Backflow Prevention Specialists _ •� ... f%CERTIFICATION OF RE-CLAIMED WATER SYSTEMS CROSS CONNECTION'SPECIALISTS
CERTIFIED CROSS CONNECTION CONTROL CONSULTANTS BACKFLOW BACKFLOW PREVENTION VALVE EXPERT
INSTALLATION-REPAIRS-TESTING-CERTIFICATION
OBACKFLOW PREVENTION SPECIALISTS, INC,
LICENSED CONTRACTOR C.C.L.#427328 CALIFORNIA (800)464-FLOW(3589)
3750-E CHARTER PARK DR.,SAN JOSE CA 951364358 (408)269-2600
1522-A DAY AVE.,SAN MATEO CA 94403 FAX(408)269-2650r�-,— '_.;".�,�T.� ,r
SERVICE ADDRESS 10300 N Tantau Ave.,Cupetlino ` S ®
: =
2004
MAILING ADDRESS Tech Facilty Siemens Bldg attn: Accounts Payable CONTACT DaVA -
.
801 Asbury Dr TEL# 773-66220
Buffalo Grove,IL 60089
MANUFACTURER MODEL NUMBER TYPE SIZE SERIAL NUMBER
Watts 909 RP 3/4" 479788
INTERNAL ® TAG LOCATION OF DEVICE chiHerbldg 5 roof
EXTERNAL ❑
IF DEVICE IS ANEW INSTALLATION PLEASE CHECK THIS BOX❑ PASSY
SS FAIL❑
• REDUCED PRESSURE DEVICES PRESSURE TYPE
DOUBLE CHECK VALVES VACUUM BREAKERS
RPP VALVES DIFFERENTIAL
CHECK VALVE CHECK VALVE PRESSURE/RELIEF
N0.1 NO.T
VALVE AIR INLET CHECK VALVE
CLOSEDjHT CLOSEDTIGHT� OPENEDAT:7�0LBS. OPENEDAT_LBS CLOSEDTIGHT ❑
INITIAL #Ibs. #lbs. #LBS #LBS
TEST OPENED UNDER 2.0 OPENED UNDER 1.0
LEAKED ❑ LEAKED ❑ OR DID NOT OPEN Cl OR DID NOT OPEN ❑ LEAKED ❑
REPAIRS
AND
MATERIALS
USED
FINAL CLOSED TIGHT❑ CLOSED TIGHT ❑ OPENED A7_LBS OPENED AT_LBS CLOSED TIGHT Cl
TEST #LBS #LBS FLBS
THE ABOVE REPORT IS CERTIFIED TO BE TRUE
INITIAL TEST BY CERTIFIED TESTER NO,-2C)56 < Ifs DATE 12-10-03
MO. DAY YR.
• REPAIRED BY DATE
FINAL TEST BY CERTIFIED TESTER NO. DATE
MO. DAY YR.
CERTIFICATION OF RE-CLAIMED WATER SYSTEMS CROSS CONNECTION SPECIALISTS
CERTIFIED CROSS CONNECTION CONTROL CONSULTANTSBACKFLOW PREVENTION VALVE EXPERT
INSTALLATION-REPAIRS-TESTING-CERTIFICATION
%ACKFLOW PREVENTION SPECIALISTS, INC.
LICENSED CONTRACTOR C.C.L.#427328 CALIFORNIA (800)464-FLOW(3569)
3750-E CHARTER PARK DR.,SAN JOSE CA 95136-1356 (408)269-2600
3608 FERNWOOD ST.,SAN MATEO CA 94403 FAX(408)269-2650 (.�,3' .,;
SERVICE ADDRESS 10300 N Tantau Ave.,CupertinoJ JAN baa,
MAILING ADDRESS Tech Facility Siemens Bldg attp}{
n:Accounts Payable CONTACT Dave t.;�}b3,
801 Asbury Dr TEL# 773-6220
Buffalo Grove,IL 60089
MANUFACTURER MODEL NUMBER TYPE SIZE SERIAL NUMBER
Watts 009 RP V 211644
INTERNAL ® TAG LOCATION OF DEVICE boiler ncedladder bldg5 Ist floor boiler#2
EXTERNAL ❑
IF DEVICE IS ANEW INSTALLATION PLEASE CHECK THIS BOX[3 PASSE] FAIL❑
• REDUCED PRESSURE DEVICES
PRESSURE TYPE
DOUBLE CHECK VALVES VACUUM BREAKERS
RPP VALVES DIFFERENTIAL
CHECK VALVE CHECK VALVE PRESSURE/RELIEF
N0.1 N0.2
VALVE AIR INLET CHECK VALVE
��
CLOSAD T HT El CLOSED TIGHT ❑ OPENED AT;'6 LBS. OPENED AT_LBS CLOSED TIGHT ❑
INITIAL #Ibs. Ibe. #LBS #LBS.
TEST OPENED UNDER 2.0 OPENED UNDER 1.0
LEAKED ❑ LEAKED ❑ OR DID NOT OPEN Cl OR DID NOT OPEN ❑ LEAKED ❑
REPAIRS
AND
MATERIALS
USED
FINAL CLOSED TIGHT❑ CLOSED TIGHT ❑ OPENED AT_LBS OPENED AT_LBS CLOSED TIGHT❑
TEST #LBS #LBS #LBS
THE ABOVE REPORT IS CERTIFIED,T{OO QBE T/RRUUUEEE
INITIALTESTBY_ `L.-.J rry`�`rLu.t� CERTIFIED TESTER NO.*265& 9DI� DATE 12-10-03
MO. DAY YR.
• REPAIRED BY
DATE
FINAL TEST BY CERTIFIED TESTER NO, DATE
MO. DAY YR.
I CERTIFICATION OF RE-CLAIMED WATER SYSTEMS _ '' CROSS CONNECTION SPECIALISTS
BACKFLOW PREVENTION VALVE EXPERT
CERTIFIED CROSS CONNECTION CONTROL CONSULTANTS
INSTALLATION-REPAIRS-TESTING-CERTIFICATION
•
BACKFLOW PREVENTION SPECIALISTS, INC.
LICENSED CONTRACTOR C.C.L.#427328 CALIFORNIA (800)484-FLOW(3589)
3750-E CHARTER PARK DR.,SAN JOSE CA 95138-1356 (408)269-2600
3608 FERNWOOD ST.,SAN MATEO CA 94403 FAX(408)269-2650�T��a�
SERVICE ADDRESS 10300 N Taritau Ave.,Cupertino ( JAN 2 0 2004
MAILING ADDRESS Tech Facih�Siemens Bldg attn: Accounts Payable attn: Accounts Payable CONTACT Dave by.
801 Asbury Dr TEL# 773-6220
Buffalo Grove, Q,60089
MANUFACTURER MODEL NUMBER TYPE SIZE SERIAL NUMBER
Watts 009 RP 3/4" N/A
INTERNAL ® TAG LOCATION OF DEVICE Bldg 5 roof Cooling tower
EXTERNAL ❑
IF DEVICE IS ANEW INSTALLATION PLEASE CHECK THIS BOX[] PAS
8 FAIL❑
• REDUCED PRESSURE DEVICES
PRESSURE TYPE
DOUBLE CHECK VALVES VACUUM BREAKERS
RPP VALVES DIFFERENTIAL
CHECKVALVE CHECKVALVE PRESSURE/RELIEF
N0.1 N0.2
VALVE AIR INLET CHECK VALVE
/� /-�
CLOS IGHT CLOSED TIGHT CPENEDATO 'V LBS. OPENEDAT_LBS CLOSED TIGHT ❑
INITIAL #Iba. #lbs. 0LB3 #LBS,
TEST OPENED UNDER 2.0 OPENED UNDER 1.0
LEAKED ❑ LEAKED Cl OR DID NOT OPEN ❑ OR DID NOT OPEN ❑ LEAKED ❑
REPAIRS
AND
MATERIALS
USED
FINAL CLOSED TIGHT❑ CLOSED TIGHT ❑ OPENED AT_LBS OPENED AT_LBS CLOSED TIGHT❑
TEST #LBS #LBS #LBS
THE ABOVE REPORT IS CERTIFIED TO BE TRUE
INITIAL TEST BY CERTIFIED TESTER NO�e� C V�s DATE 12-10-03
MO. DAY YR.
• REPAIRED BY DATE
FINAL TEST BY CERTIFIED TESTER NO. DATE
MO. DAY YR.
y
CERTIFICATION OF RE-CLAIMED WATER SYSTEMS CROSS CONNECTION SPECIALISTS
CERTIFIED CROSS CONNECTION CONTROL CONSULTANTSV
BACKFLOW PREVENTION VALVE EXPERT''
INSTALLATION-REPAIRS-TESTING-CERTIFICATION
*BACKFLOW. PREVENTION SPECIALISTS, INC.
LICENSED CONTRACTOR C.C.L.#427328 CALIFORNIA (800)484-FLOW(3569)
3750-E CHARTER PARK DR.,SAN JOSE CA 95136-1356 (408)269-2600
3608 FERNWOOD ST.,SAN MATEO CA 94403 FAX(408)269-2650
u.
SERVICE ADDRESS 10300 N TaNau Ave.,Cupertino ` JAN 2 0 2004
V
MAILING ADDRESS Tech Facility Siemens Bldg attn:Accounts Payable CONTACT Dave
801801 Asbury TEL# 773-6220
Buffalo Grove,IL 60089
MANUFACTURER MODEL NUMBER TYPE SIZE SERIAL NUMBER
Febco 825YA RP 11/2" A041144
INTERNAL ® TAG LOCATION OF DEVICE Bldg 5 outside by garage entrance on cooling tower
EXTERNAL ❑
IF DEVICE IS ANEW INSTALLATION PLEASE CHECK THIS BOX[] PAS 4_ FAIL❑
• REDUCED PRESSURE DEVICES r PRESSURE TYPE
DOUBLE CHECK VALVES VACUUM BREAKERS
RPP VALVES DIFFERENTIAL
CHECK VALVE CHECK VALVE PRESSURE/RELIEF
N0.1 N0.2
VALVE AIR INLET CHECK VALVE
CLOSED TIG�HT CLOSED TIGHT OPENED ATZ_LBS. OPENEDAT_LBS CLOSEDTIGHT ❑
INITIAL #lbs, --/ #Ibs, #LBS #LBS,
TEST OPENED UNDER 2.0 OPENED UNDER 1.0
LEAKED ❑ LEAKED ❑ OR DID NOT OPEN ❑ OR DID NOT OPEN ❑ LEAKED ❑
REPAIRS
AND
MATERIALS
USED
FINAL CLOSED TIGHT❑ CLOSED TIGHT ❑ CLOSED TIGHT❑
TEST OPENED AT_LBS OPENED AT_LBS
#LBS #LBS #LBS
THE ABOVE REPORT IS CERTIFIED TO BE TRUE
INITIAL TEST BY CERTIFIED TESTER N0. 2656 DATE 12-10.03
MO. DAY YR.
• REPAIRED BY
DATE
FINAL TEST BY CERTIFIED TESTER NO. DATE
-MO. DAY YR.
>t
CERTIFICATION OF RE-CLAIMED WATER SYSTEMS CROSS CONNECTION SPECIALISTS
CERTIFIED CROSS CONNECTION CONTROL CONSULTANTS BACKFLOW PREVENTION VALVE EXPERT
INSTALLATION-REPAIRS-TESTING-CERTIFICATION
%ACKFLOW PREVENTION SPECIALISTS, INC,
LICENSED CONTRACTOR C.C.L.#427328 CALIFORNIA (800)464-FLOW(3569)
3750-E CHARTER PARK DR.,SAN JOSE CA 95136-1356 (408)269-2600
1522-A DAY AVE.,SAN MATEO CA 94403 FAX(408)269-2650
SERVICE ADDRESS 10300 N Tantau Ave.,Cuperfino '
MAILING ADDRESS Tech Facility Siemens Bldg atlas:Accounts Payable CONTACT DaveAN 2 d 2004
801 Asbury Dr TEL# 773 y: — - --
Buffalo Grove,IL 60089
MANUFACTURER MODEL NUMBER TYPE SIZE SERIAL NUMBER
Watts 009 RP 2" 00699
INTERNAL ❑ TAG LOCATION OF DEVICE by cylone fence bldg 5
EXTERNAL
IF DEVICE IS ANEW INSTALLATION PLEASE CHECK THIS BOX[3 PASSP FAIL❑
. REDUCED PRESSURE DEVICES
PRESSURE TYPE
DOUBLE CHECK VALVES VACUUM BREAKERS
RPP VALVES DIFFERENTIAL
CHECK VALVE CHECK VALVE PRESSURE/RELIEF
N0.1 N0.2
VALVE AIR INLET CHECK VALVE
CLOSED TIGHT CLOSED TIOHT,�:M' OPENED AT Z'67 LBS. OPENEDAT_LBS CLOSEDTIGHT ❑
INITIAL #lbs. #lbs. OLDS #LBS,
TEST OPENED UNDER 2.0 OPENED UNDER 1.0
LEAKED ❑ LEAKED ❑ OR DID NOT OPEN ❑ OR DID NOT OPEN ❑ LEAKED ❑
REPAIRS
AND
MATERIALS
USED
FINAL CLOSED TIGHT❑ CLOSED TIGHT ❑ CLOSED TIGHT❑
TEST #LBS #LBS OPENED AT_LBS OPENED AT_LBS
III LBS
THE ABOVE REPORT IS CERTIFIED TO BE TRUE
INITIAL TEST BY - p� CERTIFIED TESTER NO. 2656 DATE 12-10-03
MO. DAY YR.
..REPAIRED BY
DOTE
FINAL TEST BY CERTIFIED TESTER NO. DATE
MO. DAY YR.
CERTIFICATION OF RE-CLAIMED WATER SYSTEMS gg����rr CROSS CONNECTION SPECIALISTS
BACKFLOW PREVENTION VALVE EXPERT
CERTIFIED CROSS CONNECTION CONTROL CONSULTANTS V
INSTALLATION-REPAIRS•TESTING-CERTIFICATION
�ACKF7
LOW PREVENTION SPECIALISTS INC,
LICENSED CONTRACTOR C.O.L.#427328 CALIFORNIA (800)4&r-FLOW(3569)
3750-E CHARTER PARK DR.,SAN JOSE CA 95136.1356 (408)268-2600
`- 1522-A DAY,AVE.,SAN MATEO CA 94403 FAX(408)269-2650
JAN 2 0 2004
SERVICE ADDRESS 10300 N Tantau Ave.,Cupertino
MAILING ADDRESS Tech Facility Bldg Accounts Payable attn:Accounts Payable CONTACT Dave
801 Asbury Dr TEL# 773-6220
Buffalo Grove, IL 60089
MANUFACTURER MODEL NUMBER TYPE SIZE SERIAL NUMBER
Watts 909 RP 10" 400604
INTERNAL ❑ TAG LOCATION OF DEVICE fire right of driveway bldg 5
EXTERNAL
IF DEVICE IS ANEW INSTALLATION PLEASE CHECK THIS BOX❑ PASSµI FAIL❑
•
REDUCED PRESSURE DEVICES
//�
PRESSURE TYPE
DOUBLE CHECK VALVES VACUUM BREAKERS
RPP VALVES DIFFERENTIAL
CHECK VALVE CHECK VALVE PRESSURE/RELIEF
N0.1 N0.2
VALVE AIR INLET CHECK VALVE
CLOSEDTIGHT CLOSEDTIGHT., � OPENEDAT-'•�LBS. OPENEDAT_LBS CLOSED TIGHT ❑
INITIAL 0Ibs. 6.2 9Ibe. #LBS 0 LBS.
TEST OPENED UNDER 2.0 OPENED UNDER 1.0
LEAKED ❑ LEAKED ❑ OR DID NOT OPEN ❑ OR DID NOT OPEN ❑ LEAKED ❑
REPAIRS
AND
MATERIALS
USED
FINAL CLOSED TIGHT❑ CLOSED TIGHT ❑ OPENED AT_LBS OPENED AT_LBS CLOSED TIGHT❑
TEST 0LBS OLOS 0 A
THE ABOVE REPORT IS CERTIFIED TO BE TRUE
INITIAL TEST BY CERTIFIED TESTER N6.2656 DATE 12-10-03
MO. DAY YR.
• REPAIRED BY
DATE
FINAL TEST BY CERTIFIED TESTER NO. DATE
MO. DAY YR.
4
CERTIFICATION OF RE-CLAIMED WATER SYSTEMS CROSS CONNECTION SPECIALISTS 3- BACKFLOW PREVENTION VALVE EXPERT .
CERTIFIED CROSS CONNECTION CONTROL CONSULTANTS ��) INSTALLATION-REPAIRS-TESTING-CERTIFICATION
SMvsC�eW ?+6'
%ACKFLOW PREVENTION SPECIALISTS, INC,
LICENSED CONTRACTOR C.C.L.#427328 CALIFORNIA (800) F ?,wT 9'�T%
3750-E CHARTER PARK DR.,SAN JOSE CA 95136-1356 (408)269-2600 T���
1522-A DAY AVE.,SAN MATEO CA 94403 FAX(408)269-2650
SERVICE ADDRESS 10300 N.Tantau Ave.,Cupertino
MAILING ADDRESS Tech Facility Siemens Bldg attn:Accounts Payable CONTACT Dave
801 Asbury Dr TEL# 773-6220
Buffalo Grove, IL 60089
MANUFACTURER MODEL NUMBER TYPE SIZE SERIAL NUMBER
Febco 825Y RP 2" T9302
INTERNAL ❑ TAG LOCATION OF DEVICE bldg 5 irrigation
EXTERNAL ® meter protection
IF DEVICE IS A NEW INSTALLATION PLEASE CHECK THIS BOX❑ PASSE`-FAIL❑
• REDUCED PRESSURE DEVICES PRESSURE TYPE
DOUBLE CHECK VALVES VACUUM BREAKERS
RPP VALVES DIFFERENTIAL
CHECKVALVE CHECK VALVE PRESSURE/RELIEF
N0.1 N0.2
VALVE AIR INLET CHECK VALVE
CLOSED TIGHT CLOSED TIGHT,45— OPENED ATZ_Z LBS. OPENED AT_LBS CLOSED TIGHT ❑
INITIAL albs. Z' #lbs. #LBS #LBS,
TEST OPENED UNDER 2,0 OPENED UNDER 1.0
LEAKED ❑ LEAKED ❑ OR DID NOT OPEN ❑ OR DID NOT OPEN ❑ LEAKED ❑
ry
REPAIRS
AND
MATERIALS
USED
FINAL CLOSED TIGHT❑ CLOSED TIGHT ❑ OPENED AT_LBS OPENED AT_LBS CLOSED TIGHT❑
TEST #LBS #LBS 9LBS
THE ABOVE REPORT IS CERTIFIED TO BE TRUE
INITIAL TEST BY CERTIFIED TESTER NO.2656 DATE 12-10-03
MO. DAY YR.
• REPAIRED BY
DOTE
FINAL TEST BY CERTIFIED TESTER NO. DATE
MO. DAY YR.
CERTIFICATION OF RE-CLAIMED WATER SYSTEMS CROSS CONNECTION SPECIALISTS
CERTIFIED CROSS CONNECTION CONTROL CONSULTANTS BACKFLOW PREVENTION VALVE EXPERT
INSTALLATION-REPAIRS-TESTING-CERTIFICATION
BACKFLOW PREVENTION SPECIALISTS, INC,
LICENSED CONTRACTOR C.C.L.#427328 CALIFORNIA (800)464-FLOW(3569)
3750-E CHARTER PARK DR.,SAN JOSE CA 95136-1356 (408)269-2600 _
1522-A DAY AVE.,SAN MATEO CA 94403 FAX(408)269-2650 � �
JAN 2 0 2004
SERVICE ADDRESS 10_300 N Tantau Ave.,300 N AveCupertino
MAILING ADDRESS Tech Facifi�Siemens Bldg attn: Accounts Payable attn: Accounts Payable CONTACT Dave BX'
801 Asbury Dr TEL# 773-6220
Buffalo Grove,IL 60089
MANUFACTURER MODEL NUMBER TYPE SIZE SERIAL NUMBER
Watts 009 RP 3/4" 178022
INTERNAL ® TAG LOCATION OF DEVICE boilerneedladderbldg5 garagebasement
EXTERNAL ❑
IF DEVICE IS ANEW INSTALLATION PLEASE CHECK THIS BOX[3 PAS FAIL❑
• REDUCED PRESSURE DEVICES PRESSURE TYPE
DOUBLE CHECK VALVES VACUUM BREAKERS
RPP VALVES DIFFERENTIAL
CHECK VALVE CHECK VALVE PRESSURE/RELIEF
N0.1 N0.2
VALVE AIR INLET. CHECK VALVE
CLOS�EW TIGHT a CLOSED TIGHT OPENED AT z_� LBS. OPENED AT LBS CLOSED TIGHT ❑
INITIAL #16s. X- #Ihs. #LBS #LBS,
TEST OPENED UNDER 2.0 OPENED UNDER 1.0
LEAKED ❑ LEAKED ❑ OR DID NOT OPEN ❑ OR DID NOT OPEN ❑ LEAKED ❑
REPAIRS
AND
MATERIALS
USED
FINAL CLOSED TIGHT❑ CLOSED TIGHT ❑ OPENEDAT_LBS OPENED AT_LBS CLOSED TIGHT❑
TEST #LBS #LBS #LBS
THE ABOVE REPORT IS CERTIFIED TO BE TRUE
INITIAL TEST BY CERTIFIED TESTER NO.2656 DATE 12-10-03
MO. DAY YR.
• REPAIRED BY
[NTE
FINAL TEST BY CERTIFIED TESTER NO. DATE l
MO. 4 DAV YR. }
CERTIFICATION OF RE-CLAIMED WATER SYSTEMS �� �/��ar� CROSS CONNECTION SPECIALISTS;
CERTIFIED CROSS CONNECTION CONTROL CONSULTANTS 4f""° BACKFLOW PREVENTION VALVE EXPERT
INSTALLATION-REPAIRS-TESTING-CERTIFICATION
BACKFLOW PREVENTION SPECIALNUIS,�IN4. C
LICENSED CONTRACTOR C.C.L.#427328 CALIFORNIA (800)484-FL,�3569)
3750-E CHARTER PARK DR.,SAN JOSE CA 95136-1356 FAX )269-2600 - G 2004
1522-A DAY AVE.,SAN MATEO CA 94403
SERVICE ADDRESS 10300 N Tantau Ave.,Cupertino
MAILING ADDRESS Tech Facility Siemens Bldg atm: Accounts Payable CONTACT Dave
801 Asbury Dr TEL# 773-6220
Buffalo Grove, IL 60089
MANUFACTURER MODEL NUMBER TYPE SIZE SERIAL NUMBER
Waris 909 RP 10" 400516
INTERNAL ❑ TAG LOCATION OF DEVICE by Cylone fence bldg 5
EXTERNAL
IF DEVICE IS ANEW INSTALLATION PLEASE CHECK THIS BOX❑ PASO FAIL❑
• REDUCED PRESSURE DEVICES
PRESSURE TYPE
DOUBLE CHECK VALVES VACUUM BREAKERS
RPP VALVES DIFFERENTIAL
CHECK VALVE CHECK VALVE PRESSURE/RELIEF
N0.1 N0.2
VALVE AIR INLET CHECK VALVE
CLOSED TIGHT CLOSED TIGHT OPENEDAT 2'�LBS. OPENEDAT_LBS CLOSED TIGHT Cl
Nibs. �'0 #Ihs. #LBS #LBS,
TEST OPENED UNDER 2.0 OPENED UNDER 1,0
LEAKED ❑ LEAKED ❑ OR DID NOT OPEN ❑ OR DID NOT OPEN ❑ LEAKED ❑ "
REPAIRS
AND
MATERIALS
USED e
FINAL CLOSED TIGHT Cl CLOSED TIGHT ❑ OPENED AT_LBS OPENED AT_LBS CLOSED TIGHT Cl
TEST #LBS #LBS - tLBS
THE ABOVE REPORT IS CERTIFIED TO BE TRUE
INITIAL TEST BY d CERTIFIED TESTER NO. 2656 DATE 12-10-03
MO. DAY YR.
REPAIRED BY DATE
FINAL TEST BY CERTIFIED TESTER NO. DATE
MO. DAY YR.