Loading...
12030027 engineered systems 1133 Aladdin Avenue San Leandro, CA 94577 Tel: (510) 346-4300 Fax: (510) 347-1331 Contractors Lic#120696 TEST AND BALANCE ANALYSIS REPORT Job Name: Apple DA 03-2nd Floor Sheilded Room 10500 De Anza Blvd. Cupertino, CA ACCO Job#: 628706 Contractor: Devcon Construction,Inc. Engineer: ACCO Engineered Systems AIR DISTRIBUTION SYSTEM HAS BEEN COMPLETELY BALANCED AS PER REQUIREMENTS OF SPECIFICATIONS AND RESULTS OF TESTS HEREIN LISTED. Date: April 19, 2012 Technician: Gerard Saunders Approved By: Amber Ryman acco , . . ■ . . v■■ • eeva�me ME aae®am0000mmo ■■m■mmmmmmmmm - • aMEo■■mem as mma am mm MM Mo M®® ■■m■■mmmmmm ■■� mmmm mm mmm ■■mmmmmmmmm� Gengineered systems JOB # 628706 PROJECT Apple DA 03-2nd Floor Sheilded Room DATE 4/19/2012 ADDRESS 10500 De Anza Blvd. TRAVERSE LOCATION Duct (P-1) Duct Traverse Readings A, o A2 Point No. A B C D O A3 1 319 324 289 272 0 A4 2 303 328 282 307 DID2 D3 D4 3 322 325 313 324 a o a o 11110 0 4 312 319 317 322 C4 C3 C2 C 5 B40 6 B30 Sub Totals 11 1256 1 1296 1 1201 1 1225 B4-1 Corrected B= TOTAL READINGS AVERAGE AREA CFM Total 4978 16 311.13 0.196 1 61 Air Density Correction D Size(Inches) Air Temperature F 70 E DIAMETER 6 Altitude ft S AREA 0.2 Correction Factor 1.000 I CFM60 DensityIb/cu ft 0.075 G Number of N traverse points 8 Pitot Spacing 6 Through 12 (Inches from Tip) 1 2 34 5 6 0.1938 0.6282 1.1628 1.9392 1 4.0608 4.8372 T Size(Inches) 7 1 8 E DIAMETER 6 5.37181 5.8062 S AREA 0.2 T Center Static 0.02 D A Average FPM 311 T Measured CFM 161.1 Notes: A TECHNICIAN: Gerard Saunders 0engineered systems Jos # 628706 PROJECT Apple DA 03-2nd Floor Sheilded Room DATE 4/19/2012 ADDRESS 10500 De Anza Blvd. TRAVERSE LOCATION Duct (P-2) Duct Traverse Readings a A2 Point No. A B C D 0 A3 1 253 368 284 1 345 A4 2 300 345 289 1 304 Di D2 D3 D4 a 3 317 348 299 286 11 4 282 302 291 305 C4 C3 C2 5 B4[= 6 63= Sub Totals 11 1152 1 1363 1 1163 1240 BF-1 Corrected Bj= TOTAL READINGS AVERAGE AREA CFM Total 4918 16 307.38 0.196 1 60 Air Density Correction D Size(Inches) Air Temperature F 70 E DIAMETER 6 Altitude ft S AREA 0.2 Correction Factor 1.000 I CFM 60 Density Ib/cu ft 0.075 G Number of NJ traverse points 8 Pitot Spacing 6 Through 12 (Inches from Tip) 1 2 34 5 6 0.1938 0.6282 1.1628 1.9392 1 4.0608 1 4.8372 T Size(inches) 7 8 E DIAMETER 6 5.37181 5.8062 S AREA 0.2 T Center Static 0.02 D A Average FPM 307 T Measured CFM 60.4 Notes: A TECHNICIAN: Gerard5aunders Gengineered systems JOB # 628706 PROJECT Apple DA 03-2nd Floor Sheilded Room DATE 4/19/2012 ADDRESS 10500 De Anza Blvd. TRAVERSE LOCATION Duct (P-3) Duct Traverse Readings A, AZ Point No. A B C D A3 1 263 269 298 264 A4 2 281 275 292 271 DI D2 D3 D4 3 276 272 285 273 0 0 0 0 a 4 278 281 295 284 C4 C3 C1 5 Bao 6B3:= Sub Totals 1098 1097 1170 1092 B= Corrected B= TOTAL READINGS AVERAGE AREA CFM Total 4457 16 278.56 0.196 1 55 Air Density Correction D Size(Inches) Air Temperature F 70 E DIAMETER 6 Altitude ft S AREA 0.2 Correction Factor 1.000 I CFM 60 Density Ib/cu ft 0.075 G Number of N1 traverse points 8 Pitot Spacing 6Through iz (Inches from Tip) 1 2 34 5 6 0.1938 0.6282 1.1628 1.9392 4.0608 4.8372 T Size(Inches 7 1 8 E DIAMETER 6 5.37181 5.8062 S AREA 0.2 T Center Static 0.19 D A Average FPM 279 T Measured CFM 154.7 Notes: A TECHNICIAN: Gerard Saunders engineered systems 1133 Aladdin Avenue San Leandro,CA 94577-4311 (510)346-4300• (510)347-1331• License#120696 AIR OUTLET TEST REPORT DATE: 04/19/12 PAGE: 5 PROJECT Apple DA 03-2nd Floor Sheilded Room SYSTEM NO. TU-56 and TU-60 TEST APPARATUS Flow Hood AREA SERVED Open Area OUTLET MANUFACTURER Titus SUB-SYSTEM OUTLET FLOW GAIN DESIGN CFM PRELIMS FINAL IDENTIFIER N0. TYPE SIZE COOL HEAT COOL VENT HEAT COOL HEAT COOL VENT HEAT TU-56 1 SWGI 1010 1 250 80 - - - 257 75 - Total - - - 2.6111 250 80 0 0 0 257 75 0 TU-60 1 SWGI 24x20 - 1575 450 525 - - 1582 476 521 Total - 1 2.911 6.44 1575 450 525 0 0 1582 476 521 REMARKS: BALANCE TECH: Gerard Saunders engineered systems 1133 Aladdin Avenue San Leandro,CA 94577-4311 (510)346-4300•(510)347-1331 •License#120696 AIR OUTLET TEST REPORT DATE: 04/19/12 PAGE: 6 PROJECT Apple DA 03-2nd Floor Sheilded Room SYSTEM NO. FC-1(Existing) TEST APPARATUS Flow Hood AREA SERVED Chamber OUTLET MANUFACTURER NA SUB-SYSTEM OUTLET DESIGN CFM PRELIMS FINAL IDENTIFIER NO. TYPE SIZE Ak SUPPLY SUPPLY SUPPLY FC-1 1 CD 2412 - 625 498 573 2 CD 2412 - 625 771 680 3 CD 2412 - 625 325 573 4 CD 2412 - 625 916 593 Total - - - - 2500 2510 2419 REMARKS: BALANCE TECH: Gerard Saunders Project Apple DA 03-2nd Floor Number 628706 IM, engineered systems MW MECHANICAL CONTRACTING HP=2=6 0.06°We 0.51"We SUPPLY FAN PROFILES FAN DATA MOTOR NAMEPLATE DATA Manufacturer Mammoth Manufacturer US Motors j j Model Number G052HHU Model Number <55HXMLL0561 I / O Serial Number H1150404648 Voltage 460 o Type/Class DNL Phase 1 0 Sheave Manufacturer Direct Drive F.L. Amperage 3.3 Diameter/Bore Direct Drive Service Factor DNL Shaft Centers Direct Drive Horsepower 1 HP Belts Direct Drive Motor Eff iciency DNL Filters 2/20x34.5x1 Sheave Manufacturer Direct Drive Diameter/Bore Direct Drive TEST DATA DESIGN I ACTUAL F TEST DATA ACTUAL' . :__ Motor RPM 1075/3SPD Low Voltage 476 Insert Fan Fan RPM 1075/3SPD Low Actual Amperage 1.5 /: � Characteristics and or Disc.Velocity DNL NA N.L.Amperage 0.858 External Static lln= 1 Brake Horsepower 1 .39 HP Fan Curves Here Discharge 0.5"WC 0.51"WC Calculatedof #VALUE! Suction DNL 0.06" WC TEMPERATURES DESIGN.I ACTUAL' Total 0.5"WC 1 0.57"WC I Entering Air DLN A P Filters DNL 0.13"WC Leaving Air DNL A P Heating Coil DNL NA Entering HW AP Cooling Coil DNL NA Leaving HW Fan Static 0.5"WC 0.7'WC Entering CHW CFM (L/s) 1,600 1 Leaving CHW TECHNICIAN: Gerard Saunders DATE: 4/19/2012 r engineered systems 1133 Aladdin Avenue San Leandro,CA 94577-4311 (S10)346-4300• (S10)347-1331• License#120696 AIR OUTLET TEST REPORT DATE: 04/19/12 PAGE: 8 PROJECT Apple DA 03-2nd Floor Sheilded Room SYSTEM NO. HP-2-6. TEST APPARATUS Flow Hood AREA SERVED Chamber OUTLET MANUFACTURER NA SUB-SYSTEM OUTLET DESIGN CFM PRELIMS FINAL IDENTIFIER NO. TYPE SIZE Ak SUPPLY SUPPLY SUPPLY HP-2-6 1 CD 2412 - 400 290 403 2 CD 2412 - 400 290 406 3 CD 2412 - 400 460 427 4 CD 2412 - 400 635 414 Total - - - - 1600 1675 1650 REMARKS: BALANCE TECH: Gerarad Saunders Project Apple DA 03-2nd Floor Number 628706 Ih, engineered systems MECHANICAL CONTRACTING HP=2=7 0.27"WC 0.52°WC SUPPLY FAN PROFILES FAN DATA r MOTOR NAMEPLATE DATA Manufacturer Mammoth Manufacturer Marathon I p / Model Number EC096-4HZC Model Number JQW O Serial Number 3540203 Voltage 460 / Type/Class DNL Phase 30 0 Sheave Manufacturer Martin F.L. Amperage 3.1 Diameter/ Bore AL74x1 Service Factor DNL Shaft Centers 151/2 Horsepower 2 HP Belts 1/A46 Motor Efficiency DNL Filters 4/20x34.5xl Sheave Manufacturer Brownin Diameter/Bore 1 VP50x5/8 TEST DATA DESIGN I ACTUAL TEST DATA ACTUAL. Motor RPM 1725 1775 Voltage 477 480 478 Insert Fan Fan RPM DNL 900 Actual Amperage 2.1 2.4 2.2 Characteristics and or Disc.Velocity DNL NA N.L.Amperage 0.806 0.806 0.806 External Static Brake Horsepower 1.42 HP Fan Curves Here Discharge 0.5"WC 0.52"WC Calculated Df #VALUE! Suction DNL 0.27'WC TEMPERATURES DESIGN ACTUAL: Total 0.5"WC 0.79"WC I Entering Air DNL NA A P Filters DNL 0.05"WC Leaving Air DNL NA A P Heating Coil DNL DNL Entering HW P Cooling Coil DNL DNL Leaving HW Fan Static 0.5"WC 0.84"WC Entering CHW CFM (L/s) 1 3,200 1 3,134 Leaving CHW TECHNICIAN: Gerard Saunders DATE: 4/19/2012 ) engineered systems 1133 Aladdin Avenue San Leandro,CA 94577-4311 (510)346-4300•(510)347-1331• License#120696 AIR OUTLET TEST REPORT DATE: 04/19/12 PAGE: 10 PROJECT Apple DA 03-2nd Floor Sheilded Room SYSTEM NO. HP-24 TEST APPARATUS Flow Hood AREA SERVED Chamber OUTLET MANUFACTURER NA SUB-SYSTEM OUTLET DESIGN CFM PRELIMS FINAL IDENTIFIER NO. TYPE SIZE Ak SUPPLY SUPPLY SUPPLY HP-2-7 1 CD 2412 - 800 892 798 2 CD 2412 - 800 1211 739 3 CD 2412 - 800 645 794 4 CD 2412 - 800 898 803 Total - - - 3200 3646 3134 REMARKS: BALANCE TECH: Gerard Saunders ® TESTING ENGINEERS, INC. 2811 Teagarden St. 510-835-312 MAY ® 510-834-3777 fax San Leandro,CA 94577 800-660142 2012 San Leandro S�ose` jartnez INSPECTION REPORT`/ Week Ending: 3/2/12 PROJECT# 55645 TYPE OF INSPECTION: Proof Load Testing PROJECT: PLACE OF INSPECTION: Apple DA03.1 Chambers obsite 10500 De Anza Cupertino,CA Permit# 12030027 �./ DATE 3/2/12 HOURS 4 INSPECTOR M.Ardizzone Reported to Scott at the jobsite as requested. Applied a torque load of 25 foot lbs. to 3/8" diameter Hilti KB-TZ expansion anchors located in the floor for EMF Chambers in OTS lab. Twenty-four(24)anchors of a total of 48 installed were tested representing 50% without visually apparent distress or failure. The preceding work was,to the best of my knowledge,in compliance with approved plans and specifications, including revisions by engineer,and proof load values and rate of testing were supplied by manufacturer. Reviewed by: ME �_ avr Special Inspection Division Manager lcc: Apple Computer Inc./L. Kim Devcon Construction/J. Woodbury City of Cupertino/Bldg. Inspection Dept. This report can be reproduced only in its entirety unless written permission from TEi is obtained. Page 1 of 1 � cartinez TESTING ENGINEERS, INC. 12 2811 Teagarden St. 510-835-3142510-834-3777 fax San Leandro,CA 94577 800-660-3142 San Leandro San Jose INSPECTION REPORT Week Ending: 3/23/12 PROJECT# 55645 TYPE OF INSPECTION: Proof Load Testing PROJECT: PLACE OF INSPECTION: Apple DA03.1 Chambers Jobsite 10500 De Anza Cupertino,CA Permit# 12030027 DATE 3/22/12 HOURS 2 INSPECTOR M. Ardizzone Reported to Abnar at the jobsite as requested. Applied a torque load of 25 foot lbs. to 3/8" diameter Hilti KB-TZ expansion anchors located in the 2nd floor for chambers. Thirty-two(32)anchors of a total of 64 installed were tested representing 50% without visually apparent distress or failure. The preceding work was,to the best of my knowledge,in compliance with approved plans and specifications,including revisions by engineer,and proof load values and rate of testing were supplied by manufacturer. Reviewed by: avi ppero Special Inspection Division Manager lcc: Apple Computer Inc./L.Kim Devcon Construction/J. Woodbury City of Cupertino/Bldg. Inspection Dept. This report can be reproduced only in its entirety unless written permission from TO is obtained. Page 1 of 1 TESTING ENGINEERS, INC. gad � 2811 Teagarden St. 510-835-3142 510 534-3777 fax San Leandro,CA 94577 800-660-3142 2012 l JJ San Leandro _ San Jose Martinez INSPECTION REPORT®y Week Ending: 3/30/12 PROJECT# 55645 TYPE OF INSPECTION: Expansion Anchors PROJECT: PLACE OF INSPECTION: Apple DA03.1 Chambers Jobsite 10500 De Anza Cupertino,CA Permit# 12030027 DATE 3/26/12 HOURS 4 INSPECTOR M.Ardizzone Reported to Abnar of Devcon Construction at the jobsite as requested. Inspected predrilled holes for proper diameter and depth. Observed the cleaning of holes and witnessed the proper insertion of sixty-three(63)3/8" diameter Hilti KB-TZ expansion anchors,3-3/4" in length,embedded 3-1/4" and twenty-one(21)1/2" diameter Hilti KB-TZ expansion anchors,3-3/4" in length,embedded 3-1/4" all into 2nd floor chamber at RF lab. The preceding work was, to the best of my knowledge,in compliance with approved plans and specifications,including revisions by engineer. Reviewed by:—15_ avid. ppero Special Inspection Division Manager lcc: Apple Computer Inc./L.Kim Devcon Construction/J. Woodbury City of Cupertino/Bldg. Inspection Dept. This report can be reproduced only in its entirety unless written perndssion from TEI is obtained. Pagel of 1