12030027 engineered systems
1133 Aladdin Avenue
San Leandro, CA 94577
Tel: (510) 346-4300
Fax: (510) 347-1331
Contractors Lic#120696
TEST AND BALANCE ANALYSIS REPORT
Job Name: Apple DA 03-2nd Floor Sheilded Room
10500 De Anza Blvd.
Cupertino, CA
ACCO Job#: 628706
Contractor: Devcon Construction,Inc.
Engineer: ACCO Engineered Systems
AIR DISTRIBUTION SYSTEM HAS BEEN COMPLETELY BALANCED
AS PER REQUIREMENTS OF SPECIFICATIONS AND RESULTS OF
TESTS HEREIN LISTED.
Date: April 19, 2012
Technician: Gerard Saunders
Approved By: Amber Ryman
acco ,
. . ■ . . v■■ • eeva�me
ME
aae®am0000mmo
■■m■mmmmmmmmm
- • aMEo■■mem as mma
am mm MM Mo M®®
■■m■■mmmmmm
■■�
mmmm mm mmm
■■mmmmmmmmm�
Gengineered systems
JOB # 628706
PROJECT Apple DA 03-2nd Floor Sheilded Room DATE 4/19/2012
ADDRESS 10500 De Anza Blvd. TRAVERSE LOCATION Duct (P-1)
Duct Traverse Readings A,
o A2
Point No. A B C D O A3
1 319 324 289 272 0 A4
2 303 328 282 307 DID2 D3 D4
3 322 325 313 324 a o a o 11110 0
4 312 319 317 322 C4 C3 C2 C
5 B40
6 B30
Sub Totals 11 1256 1 1296 1 1201 1 1225 B4-1
Corrected B=
TOTAL READINGS AVERAGE AREA CFM Total
4978 16 311.13 0.196 1 61
Air Density Correction D Size(Inches)
Air Temperature F 70 E DIAMETER 6
Altitude ft S AREA 0.2
Correction Factor 1.000 I CFM60
DensityIb/cu ft 0.075 G Number of
N traverse points 8
Pitot Spacing 6 Through 12
(Inches from Tip)
1 2 34 5 6
0.1938 0.6282 1.1628 1.9392 1 4.0608 4.8372 T Size(Inches)
7 1 8 E DIAMETER 6
5.37181 5.8062 S AREA 0.2
T
Center Static 0.02
D
A Average FPM 311
T Measured CFM 161.1
Notes: A
TECHNICIAN: Gerard Saunders
0engineered systems
Jos # 628706
PROJECT Apple DA 03-2nd Floor Sheilded Room DATE 4/19/2012
ADDRESS 10500 De Anza Blvd. TRAVERSE LOCATION Duct (P-2)
Duct Traverse Readings a A2
Point No. A B C D 0 A3
1 253 368 284 1 345 A4
2 300 345 289 1 304 Di D2 D3 D4 a
3 317 348 299 286 11
4 282 302 291 305 C4 C3 C2
5 B4[=
6 63=
Sub Totals 11 1152 1 1363 1 1163 1240 BF-1
Corrected Bj=
TOTAL READINGS AVERAGE AREA CFM Total
4918 16 307.38 0.196 1 60
Air Density Correction D Size(Inches)
Air Temperature F 70 E DIAMETER 6
Altitude ft S AREA 0.2
Correction Factor 1.000 I CFM 60
Density Ib/cu ft 0.075 G Number of
NJ traverse points 8
Pitot Spacing 6 Through 12
(Inches from Tip)
1 2 34 5 6
0.1938 0.6282 1.1628 1.9392 1 4.0608 1 4.8372 T Size(inches)
7 8 E DIAMETER 6
5.37181 5.8062 S AREA 0.2
T
Center Static 0.02
D
A Average FPM 307
T Measured CFM 60.4
Notes: A
TECHNICIAN: Gerard5aunders
Gengineered systems
JOB # 628706
PROJECT Apple DA 03-2nd Floor Sheilded Room DATE 4/19/2012
ADDRESS 10500 De Anza Blvd. TRAVERSE LOCATION Duct (P-3)
Duct Traverse Readings A,
AZ
Point No. A B C D A3
1 263 269 298 264 A4
2 281 275 292 271 DI D2 D3 D4
3 276 272 285 273 0 0 0 0 a
4 278 281 295 284 C4 C3 C1
5 Bao
6B3:=
Sub Totals 1098 1097 1170 1092 B=
Corrected B=
TOTAL READINGS AVERAGE AREA CFM Total
4457 16 278.56 0.196 1 55
Air Density Correction D Size(Inches)
Air Temperature F 70 E DIAMETER 6
Altitude ft S AREA 0.2
Correction Factor 1.000 I CFM 60
Density Ib/cu ft 0.075 G Number of
N1 traverse points 8
Pitot Spacing 6Through iz
(Inches from Tip)
1 2 34 5 6
0.1938 0.6282 1.1628 1.9392 4.0608 4.8372 T Size(Inches
7 1 8 E DIAMETER 6
5.37181 5.8062 S AREA 0.2
T
Center Static 0.19
D
A Average FPM 279
T Measured CFM 154.7
Notes: A
TECHNICIAN: Gerard Saunders
engineered systems
1133 Aladdin Avenue San Leandro,CA 94577-4311
(510)346-4300• (510)347-1331• License#120696
AIR OUTLET TEST REPORT
DATE: 04/19/12
PAGE: 5
PROJECT Apple DA 03-2nd Floor Sheilded Room
SYSTEM NO. TU-56 and TU-60 TEST APPARATUS Flow Hood
AREA SERVED Open Area OUTLET MANUFACTURER Titus
SUB-SYSTEM OUTLET FLOW GAIN DESIGN CFM PRELIMS FINAL
IDENTIFIER N0. TYPE SIZE COOL HEAT COOL VENT HEAT COOL HEAT COOL VENT HEAT
TU-56 1 SWGI 1010 1 250 80 - - - 257 75 -
Total - - - 2.6111 250 80 0 0 0 257 75 0
TU-60 1 SWGI 24x20 - 1575 450 525 - - 1582 476 521
Total - 1 2.911 6.44 1575 450 525 0 0 1582 476 521
REMARKS:
BALANCE TECH: Gerard Saunders
engineered systems
1133 Aladdin Avenue San Leandro,CA 94577-4311
(510)346-4300•(510)347-1331 •License#120696
AIR OUTLET TEST REPORT
DATE: 04/19/12
PAGE: 6
PROJECT Apple DA 03-2nd Floor Sheilded Room
SYSTEM NO. FC-1(Existing) TEST APPARATUS Flow Hood
AREA SERVED Chamber OUTLET MANUFACTURER NA
SUB-SYSTEM OUTLET DESIGN CFM PRELIMS FINAL
IDENTIFIER NO. TYPE SIZE Ak SUPPLY SUPPLY SUPPLY
FC-1 1 CD 2412 - 625 498 573
2 CD 2412 - 625 771 680
3 CD 2412 - 625 325 573
4 CD 2412 - 625 916 593
Total - - - - 2500 2510 2419
REMARKS:
BALANCE TECH: Gerard Saunders
Project Apple DA 03-2nd Floor
Number 628706 IM, engineered systems
MW MECHANICAL CONTRACTING
HP=2=6
0.06°We 0.51"We SUPPLY FAN PROFILES
FAN DATA MOTOR NAMEPLATE DATA
Manufacturer Mammoth Manufacturer US Motors
j j Model Number G052HHU Model Number <55HXMLL0561
I /
O Serial Number H1150404648 Voltage 460
o Type/Class DNL Phase 1 0
Sheave Manufacturer Direct Drive F.L. Amperage 3.3
Diameter/Bore Direct Drive Service Factor DNL
Shaft Centers Direct Drive Horsepower 1 HP
Belts Direct Drive Motor Eff iciency DNL
Filters 2/20x34.5x1 Sheave Manufacturer Direct Drive
Diameter/Bore Direct Drive
TEST DATA DESIGN I ACTUAL F TEST DATA ACTUAL' . :__
Motor RPM 1075/3SPD Low Voltage 476
Insert Fan Fan RPM 1075/3SPD Low
Actual Amperage 1.5 /: �
Characteristics and or Disc.Velocity DNL NA N.L.Amperage 0.858
External Static lln= 1 Brake Horsepower 1 .39 HP
Fan Curves Here Discharge 0.5"WC 0.51"WC Calculatedof #VALUE!
Suction DNL 0.06" WC TEMPERATURES DESIGN.I ACTUAL'
Total 0.5"WC 1 0.57"WC I Entering Air DLN
A P Filters DNL 0.13"WC Leaving Air DNL
A P Heating Coil DNL NA Entering HW
AP Cooling Coil DNL NA Leaving HW
Fan Static 0.5"WC 0.7'WC Entering CHW
CFM (L/s) 1,600 1 Leaving CHW
TECHNICIAN: Gerard Saunders DATE: 4/19/2012
r
engineered systems
1133 Aladdin Avenue San Leandro,CA 94577-4311
(S10)346-4300• (S10)347-1331• License#120696
AIR OUTLET TEST REPORT
DATE: 04/19/12
PAGE: 8
PROJECT Apple DA 03-2nd Floor Sheilded Room
SYSTEM NO. HP-2-6. TEST APPARATUS Flow Hood
AREA SERVED Chamber OUTLET MANUFACTURER NA
SUB-SYSTEM OUTLET DESIGN CFM PRELIMS FINAL
IDENTIFIER NO. TYPE SIZE Ak SUPPLY SUPPLY SUPPLY
HP-2-6 1 CD 2412 - 400 290 403
2 CD 2412 - 400 290 406
3 CD 2412 - 400 460 427
4 CD 2412 - 400 635 414
Total - - - - 1600 1675 1650
REMARKS:
BALANCE TECH: Gerarad Saunders
Project Apple DA 03-2nd Floor
Number 628706 Ih, engineered systems
MECHANICAL CONTRACTING
HP=2=7
0.27"WC 0.52°WC SUPPLY FAN PROFILES
FAN DATA r MOTOR NAMEPLATE DATA
Manufacturer Mammoth Manufacturer Marathon
I p
/ Model Number EC096-4HZC Model Number JQW
O Serial Number 3540203 Voltage 460
/
Type/Class DNL Phase 30
0
Sheave Manufacturer Martin F.L. Amperage 3.1
Diameter/ Bore AL74x1 Service Factor DNL
Shaft Centers 151/2 Horsepower 2 HP
Belts 1/A46 Motor Efficiency DNL
Filters 4/20x34.5xl Sheave Manufacturer Brownin
Diameter/Bore 1 VP50x5/8
TEST DATA DESIGN I ACTUAL TEST DATA ACTUAL.
Motor RPM 1725 1775 Voltage 477 480 478
Insert Fan Fan RPM DNL 900 Actual Amperage 2.1 2.4 2.2
Characteristics and or Disc.Velocity DNL NA N.L.Amperage 0.806 0.806 0.806
External Static Brake Horsepower 1.42 HP
Fan Curves Here Discharge 0.5"WC 0.52"WC Calculated Df #VALUE!
Suction DNL 0.27'WC TEMPERATURES DESIGN ACTUAL:
Total 0.5"WC 0.79"WC I Entering Air DNL NA
A P Filters DNL 0.05"WC Leaving Air DNL NA
A P Heating Coil DNL DNL Entering HW
P Cooling Coil DNL DNL Leaving HW
Fan Static 0.5"WC 0.84"WC Entering CHW
CFM (L/s) 1 3,200 1 3,134 Leaving CHW
TECHNICIAN: Gerard Saunders DATE: 4/19/2012
) engineered systems
1133 Aladdin Avenue San Leandro,CA 94577-4311
(510)346-4300•(510)347-1331• License#120696
AIR OUTLET TEST REPORT
DATE: 04/19/12
PAGE: 10
PROJECT Apple DA 03-2nd Floor Sheilded Room
SYSTEM NO. HP-24 TEST APPARATUS Flow Hood
AREA SERVED Chamber OUTLET MANUFACTURER NA
SUB-SYSTEM OUTLET DESIGN CFM PRELIMS FINAL
IDENTIFIER NO. TYPE SIZE Ak SUPPLY SUPPLY SUPPLY
HP-2-7 1 CD 2412 - 800 892 798
2 CD 2412 - 800 1211 739
3 CD 2412 - 800 645 794
4 CD 2412 - 800 898 803
Total - - - 3200 3646 3134
REMARKS:
BALANCE TECH: Gerard Saunders
® TESTING ENGINEERS, INC.
2811 Teagarden St. 510-835-312 MAY ® 510-834-3777 fax
San Leandro,CA 94577 800-660142 2012
San Leandro S�ose` jartnez
INSPECTION REPORT`/ Week Ending: 3/2/12
PROJECT# 55645 TYPE OF INSPECTION:
Proof Load Testing
PROJECT: PLACE OF INSPECTION:
Apple DA03.1 Chambers obsite
10500 De Anza
Cupertino,CA
Permit# 12030027 �./
DATE 3/2/12
HOURS 4
INSPECTOR M.Ardizzone
Reported to Scott at the jobsite as requested.
Applied a torque load of 25 foot lbs. to 3/8" diameter Hilti KB-TZ expansion anchors located in the floor for EMF Chambers in
OTS lab. Twenty-four(24)anchors of a total of 48 installed were tested representing 50% without visually apparent distress
or failure.
The preceding work was,to the best of my knowledge,in compliance with approved plans and specifications, including
revisions by engineer,and proof load values and rate of testing were supplied by manufacturer.
Reviewed by:
ME
�_
avr
Special Inspection Division Manager
lcc: Apple Computer Inc./L. Kim
Devcon Construction/J. Woodbury
City of Cupertino/Bldg. Inspection Dept.
This report can be reproduced only in its entirety unless written permission from TEi is obtained.
Page 1 of 1
� cartinez
TESTING ENGINEERS, INC.
12
2811 Teagarden St. 510-835-3142510-834-3777 fax
San Leandro,CA 94577 800-660-3142
San Leandro San Jose
INSPECTION REPORT Week Ending: 3/23/12
PROJECT# 55645 TYPE OF INSPECTION:
Proof Load Testing
PROJECT: PLACE OF INSPECTION:
Apple DA03.1 Chambers Jobsite
10500 De Anza
Cupertino,CA
Permit# 12030027
DATE 3/22/12
HOURS 2
INSPECTOR M. Ardizzone
Reported to Abnar at the jobsite as requested.
Applied a torque load of 25 foot lbs. to 3/8" diameter Hilti KB-TZ expansion anchors located in the 2nd floor for chambers.
Thirty-two(32)anchors of a total of 64 installed were tested representing 50% without visually apparent distress or failure.
The preceding work was,to the best of my knowledge,in compliance with approved plans and specifications,including
revisions by engineer,and proof load values and rate of testing were supplied by manufacturer.
Reviewed by:
avi ppero
Special Inspection Division Manager
lcc: Apple Computer Inc./L.Kim
Devcon Construction/J. Woodbury
City of Cupertino/Bldg. Inspection Dept.
This report can be reproduced only in its entirety unless written permission from TO is obtained.
Page 1 of 1
TESTING ENGINEERS, INC.
gad �
2811 Teagarden St. 510-835-3142 510 534-3777 fax
San Leandro,CA 94577
800-660-3142
2012 l JJ
San Leandro _
San Jose Martinez
INSPECTION REPORT®y Week Ending: 3/30/12
PROJECT# 55645 TYPE OF INSPECTION:
Expansion Anchors
PROJECT: PLACE OF INSPECTION:
Apple DA03.1 Chambers Jobsite
10500 De Anza
Cupertino,CA
Permit# 12030027
DATE 3/26/12
HOURS 4
INSPECTOR M.Ardizzone
Reported to Abnar of Devcon Construction at the jobsite as requested.
Inspected predrilled holes for proper diameter and depth. Observed the cleaning of holes and witnessed the proper insertion
of sixty-three(63)3/8" diameter Hilti KB-TZ expansion anchors,3-3/4" in length,embedded 3-1/4" and twenty-one(21)1/2"
diameter Hilti KB-TZ expansion anchors,3-3/4" in length,embedded 3-1/4" all into 2nd floor chamber at RF lab.
The preceding work was, to the best of my knowledge,in compliance with approved plans and specifications,including
revisions by engineer.
Reviewed by:—15_
avid. ppero
Special Inspection Division Manager
lcc: Apple Computer Inc./L.Kim
Devcon Construction/J. Woodbury
City of Cupertino/Bldg. Inspection Dept.
This report can be reproduced only in its entirety unless written perndssion from TEI is obtained.
Pagel of 1