PLAN REVIEW No. PLAN REVIEW COMMENTS 2. Construction Site Fire Safety: All construction sites must comply with applicable provisions of the CFC Chapter 33 and our Standard Detail and Specification SI-7. Provide appropriate notations on subsequent plan submittals, as appropriate to the project. CFC Chp. 33. 3. Water Supply Requirements: Potable water supplies shall be protected from contamination caused by fire protection water supplies. It is the responsibility of the applicant and any contractors and subcontractors to contact the water purveyor supplying the site of such project, and to comply with the requirements of that purveyor. Such requirements shall be incorporated into the design of any water-based fire protection systems, and/or fire suppression water supply systems or storage containers that may be physically connected in any manner to an appliance capable of causing contamination of the potable water supply of the purveyor of record. Final approval of the system(s) under consideration will not be granted by this office until compliance with the requirements of the water purveyor of record are documented by that purveyor as having been met by the applicant(s). 2019 CFC Sec. 903.3.5 and Health and Safety Code 13114.7. 4. Address identification: (As noted on Sheet A1) New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. Where required by the fire code official, address numbers shall be provided in additional approved locations to facilitate emergency response. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall be a minimum of 4 inches (101.6 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure. Address numbers shall be maintained. CFC Sec. 505.1. This review shall not be construed to be an approval of a violation of the provisions of the California Fire Code or of other laws or regulations of the jurisdiction.  A permit presuming to give authority to violate or cancel the provisions of the fire code or other such laws or regulations shall not be valid.  Any addition to or alteration of approved construction documents shall be approved in advance. [CFC, Ch.1, 105.3.6] City Y E PLANS Y E SPECS Y E NEW Y E RMDL CONST. TYPE BY PAGE SEC/FLOOR R-3/U OCCUPANCY LOAD 5988 AREA Aditi Mukherjee ApplicantName SFR NAME OF PROJECT LOCATION Y E AS 2OF 2 2VB DATE 10/30/2020CUP Baker, Kathy PROJECT DESCRIPTION Residential Construction TABULAR FIRE FLOW REDUCTION FOR FIRE SPRINKLERS REQUIRED FIRE FLOW @ 20 PSI 2000 50%1000 PROJECT TYPE OR SYSTEM New Structure Rodrigues Ave20713 Cupertino