BLD-2023-0384_CF1RRegistration Number: 422-A020095011A-000-000-0000000-0000 Registration Date/Time: 2022-06-23 09:03:47 HERS Provider: CHEERS
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.006
Schema Version: rev 20210501
Report Generated: 2022-06-23 09:12:31
CERTIFICATE OF COMPLIANCE CF1R-ALT-02-E
Alterations to Space Conditioning Systems (formerly CF-1R-ALT-HVAC) (Page 1 of 3)
Project Name: 19500 Pruneridge Ave 2 2104 Date Prepared: 2022-06-23
A. General Information
CF1R-ALT-02 is applicable to multiple space conditioning systems contained within a single dwelling unit. When multiple dwelling units must be documented, use one
CF1R-ALT-02 document for each dwelling unit.
01 Project Name 19500 Pruneridge Ave 2 2104 02 Date Prepared 2022-06-23
03 Project Location 19500 Pruneridge Ave 2 2104 04 Building Type Multifamily
05 CA City Cupertino 06 Dwelling Unit Name 19500 Pruneridge Ave 2 2104
07 Zip Code 95014 08 Dwelling Unit Conditioned Floor
Area (ft2)950
09 Climate Zone 4 10
Number of Space Conditioning
(SC) Systems in this Dwelling
Unit:
1
B. Space Conditioning (SC) System Information
01 02 03 04 05 06 07 08 09 10
SC System ID or
Name
SC System
Location or Area
Served
CFA served by this
SC System (ft2)
Is the SC system a
ducted system?
Installing a
refrigerant
containing
component?
Installing new SC
system
components?
Installing more
than 40 feet of
ducts?
Installing entirely
new duct system?
Installing entirely
new SC system?Alteration Type
System 1 Location 1 950 Yes Yes Yes No No No
Altered space
conditioning
system
C. Extension of Existing Duct System, Greater Than 40 Feet (Section150.2(b)1Diib)
This section does not apply to this project.
NOTICE: This document has been generated by ConSol Home Energy Efficiency Rating System Services, Inc. (CHEERS) using information uploaded by third parties not affiliated with or related to CHEERS. Therefore, CHEERS is not
responsible for, and cannot guarantee, the accuracy or completeness of the information contained in this document.
CERTIFICATE OF COMPLIANCE CF1R-ALT-02-E
Alterations to Space Conditioning Systems (formerly CF-1R-ALT-HVAC) (Page 2 of 3)
Registration Number: 422-A020095011A-000-000-0000000-0000 Registration Date/Time: 2022-06-23 09:03:47 HERS Provider: CHEERS
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.006
Schema Version: rev 20210501
Report Generated: 2022-06-23 09:12:31
D. Altered Space Conditioning System (Sections 150.2(b)1E and F)
01 02 03 04 05 06 07 08 09 10 11 12 13
System ID/
Name
SC System
Description
of Area
Served
Heating
System Type
Altered
Heating
Components
Heating
Efficiency
Type
Heating
Minimum
Efficiency
Value
Cooling
System Type
Altered
Cooling
Components
Cooling
Efficiency
Type
Cooling
Minimum
Efficiency
Value
Required
Thermostat
Type
New or
Replaced
Duct Length
New Duct
R-Value
System 1 Location 1 Central split
HP
All new
heating
components
HSPF 8 Central split
HP
All new
cooling
components
SEER 14 Setback
N/A - no
ducts
replaced.
n/a
Required Documentation:
CF2R-MCH-01-E - Space Conditioning Systems
- Duct insulation requirement for the new portions of supply-air and return-air ducts or plenums: R6 (CZ 1-10, 12 and 13) and R8 (CZ 11 and 14-16)
CF2R and CF3R-MCH-20-H - Duct Leakage Test required when heating or cooling components are installed in ducted systems, or when more than 40 ft of duct length is replaced
-Leakage rate compliance: <= 15 percent or <= 10 percent leakage to outside, or seal all accessible leaks.
CF2R and CF3R-MCH-25-H Refrigerant Charge verification required when refrigerant containing components are installed or altered (applicable in CZ 2, 8-15).
CF2R and CF3R-MCH-23 Airflow Rate >= 300 CFM per ton required when MCH-25 is required.
Exceptions:
- Duct systems registered with HERS provider as previously sealed are exempt from MCH-20 Duct Leakage Testing requirements.
- Heating-only systems and Air Handler Furnace changes do not require verification of Air Flow MCH-23, or Refrigerant Charge MCH-25.
-Existing duct systems constructed, insulated or sealed with asbestos are exempt from MCH-20 Duct Leakage Testing requirements.
E. Entirely New or Complete Replacement Duct System, with or without Equipment Changeout (Sections 150.2(b)1Diia and 150.2(b)1E, F)
This section does not apply to this project.
F. Entirely New or Complete Replacement Space Conditioning System (Section 150.2(b)1C)
This section does not apply to this project.
NOTICE: This document has been generated by ConSol Home Energy Efficiency Rating System Services, Inc. (CHEERS) using information uploaded by third parties not affiliated with or related to CHEERS. Therefore, CHEERS is not
responsible for, and cannot guarantee, the accuracy or completeness of the information contained in this document.
CERTIFICATE OF COMPLIANCE CF1R-ALT-02-E
Alterations to Space Conditioning Systems (formerly CF-1R-ALT-HVAC) (Page 3 of 3)
Registration Number: 422-A020095011A-000-000-0000000-0000 Registration Date/Time: 2022-06-23 09:03:47 HERS Provider: CHEERS
CA Building Energy Efficiency Standards - 2019 Residential Compliance Report Version: 2019.1.006
Schema Version: rev 20210501
Report Generated: 2022-06-23 09:12:31
Documentation Author's Declaration Statement
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Shannon Phillips
Documentation Author Signature:
Company:
We Green, Inc.
Signature Date:
2022-06-23
Address:
3675 Ruffin Road Suite 320
CEA/ HERS Certification Identification (if applicable):
RCN13045
City/State/Zip:
San Diego CA 92123
Phone:
888-991-4377
Responsible Person's Declaration statement
I certify the following under penalty of perjury, under the laws of the State of California:
1.The information provided on this Certificate of Compliance is true and correct.
2.I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer).
3.That the energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the
requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4.The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets,
calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
5.I will ensure that a registered copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable
inspections. I understand that a registered copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Designer Name:
Leon Schaper
Responsible Designer Signature:
Company :
AQUINAS HVAC INC
Date Signed:
2022-06-23
Address:
1177 NORTH 15TH STREET
License:
1042033
City/State/Zip:
SAN JOSE CA 95112
Phone:
(619) 889-4003
NOTICE: This document has been generated by ConSol Home Energy Efficiency Rating System Services, Inc. (CHEERS) using information uploaded by third parties not affiliated with or related to CHEERS. Therefore, CHEERS is not
responsible for, and cannot guarantee, the accuracy or completeness of the information contained in this document.
Digitally signed by ConSol Home Energy Efficiency Rating System Services, Inc. (CHEERS). This digital signature is provided in order to secure the
content of this registered document, and in no way implies Registration Provider responsibility for the accuracy of the information.