11040141 - SI -== a.Za,r _ & ASSOCIATES , INC . GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING CONSTRUCTION TESTING AND INSPECTIONS November 17, 2011 [E 0 IJ 11 KA Project No.: 04611095 NOV 2 2011 Permit Noi: 11041401 Western Athletic Clubs 1 Lombard Street BY San Francisco, California 94111 ' Attention: Mr. Edgar Elliott Subject: Special Inspection Services—Progress Report No. 1 Bayes b Silicone Valley FILE _IOi�orth Wolfe Road Cupertino, California Gentlemen: In accordance with your request and authorization, our firm has provided construction observation and materials testing services for the above-referenced project. This report documents the services provided by our field personnel during the time period of October 28 through November 11, 2011. Copies of our daily field reports documenting the work observed and our findings are attached. Special inspection tasks include: • Observation of foundation excavations for consistency with the soils described in the project geotechnical investigation report and the geotechnical recommendations for foundation embedment. • Observation during the installation of epoxy-set reinforcing steel dowels. • Performed pullout or proof load testing on previously installed epoxy-set reinforcing steel dowels. • Observation of in-progress and completed reinforcing steel placement. • Observation of concrete placement. • Sampling of concrete during placement and preparation of compression test specimens. • Monitoring of time from batching to placement, and testing of concrete for slump and temperature. • Transportation of compression test specimens to the laboratory for curing and testing. • Collection of copies of certified mill test reports. • Review of welder's qualification papers. • Observation of structural welding completed at the shop. • Performance of Schmidt Hammer testing at the existing concrete floors slabs for evaluation of concrete compressive strength. 6711 Sierra Court,Suite B•Dublin,California 94568•(925)307-1160•Fax:(925)307-1161 With Offices Serving The Western United States 04611095 PRI KA No. 04611095 Page No. 2 CONCLUSIONS Based on the observations of our technician and the results of field testing services, it is our professional opinion that the construction observed and the materials tested during the identified time period were, to the best of our knowledge, in accordance with the approved project plans and the requirements of the 2010 California Building Code. Laboratory test results are reported under separate cover as the tests are completed. LIMITATIONS Construction observation, inspection and testing (special inspection) services are techniques used to check construction for conformance with the project requirements as the work progresses and to reduce the potential that construction elements are not in compliance with the project requirements as the work is completed. Even with diligent construction monitoring, some construction defects may be missed. In all cases, the contractor retains sole responsibility for the quality of work, for adhering to plans and specifications and for repairing defects, deficiencies or omissions, regardless of when they are found. We have performed our services in a manner consistent with the standard of care and skill ordinarily exercised by firms of our type practicing under similar conditions at this same time and locality. However, we do not undertake the guarantee of construction or production of a completed project conforming to the project plans and specifications. No warranty or guarantee is expressed or implied. Our services during the identified period of time were limited to those documented in our attached reports. If you have any questions regarding the information contained in this cover letter or the attached reports, or if we can be of further assistance, please contact our Dublin office at (925) 307-1160. Respectfully submitted, KRAZAN & ASSOCIATES, INC. Gregory J. Ruf, PE / Managing Engineer Attachments: Daily Field Reports (15 pages) cc: Addressee Form4 Architecture, Inc. Louie International City of Cupertino Krazan&Associates,Inc. With Offices Serving The Western United States 04611095 PRI 1(raZaZ & Associates , Inc . Page of GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING DSA File/AppI.No. CONSTRUCTION TESTING AND INSPECTION OSHPD No. Permit No. L(64'l 446 DATE: ( d-Z'- // CONTRACTOR: - a PROJECT#: 4-‘//.!).95-. I.O.R.: C PROJECT: i ( "-43, PRESENT AT SITE: 4i/477 /cc,'Tel'lerf LOCATION: dy# 2.9/A4 COPIES TO: KRAZAN PROJECT MANAGER: WEATHER: TEMP: /z_ L:... �i .r •//u' .1. Fi, _/_I...;. / ' LJ _r�fit/- 7 Q% r 6 1� i - ,a01.. '/.._ _ AI — - A 6�e%*Vi�r7�2� 625. • r t", . /107,-)st,r�2< <sx/ .>it/G iii' , -GSI"#---___ �_L_ l i/� �iL� 9 J !r a - - '— !---, e1-5-- � Le.- L%—= - / i — ,! _ -- ..-----:2--_-0-A,- -0L %L il! i ZRS67.e Zip, [r_ .1.71.,'!"_ lig /� --/_ . - _-�/6 --- /'",--- ,. -- GC d --.A.,.4---. .. i��_ l ! ..f.4-.1-.-- '3 e.1=LN"� -72P4°"--- �1i i l _.„', `! - A - !t! o� ==<= • r-) T-.e -- � ��s J Lam- /�6.c, _ _l.J, y ., _,_-.- ��s ,_,PL_..-"'ZA., - ,Ar.i: i es 4x14!.• 00 7- - i _-� ,, t��Z.-- _ ar ---;;C• L C�,4jc> JOz-( _ 4› e=c A'2 /-iS /- ------ lei- 0 - AsIlEl 4 L� '1iTi� a+7 - "....) e/ -i� A a ,1L- / h./I - p -� �/ - G---€...-+ - --291`.r'.S .==.41./2.2, ,),4' . To the best of my knowledge, the above WAS/WAS NOT performed in accordance with the approved plans, specifications, and regulatory requirements. Superintendent/Representative: Technician: 215 West Dakota Avenue,Clovis,CA 93612 • (559)348-2200 4221 E.Brickell St.,0n 61 • (909)974-4400 2205 Coy Avenue,Bakersfield,CA 93307 • (661)837-9200 43379 Business Park Dr.,St . 00,Temecula,CA 92590 • (951)694-0601 448 Mitchell Rd.,Ste.C,Modesto,CA 95354 • (209)572-2200 922 Valley Ave NW,Ste. 101,Puyallup,WA 98371 • (253)939-2500 545 Parrott St.,San Jose,CA 95112 • (408)271-2200 20714 State Hwy 305 N.E.,Ste.3C,Poulsbo,WA 98370 • (360)598-2126 5044 Bailey Loop,McClellan,CA 95652 • (916)564-2200 11715 N.Creek Pkwy South,Ste.C106,Bothell,WA 98011 • (425)485-5519 2979 W.Fairmount Avenue,Phoenix,AZ 85017 • (602)265-7090 11616 E.Montgomery Dr.,Ste.31,Spokane Valley,WA 99206• (509)534-9711 FILE COPY l<1aZa1Z & Associates , Inc . DSA File/Appl.No. GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING OSHPD No. CONSTRUCTION TESTING AND INSPECTION Permit No. DATE: //% /l CONTRACTOR: vyN - -- C Oite-5, . PROJECTt0 //D95 PERMIT NO. PROJECT: _ L Sic: . -1 C2 4 INSPECTOR. AK' - ..c-�ZA i LOCATION:/1/r7//'V• ado'j tre " JURISDICTION: fy '/ P 1�0 KRAZAN PROJECT MANAGER: •ev;j= WEATHER: Q /aka/AuegT IP: ❑ HIGH STRENGTH BOLTS A325 A490 • ❑ A Skidmoore test was performed on the -inch 0 bolts with the following torque readings: lbs./ft. lbs./ft lbs./ft. lbs./ft lbs./ft. Average torque reading: lbs./ft.tension. ❑ High strength bolt inspection was performed on the -inch 0 bolts at the following locationns: ❑ The bolts DID/DID NOT meet the required lbs./ft.tension. ❑ ANCHORS Proof Load Torque Test Epoxy ❑ %of total -inch 0 bolts were torque tested to lbs./ft.tension at the following locations: ❑ %of total anchors were load tested to lbs./ft. tension at the following locations: Visual inspection was performed on 0�� — _ r: B► ��% �� / .. -0 NOTES - DISCREPANCIES % COMPLETE 410, . .0r-- ��� / !/� % B iOl. Yi . 4, - .Ii_ .. _ i • -' _i//JL/. Oi - �� A ' 4 g..J1 -- i .0 0 , .-.:i/ A .."2.41, i O - ._J t i i / 7 , / .1► /!i - / — i T/ JVD .. i - , ,,- / ' O/_ j� �.� 9.'w! a Ar.. --- m_ 7 / .- ---7 # _ - > //.- _ � --sy' ' _ ., . A' ' / / i .....2..- r -, To the best of my knowledge, the ab•4ry WADS)NOT performed in accordance with the..proved plans, speci' - '.,s, d regulatory requirements. Superintendent/Representative: �/Ei�`"' ' "1°Aa Technician: j� ���fea(Q 215 West Dakota Avenue,Clovis,CA 93612 • (S59)348-2200 4221 E.B c ell St. int.o,CA 91761 • (909)974-4400 2205 Coy Avenue,Bakersfield,CA 93307 • (661)837-9200 43379 Business l Dr.,Ste.300,Temecula, r• 92590 • (951)694-0601 448 Mitchell Rd.,Ste.C,Modesto,CA 95354 • (209)572-2200 922 Valley Ave •W,Ste. 101,Puyallup,WA 9:371 • (253)939-2500 6711 Sierra Court.Ste.B,Dublin,CA 94568 • (925)307-1160 1230 Finn Hill Road NW,Ste.A,Poulsbo, WA 98370 • (360)598-2126 5044 Bailey Loop,McClellan,CA 95652 • (916)564-2200 11715 N.Creek Pkwy South,Ste.C 106,Bothell, WA 98011 • (425)485-5519 2979 W.Fairmount Avenue,Phoenix,AZ 85017 • (602)265-7090 11616 E.Montgomery Dr.,Ste.31,Spokane Valley,WA 99206 • (509)534-9711 FILE COPY DSA File/Appl.No. IK.1'2LZ3JT1 & Associates , Inc . GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING • OSHPD No. CONSTRUCTION TESTING AND INSPECTION Permit No. DATE: ///7/// CONTRACTOR: �5_ _,� PROJECT it 0c/. /G,'96-- PERMIT NO: PROJECT: >�Y -- .Uf7'cJii/co c/&—/%C1�3/ INSPECTOR / .4.r _ 't._ / - i ,,,r 4 LOCATION:( �/��.-77.!/j,/-�9 JURISDICTION:L� c4,'�p 4 , KRAZAN PROJECT MANAGER: v WEATHER: �j ��� TEMP;E4 _ • ❑ HIGH STRENGTH BOLTS A325 A490 ❑ A Skidmoore test was performed on the -inch e bolts with the following torque readings: lbs./ft. lbs./ft lbs./ft. lbs./ft lbs./ft. Average torque reading: lbs./ft.tension. ❑ High strength bolt inspection was performed on the -inch 0 bolts at the following locationns: ❑ The bolts DID/DID NOT meet the require lbsift.tension. ANCHORS r of Load . Torque Test Epoxy [7�. %of -inch e bolts were torque tested to lbsift.tension at the following locations: c" 0 %of / total were load tested to -����"� - lbs./ft. tensio •t the following locations: .� O 1 — 1 // .fi. / ❑ Visual inspection was performed on NOTES DISCREPANCIES % COMPLETE • t, - / rr ' - l M �//!/,64-5 To the best of my knowledge, the ab•, 0/WAS NOT performed in accordance with the proved plans�ci' atio nd regulatory requirements. Superintendent/Representative: Technician:/'? 1^ lJ / 215 West Dakota Avenue,Clovis,CA 93612 • (559)348-2200 4221 E.Brick St.,) ario,CA 91761 • (909)9744400 2205 Coy Avenue,Bakersfield,CA 93307 • (661)837-9200 43379 Business P.r Dr.,Ste.300, Temecula,CA 92590 • (951)694-0601 448 Mitchell Rd.,Ste.C,Modesto,CA 95354 • (209)572-2200 922 Valley Ave ,Ste. 101,Puyallup, WA 98371 • (253)939-2500 6711 Sierra Court.Ste.B,Dublin,CA 94568 • (925)307-1160 1230 Finn Hill Road NW,Ste.A,Poulsbo,WA 98370 • (360)598-2126 5044 Bailey Loop,McClellan,CA 95652 • (916)564-2200 11715 N.Creek Pkwy South,Ste.C106,Bothell, WA 98011 • (425)485-5519 2979 W.Fairmount Avenue,Phoenix,AZ 85017 • (602)265-7090 11616 E.Montgomery Dr.,Ste.31,Spokane Valley,WA 99206 • (509)534-9711 FILE COPY aiZ & Associates , Inc . DSA File/Appl.No. GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING OSHPD No. CONSTRUCTION TESTING AND INSPECTION Permit No. , 10Yo IN-1 e DATE: t I (Veil 1 �j CONTRACTOR: ,crt, 'IDA Z �•O.�s�' L�il�,� PROJECT#: Ve Dc?lT J PERMIT NO: PROJECT: ?c Cl t J /S)� I j(Dn V,(l it INSPECTOR: �1 LOCATION: 1 vl D I CO r --.)D 14_ e/P'1 n� JURISDICTION: �t KRAZAN PROJECT MANAGER: G.', I u WEATHER: SN n Ai TEMP: J HIGH STRENGTH BOLTS A325 _ A490 ❑ A Skidmoore test was performed on the -inch 0 bolts with the following torque readings: lbs./ft. lbs./ft lbs./ft. lbs./ft lbs./ft. Average torque reading: lbs./ft.tension. ❑ High strength bolt inspection was performed on the -inch 0 bolts at the following locationns: ❑ The bolts DID/DID NOT meet the required lbs./ft.tension. E ANCHORS/ty�,,,>I Proof Load Torque Test N Epoxy . ❑ %of total -inch 0 bolts were torque tested to lbs./ft.tension at the following locations: ❑ %of total anchors were load tested to lbsfft. tension at the following locations: ..1 Visual i on(w�,s performed on � %4n -A W )-ed _ t • i 0 o- 4 `w)41I, �f-z) P) 4- , 1,.‘0, d cp' S &rpt( r at.`)'y �/ 6 49 �/ ✓Pli r� eiv, r 31 NOTES DISCREPANCIES % COMPLETE ( o„- y.1-10. o 40 ( SI-cd r.,,,..4 itS (, 11-11-e., d„ r pi be, I I- '-11, rc i-,-('s P \e,t( l 11 s s' cvd L-Cd 11-) &Li.. t--1-01•t1 s-4--J JeanE p e J uttd �. /4-, N., ?,)-r Irl [b )'- S O To the best of my knowledge, the above 0/WAS NOT performed in accordance with the approved plans, specifications, and regulatory requirements. Superintendent/Representative: Tec 'cian: V 215 West Dakota Avenue,Clovis,CA 93612 • (559)348-2200 4221 E.Brickell St.,Ontario,CA 91761 • (909)974-4400 2205 Coy Avenue,Bakersfield,CA 93307 • (661)837-9200 43379 Business Park Dr.,Ste.300,Temecula,CA 92590 • (951)694-0601 448 Mitchell Rd.,Ste.C,Modesto,CA 95354 • (209)572-2200 922 Valley Ave NW,Ste. 101,Puyallup,WA 98371 • (253)939-2500 6711 Sierra Court.Ste.B,Dublin,CA 94568 • (925)307-1160 1230 Finn Hill Road NW,Ste.A,Poulsbo,WA 98370 • (360)598-2126 5044 Bailey Loop,McClellan,CA 95652 • (916)564-2200 11715 N.Creek Pkwy South,Ste.C106,Bothell,WA 98011 • (425)485-5519 2979 W.Fairmount Avenue,Phoenix,AZ 85017 • (602)265-7090 11616 E.Montgomery Dr.,Ste.31,Spokane Valley,WA 99206 • (509)534-9711 FILE COPY tow Fle/Appl.No. A I A Z 8L Associates , Inc . DSA GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING OSHPD No. CONSTRUCTION TESTING AND INSPECTION Permit No. DATE 1 1 — - 1 1 CONTRACTOR: S P. � PROJECTS: 41-la I,I &9,s I.O.R.: —IS"— PROJECT: l et1s.. 4I. PRESENT AT SITE: t� LOCAT1OAt C,&., }► OA_ COPIES TO: �-- KRAZAN PROJECT GER: ahre4A `L c WEATHER: TEMP: 6e0 STRUCTURAL STEEL 5g.E7 OP WELDIN % T. NNC MATERIAL ID 0 U.T. 0 M.T. 0 P.T. l ed. VK1das ..)CLA. ..4.aj L .. S b I. 1, Location 3 4.a yr- 141-(CO1 e1,s_.a.,eQ s Pe_ 1L0 1 Q 1 ekt 3 1, to l E rvt,(3.a+ l o t Gin g 3r 1 tat.Grtn B'4 ,.1Dt t z,1 C2_, s fa_ „..1.(c- ' too TB,3, too B'kF1,00Bt, toof32.. KlVdder qualification/certification verified for: 1VS rr a_vtb SKPosition: FLAT VERTICAL ORIZONTAL OVERHEAD Filler Metal: C`D7-7-fp R Process: SMAW41220 GMAW SAW 0 Other: • - 4 Weld Type: aBb C.P. P.P. PLUG 0 Other. Weld Size 3/16' 41,50 5/16" ell0 0 Other: Codes: t_' MO TITLE 21 UBC ASME [z NOTES fl DISCREPANCIES n % COMPLETE V 1.444.Ce.+nac, l Lai14,.. as...-t:4- A r l L 44St rernkic.. MT 4drltr�, "CD-1" lev,the4413 • u To the best of my knowledge,the abo !_WAS?/ .AS NOT performed in accordance with the approved plans,specifications,and regulatory requirements. SuperintenderdlRepresentative: Technician: r" J A--, el*PL., Ll�� ='#G o�lsa/ 215 West Dakota Avenue,Clovis,CA 93612 • (559)348-2200 4221 St.,Ontario,CA 91761 • (909)974-4400 2205 Coy Avenue,Bakersfield,G4 93307 • (661)837-9200 43379 Business Park Dr.,Ste.300,Temecula,CA 92590 • (951)694-0601 448 t6tdieD Rd,Ste.C,Modesto,C4 95354 • (209)572-2200 922 Valley Ave NW,Ste. 101,Puyallup,WA 98371 • (253)939-2500 6711 Sema Court.Ste.B,Dublin,CA 94568 • (925)307-1160 1230 Finn Hill Road NW,Ste.A,Poulsbo,WA 98370 • (360)598-2126 5044 Bailey Loop,McClellan,CA 95652 • (916)564-2200 11715 N.Creek Pkwy South,Ste.C106,Bothell,WA 98011 • (425)485-5519 2979 W.Fairmount Avenue,Phoenix,A2 85017 • (602)265-7090 11616 E.Montgomery Dr.,Ste.31,Spokane Valley,WA 99206 • (509)534-9711 FILE COPY CFC.. 3(Tfyi SSAB0(-1 Test Certificate 1770 Bill Sharp Boulevard,Muscatine,IA 52761-9412 Form Tom:Reviairm 1:Date 31 Oct 20150 Customer: VALLEY IRON INCtomer P.O. No.: 116189 • 1BM Order No.: 41-246571.12 I Shipping Manifest: MB086687 3114 S.CHERRY AVE � PII ASTM A572-50/14343(06)/A709-30/111343(06A) ' PO BOX 12024 Ship Data: 10 Jul 09 Cert No: 06}163100 1 CA � 1�� Cart Date10 Jai 09 (Page 1 of;1) 2024 SI e: 1.000 X 96.00 X 240.0 (IN) • Tested Places Tensiles . Charily Impact nista Beat Piece Piece 9it VS 96 Average Abs,�(FILB) 45 Shear Tat Tat 'IDt BDWTT W Dimensions Loc (PSI) j(PSI) 21n Sin Ir Hardness 1 2 3 Avg 1 2 3 Avg Torp Dhr Sls ' ap 46Shr• B90538 C28 1:357M882=11:65.*: .003X96.00 L i r a t s s !"'� 390538 • C30 0.371 x96 00�L3G�� IL 65 t'��� 13UTS t a a 36 T Heat. (headcal Analysis Id C Mn P 8 81 Tat Ak. Cu Cr Mo Cb V T1 ORGN, B90538 (.15 1 1.161_0121_0011 .04 I .0211 .22 1.14 1.10 1.05 1.001 1.052 1.006 f US,, • • MERCURY IS NOT A METALLURGICAL COMPONENT OF THE STEEL AND NO MERCURY WAS INTENTIONALLY ADDED • DURING THE MANUFACTURE OF THIS PRODUCT • 100% MELTED AND MANUFACTURED IN THE USA. MTR DIN EN10204 TYPE 3.1 COMPLIANT. B9G538 C31 PCES: 3; WGT: 19684 • • Cost Part#: WE HEREBY CERTIFY THAT THUS MATERIAL WAS TESTED IN ACCORDANCE WI1H.AND MEETS THE B.H.Wales i • REQUIREMENTS OP.THE APPROPRIATE SPECIFICATION semi T iLv GBr-peooucr • i. • Bill To: Ship To: 121 Order Date:07/25/2011 CERTIFIED MATERIAL TEST REPORT BROWN STRAUSS DIV. BLUE 'PEE BROWN STRAUSS STEEL PO No:77931-3Q GERDAU• AAiERIBTEEL ACCTS PAYABLE 4221 EAST MARIPOSA ROAD Mill Order No:3913797 Midlothian Mill 2495 URAVAN ST. ROCKWELL TRACK 44 Load No:1402495 ®GERDAUAMERISTEE1 300 Ward Road AURORA CO STOCKTON CA Manifest No:2096981 Midlothian, TX 76065 80011 US 9521.5 US (972)775-8241 Si2E GRADE LENGTH PRODUCT SPECIFICATIONS W 18 X 354 / W460 X 52 992/572-50 65 FT / 19.812 M WF BEAMS ASTM A6-09, A992-06a, A572-07 • HEAT N : 2261435M CHEMICAL ANALYSIS . C Mn P S Si. Cu Ni Cr Mo Sn V Al Nb CE .08 .97 .015 .015 .26 .42 .10 .13 .031 .009 .002 .0U4 .021 .31 PHYSICAL PROPERTIES Yield Strength Tensile Strength Specimen Area Elongation Bend Test ROA KSI MPa KSI MPa Sq In Sq cm % Gage Length Dia. Result t 60.3 415.8 77.0 530.9 0.575 3.71 23.1 BIn 200 mm 62.7 432.3 78.3 539.9 0.584 3.77 24.8 8In 200 mm TENSILE TEST RATIOS YLD/TENS TENS/YLD YLD/TENS TENS/YLD .78 1.28 .8 1.25 • All manufacturing processes of this product, including electric arc MELTING and continuous CASTING, occurred in the U.S.A. CMTR complies with EN 10204 3.1 . "I hereby certify that the contents of this report are correct and accurate. All testa and operations performed by this materia],- manufacturer or its sub-contractors, when applicable, are in compliance with the requirements of the material specifictions and applicable purchaser, designated requirements." Signed• ., — -. i�c�6. 1lJ Tom L. Harrington: Quality �"�Date:Oct. 11, 2011 Signed: Date: • g ,A surance Manager . Notary Public (if applicable) Page: 2 of 2 Bill To: Ship To: 121 Order Date:09/27/2011 CERTIFIED MATERIAL TEST REPORT BROWN STRAUSS DIV. BLUE TSE BROWN STRAUSS STEEL PO No:79006 • GERDAU AMERISTEEL • ACCTS PAYABLE 4221 EAST MARIPOSA ROAD Mill Order No:3935041 Midlothian Mill 2495 URAVAN ST. ROCKWELL TRACK ff4Load No:1402495 ®GE2DAUAMERI5TEEL 300 Ward Road AURORA CO STOCKTON CA Manifest No:2096981 Midlothian, TX 76065 80011 US 95215 US (972)775-8241 SIZE GRADE LENGTH PRODUCT SPECIFICATIONS W 12 X 304 / W310 X 44.5 992/572-50 60 FT / 18.288 M WF BEAMS ASTM A6-09, A9 -05a. A572-07 HEAT N : 17.937250,: 22- CHEMICAL ANALYSIS C n P S Si Cu Ni Cr Mo Sn V Al Nb CE .09 .99 .0.1.5 .032 .22 .30 .08 .13 .029 .006 .002 .003 .018 .31 PHYSICAL PROPERTIES Yield Strength Tensile Strength Specimen Area Elongation Bend Test ROA KSI MPa KSI MPa Sq In Sq cm % Gage Length Dia. Result t 55.9 385.4 74.4 513.0 0.635 4.10 22.2 BIn 200 mm • 56.5 389.6 74.5 513.7 0.630 4.06 23.1 81n 200 mm TENSILE TEST RATIOS YLD/TENS TENS/YLD YLD/TENS TENS/YLD .75 1.33 .76 1.32 • • All manufacturing 'processes of this product, including electric arc MELTING and continuous CASTING, occurred in the U.S.A. CMTR complies with EN 10204 3.1 "I hereby certify that the contents of this report are correct and accurate. All tests and operations performed by this material manufacturer or its sub-contractors, when applicable, are in compliance with the requirements of the material specifications and applicable purchaser designated requirements. " LT SF Signed— oect-1 � se-- -� �- -_7.- Date:oet. 11, 20li Signed: Date: Tom .L. Harrington: Quality ,surance Manager Notary Public (if applicable) ' Page: 1 of 1 • NUCOR-YAMATO STEEL CO. CERTIFIED MILL TEST REPORT P 0 Box 1228 DATE 10011 MILTED AND MAMVTACTUULD DI U.S.A BLYTHEVILLE AB 12316 7/29/11 • All shun pro6lcad by Rem-Tante Sled uv cut nd KALI to a full)M1Ld and flee grain lractiu. SOLD TO SHIP TO mmuww NTKRVSS MLLE W. IIHUWN bTtihUSS-S.1x:KTUN -1`i` t . 2495 URAVAN STREET 4221 E MARIPOSA ROAD 7606 ROCKWELL Dna 4 i. �i�` -, •�- AURORA, CO 80011 STOCKTON, CA 33009 7722B FFQ2 *1 SPECIFICATIONS ..t.'k.: _t.. L e' t ,. ,• _t• �. t ASTM A709/A709M-09 GR5Os (3455) ASTM A6/A6M-09 MECHANICAL PROPERTIES CHEMICAL PROPERTIES 1 l 1 rrer larDeIGaum® WTI MT* l8A8PYIMPACT nal min rmaa /ttarao iurr nvecraraeao C Mn P S Si Cu Ni Cr Mo V Cb ,CE ;Iona raw GT$ TIU$C1 x r Fr Liz off*.. 1,11va x o mora Ss•Pan C1 1 W14 - 30.0 5 369401 .78 52000 67000 24 ' .08 .91 .016 035 .22 .29 .11 .10 .03 .00 .013 .29 50' .78 53000 68000 25 . .01 .16 W360 x 44.0 359 462 24 15.240 M 365 469 25 2 W14 - 30.0 2 369403 .79 55000 70000 26 .08 .93 .017 031 .22 .29 .12 .12 .03 .00 .013 .30 50' .77 55000 71000 24 .01 .16 W360 x 44.0 379 483 26 15.240 K 379 490 24 3 W14 - 30.0 2 369401 .78 52000 67000 24 .08 .91 .016 035 .22 .29 .11 .10 .03 .00 .013 .29 55' L .78 53000 68000 25 .01 .16 W360 x 44.0 359 462 24 16.764 M 365 469 25 4 W14 - 30.0 5 369407 .78 51000 65000 24 .07 .93 .017 030 .21 .28 .11 .11 .03 .00 .011 .29 55' .17 54000 70000 25 .01 .15 W360 x 44.0 352 446 24 16.764 M 372 483 25 ELONGATION BASED ON 8.00 INCH GAUGE LENGTH- CARBON EQG7VALENT d' -C�•I t'6*((r+Mo-V);s=(�7TC )!16 Pcm=C*51/301-Mo/20+Cu/20+NI/60*Cr/20-Mo/15+V/1 On-5B for .0007 Mer.o:<has no bam mo of t ha d�rea masafactvesng oft maessal. Corroarion Index:CI�6.01(o%Cil)+3.SS(%NI)+1.2(%Cr)+1.4?(°%Sl)+17.28(%P)-7.29(%Cu)(%NI)9.10(%Ni)(4/%P)a3.39(%Cu) I�yp�ylhtiVegans(leis rem'UeaROI>ft$ aneanob grand tornSTATE OF ARKANSAS 13A1Y*genie=dOpml1EI IfB15118ta m in' sMika COUNTY OF MISSISSIPPI GARY PENNELL SWORN TO AND sUBSCR1BED BEFORE ME THIS -0D►urranumace Day of_ rano/Kaud NUCOR•YAMATO STEEL CO. CERTIFIED MILL TEST REPORT DATE 1/09/09 10096 MELTED AND MANUFACTURED IN U.SA. P.O.BOX 127E • BLYTTIEVILLE,AR 72316 Al shapes poduced by Nucor-Tomato Stall we east I r•n O I:L r:5. 261592 and rolled to a fully killed d One Dain practice. S S ASTM A992/A9928-06a A572/A572N 0850-06 ?ILL O1 LADING 943382 H ASW STEEL - NEST COAST I C/O =RP ON TRtJCAb1Ci TM P ASA709/A70911-07 01150 (345) CUSTOMER NO 9011 P 11355 ARRDN ROOTE ROAD • C ASTM A709/A709M-07 t3R508 (3458) RANCHO COCAMONGA, CA 91730 I ASTM A6/A6N-07 T CUSTOMER f.0. LA-5161 O C S A O ASCO STffi. T L I O 1641 NEN MARXET AVE. 0 BOUTS PLA3NFIELD, NJ 07080 N T S 0 maCKANICALPROPERMIa CHEIO9441. _ OTYEWAmug itFATa Dew �D .,�., , � CHAR" rIMPACT C Mn P S Si Cu Ni Cr Mo V Cb CE ITEM yarTia Pa PJa7 x •f FT-WS $n p CI •E... NPR arc96_ •C. 128E9 1 W27 -217.0 1 328944 .76 56000 74000 29 .07 1.39 .022 .019 .28 .30 .10 .11 .03 .05 .002 .37 35' .75 55000 73000 30 .01 .19 11690 x323.0 386 510 29 10.668 M 379 503 30 2 827 -217.0 2 328961 .76 60000 79000 24 .07 1.35 .021 .022 .25 .28 .09 .12 .03 .05 .001 .36 50' .75 58000 77000 25 .01 .18 W690 x323.0 414 545 24 • 15.240 M 400 531 25 3 877 -217.0 2 328933 .75 57000 76000 27 .07 1.39 .024 .023 .28 .30 .09 .11 .03 .05 .002 .37 60' .74 55000 74000 28 .01 .19 W690 x323.0 393 524 27 . 18.288 M 379 510 28 4 W27 -217.0 2 328948 .78 59000 76000 25 • .07 1.37 .020 .015 .24 .33 .11 .12 .03 .05 .003 .37 65' .76 58000 76000 27 .01 .19 W690 x323.0 407 524 25 - 19.812 M • 400 524 27 5 1127 -258.0 1 321530 .76 57000 75000 28 .08 1.37 .019 .015 .24 .28 .11 .10 .02 .05 .002 .37 50' .76 56000 74000 27 .01 .19 11690 x384.0 •393 517 28 15.240 M 386 510 27 6 W27 -258.0 1 32891 -76 57000 75000 27 .07 1.37 -022 .023 .26 .29 .09 .11 .03 .05 .002 .37 50' . .76 57000 75000 27 -01 .18 W690 X384.0 \ 393 517 27 15.240 N 393 517 27 • 7 1127 -258.0 1 328910 .76 57000 75000 27 .07 1.37 .026 .022 .21 .28 .10 .14 .03 .05 .002 .37 60' 4-0.76 57000 75000 28 .01 .18 W690 x384.0 393 517 27 18.288 M 393 517 28 8 W27 -258.0 ( 1 328915x.75 57000 76000 26 .07 1.37 .022 .023 .24 .28 .09 .13 .03 .05 .002 .36 60' 77 58000 75000 27 .01 .18 11690 x384.0 393 524 26 18.288 N 400 517 27 : 9 827 -258.0 1 322513 .77 58000 75000 27 .07 1.38 .020 .017 .25 .24 .09 .10 .03 .05 .003 .36 65' /.76 58000 76000 27 -01 .18 • 1 W690 x384.0 400 517 27 19.812 N 400 524 27 • _ J. c•K.&b.g•n•q•ur+ •••i• NA+w -C�f CARBON 001DYALvmTICCEW)-C•MA•ID4 VJ*CIO 40.03 I o..•rrre alqTt ELONGATION BASED ON 0.00 INCH GAUGE WIDTH STATE OF ARKANSAS COUNTY OF n::.::••^•.4`�'1" ',,,, SWORN TO AND SUBSCRIBED BORE . ,,.. I hereby rarefy Bat Ore of Ods report we ,ie.. ra...ev aCeurata and correct All test results and operations 9 01 widowed by this meteAal menufaeaaar are In Day A d II NIT' '. Ipropllartoe sigh Die repulrartlerlta of the Oretstlai • QUALITY ASSURANCE _JI � W NOTARY epecEkalons Idea In the Specifics/km Block above. `l,, goi � CUSTOMER COPY MY COMMISSION EXPIRES 10 21 20�. . NUCoR-YAMArn STEE CQ,. T . 1/09/09 • P.0:00:4142d Ii BLY0tOnJ AR74318 1 Aialti*.0loml .E0)* 4'**101#1A • • • Od"r*O ti)9 r•CSi d 01tif 0os•: • • I'::O E :JO •25140 J. 8 gam'.- $ AB J199?7#99�1 Oso 5 f �1 X30-06• • • Di L..; OF .DING '1'1141.314 • D 'RIM 049' P A709/i10$0007 ,r, so i.ii .- - .- I 1180 ' C/0': P•0 ._ ..E. ,i :A709/k 0.r4O7 ,sas0A'(34591. • . . : cuS-0;.'E.::. :o ilii'• P s .,` 4 n8711 M/6M-.O7 . Bi119 •• �' 91?3Q •I ` Ai S • 'T . 0 • 0. 102.84 • - - l • 8. 4.04.3„1100!^IOIR ! AVSL 0 • , S0 Pyr li3 07000 .6 1 , . T p .• o sBa� Sp9 P' $ 6`I QI �I Cr KAo'E V •. :1(p '!2: • Y epr • .l.or mor } t RBI f011 aTr'lac. r L.:Mei .PBI• PIA :. :.: F' �1 4 PARI .p • •1 • .-358.0 328919 •7657000•75000 21 .07.1.37 022' 023 .26 .29 .09 .. . ..q .18.05,002 .37 . .75 0061509 •27 • • I : ae3ao.o 3• - 819 2 . 19.81.2 11 - •.393 517 27-, - • -• L. : •.: -. :.. • : • a i ti . • • • ■.'c.�•�r•e,1:g•a. 4r�+aw�, 'CA401001101AIa1o. .7,00, i �.�..`�..yy��y�i�y�igqyy��,....:.:::•....•'.:1'......-.•:. ..1.:...,:i. �., .. :... a FLQ?IOAt10N8i4��1.8p041(IIQRt1Q�'E�IGItI '.TOAWD.51.180000:'..!.'.,:—.;•.., - -: '!•.• -L Y YIMtlhsao_n1F4sdrisAO� :. • t 4ea a_eS.O omlllo4 N041.060:nd#61.1or�s 9 .p a acke, ;. . .CUSTOMER COPY PAY _ is it 4 , - 1 • -.,==..1Krazan & Associates , Inc . OSA FilelAppl. No. GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING OSHPD No. CONSTRUCTION TESTING AND INSPECTION 1 1/4-0 "-1 Permit No. ) 1 DATE: )1 C b ) CONTRACTOR: SCln �S C (-01\1Q��tl�1 ' PROJECT a: Leeei1 ORS I.O.R.: PROJECT: [kJ Q1 ;I;C4/1, Va:1), PRESENT AT SITE: hal-41- w/ -C ^ \x(19-St (tl,S1'it-•t �c LOCATION: 10( A/, 'o1 ft L rr 0 COPIES TO: c;,b C C O ki�� J KRAZAN PROJECT MANAGER: wI PLW WEATHER: S J TEMP: ❑ CONCRETE ❑ MASONRY ❑ Other ❑ Inspected the batch plant operations. Batch Plant: ❑ per UBC ❑ Discrepancies as noted below ❑ Inspected placement of CONCRETE / CMU'S / VENEER / GROUT at the following locations: ❑ CAST / PICKED UP set (s) of CONCRETE / MORTAR / GROUT / PRISMS / SAMPLES were cast for mix # with a slumpls) of inches, temperature of F, an air content of %, and unit weight of at the following locations: ❑ Total Yards Placed: ❑ Number of workers on CONCRETE / MASONRY / GROUT crew: ❑ Lab Data Sheet Nols).: X REINFORCING STEEL • ❑ SAMPLED / TAGGED reinforcing steel from Sizels)/Heat Numbers: , Gyy / r 1 Inspected the placement of reinforcing steel for the f V at the following locations: LI 1 e,. r; 1 ' Li 3 t--1' ',cM I_ 4c- 1 / L;,s kyd�, +0. ‘ Lia NOTES --4-9 111 DISCREPANCIES El % COMPLETE .44 T C-ItW 14-1\ C-It�jC�,lc.t N:3 . T+jc + � c'tkie,tesSiQLc• d, 6\IANS, I &( $ V (U 1 �Pne4, I know of my own personal knowledge that the work -/was not, in every material respect, been performed in compliance with the f36 approved documents. Superintendent/Representative: Technician: p. y FILE COPY 4 aZ & Associates , Inc . DSA File/Appl.No. GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING OSHPD No. CONSTRUCTION TESTING AND INSPECTION Permit No. I u 0 6 f `i: DATE: //QV// CONTRACTOR: 5 j"(�D/7 37 �i�T / PROJECTt'b// 1 Q 5' PERMIT NO: f _ PROJECT: /27L/' G1-u5 ,-� INSPECTOR:,ILfejML/O LOCATION: '`�..1 -li f / 1i. -�A JURISDICTION: C/ / a// C^ / //� KRAZAN PROJECT MANAGER: WEATHER: ,275 TEMP: HIGH STRENGTH BOLTS A325 A490 ❑ A Skidmoore test was performed on the -inch e bolts with the following torque readings: IbsJft. lbs./ft lbs./ft. _lbs./ft lbs./ft. Average torque reading: lbs./ft.tension. ❑ High strength bolt inspection was performed on the -inch e bolts at the following locationns: ❑ The bolts DID/DID NOT meet the required lbs./ft.tension. VANCHORS V Proof Load Torque Test Epoxy ❑ %of total -inch e bolts were torque tested to lbs./ft.tension at the following locations: /iJ %of I G' I (� �a BF 1---L'I'Z load tested to a v( 'O W lbs./ft. tension at th following locations: 5 4-' CYe 11{�r S ) ;.�2 /c k1.- ; L)nec 19. k tT/r,.. o Visual inspection was performed on 2OTES DISCREPANCIES % COMPLETE 7 /i.6 . - (9Z.Z. egibi5 0 > `-/%ei7lW7 7 v/85 n All L-Z - ZP _ ? S/v$/ D&1'723.5 ,. Q W 1!5 • '7 i i 1-b/n72,8s 7 ,5 / /1/nib-07es To the best of my knowledge, the above A /WAS NOT performed in accordance with the approved plans, specifications, and regulatory requirements. Superintendent/Represent ative:.„_,,,- Technician: nn ..re ikitit 215 West Dakota Avenue,Clovis,CA 93612 • (559)348-2200 4221 E.Brickell St.,Ontario,CA 91761 __ - • (909)974-4400 ____ 2205 Coy Avenue,Bakersfield,CA 93307 • (661)837-9200 43379 Business Park Dr.,Ste.300,Temecula,CA 92590 • (951)694-0601 448 Kitchell Rd.,Ste.C,Modesto,CA 95354 • (209)572-2200 922 Valley Ave NW,Ste. 101,Puyallup,WA 98371 • (253)939-2500 6711 Sierra Court.Ste.B,Dublin,CA 94568 • (925)307-1160 1230 Finn Hill Road NW,Ste.A,Poulsbo,WA 98370 • (360)598-2126 5044 Bailey Loop,McClellan,CA 95652 • (916)564-2200 11715 N.Creek Pkwy South,Ste.C106,Bothell, WA 98011 • (425)485-5519 2979 W.Fairmount Avenue,Phoenix,AZ 85017 • (602)265-7090 11616 E.Montgomery Dr.,Ste.31,Spokane Valley,WA 99206 • (509)534-9711 FILE COPY 'aZ l & Associates , Inc . Page l of GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING DSA File/Appl.No. CONSTRUCTION TESTING AND INSPECTION OSHPD No. Permit No. DATE: /�,/D // CONTRACTOR, '� . 3 (;4/3'7".. PROJECT if: 0 //�.5-r •:e1- 6r A---- e., ) . PROJECT: ;39, .Z z/4:7 Z/co,'c OZI PRESENT AT SITE: •57/7777 .7,2"..z/.:(,?,5%/-e• ��l� LOCATION: jeV LU ,- 7/�YJ COPIES TO: e ":02,t.-- J e'- •GrJc t KRAZAN PROJECT MANAGER: 6--,_ ../,',4---- WEATHER: �, C.,f TEMP: e;'—r- i//iri/ ice/ .,#'_-__.L—' ii /!Lal �liyl't i���� o .I/j ✓i.�/ . %* ePAr %/ I//// ,i7&,‘•;44e2..e/ c...2.-r2....as'a-e", '."/ [ %iy� / moi/ i _,,/,- 7 ---_Ari -t-d/e9-fri AtIPMPVINTII,I7 ,11e5i1M/r- '/ # 10�f' i d�c1 i v(e /2,,,-_ L i % ,ice/ / / GSL% 7 CGCY c-gaZe eLe>e , et W..e e y I _ge-r#, e Z -Z_ , K.2 0', '10 1, /9 ) 3� - ,s e ) 5/ _ 5e/W) 43 =--*_=6De. ...r.ez> 4 5/ _ /5c,ze35- _ 4(2t5 41 = 5,00 3) 34 4300 -35- = 4550 -3_. = 4700 1) 3- 4�3X .. _ 4L700 ,. _ 4-700 5)35 =- '15-06 .3,5- =-- 57e 34 . 6a 4)30 = 47o' = 4766 34 = 4360 7)36 ` 4706 3 = 47' 34 -=4300 g)3 , = 47O 3, -- ¢3a 34 _ 4306 9).35" - , 34- 436' 3. = 4'36 /0 34 = 4 00 -- -'_- 6-,e) 34-- • " '• jsaed i �/ ill . = 2 i _ _ _•/AkW�rA„4 45, • , . ,l/S/.% .../. %!l// /��. Z. /iii. /! / 1 / ., /. . /. 0 "i_ / i _/ To the best of my knowledge, the ab• e WA /WAS NOT performed in accordance with th> .••prove plans, spec' ions, and regulatory requirements. Superintendent/Representative: Technician: , v- 7 711, rf 215 West Dakota Avenue,Clovis,CA 93612 • (559)348-2200 4221 E.Brickell St '*ntario,CA 91761 • (909)974-4400 2205 Coy Avenue,Bakersfield,CA 93307 • (661)837-9200 43379 Business rk Dr.,Ste.300, Temecula,CA 92590 • (951)694-0601 448 Mitchell Rd.,Ste.C,Modesto,CA 95354 • (209)572-2200 922 Valley Ave W,Ste. 101,Puyallup,WA 98371 • (253)939-2500 545 Parrott St.,San Jose,CA 95112 • (408)271-2200 20714 State Hwy 305 N.E.,Ste.3C,Poulsbo,WA 98370 • (360)598-2126 5044 Bailey Loop,McClellan,CA 95652 • (916)564-2200 11715 N.Creek Pkwy South,Ste.C106,Bothell, WA 98011 • (425)485-5519 2979 W.Fairmount Avenue,Phoenix,AZ 85017 • (602)265-7090 11616 E.Montgomery Dr.,Ste.31,Spokane Valley,WA 99206• (509)534-9711 FILE COPY • - I'.1 aZalf 1 & Associates , Inc . DSA File GEOTECHNICAL ENGINEERING • ENVIRONMENTAL ENGINEERING DSA App.No. CONSTRUCTION TESTING AND INSPECTION Permit No 1/ // // ' DATE: CONTRACTOR:P /! � O.SP ���'�jyG4, PROJECT t - �/� ` c.143,F��_ /e-s �� PROJECT: - ,� Z., ' CD.7"" . ' PRESENT AT SIT • %imar r an.. LOCATION' •# ,-,4 1,r6//D ` . COPIES TO; 4 / ...''',7--- -.z.(2.//p . Q /Ze KRAZAN OJECT MANAGER: /, iC'�7 ' WEATHER: ..4,/_ ;€__S-- TEMP:72 i I I CONCRETE ❑ MASONRY ❑ Other ❑ Inspected the belch plant operations.Batch Plant: . 0 per UBC 0 Disaepandes as noted below. ❑ ins"-pd placemen CRETE CMU'S / VENEER / GROAT at the following locations: m57( C ?/G?/�P PICKED UP / set(s) of d'/MORTAR /GROUT /PRISMS/SAMPLES were c for mix x 1-AP69�/ with a stump(s) of "2" inches, temperature 01 c-5--- •F an air cont of %.and unit weight of at the following locations: Dotal yards placed. �0 Number of workers o /GROUT crew ❑ Lab Data Sheet No(s).: 9¢ f/e n REINFORCING STEEL Q SAMPLED /TAGGED reirtbndrig steel from • Size(s)iHeat HranberlE O Inspected the placement of refrdordng steel ter the at the following locations: • NOTES El DISCREPANCIES ❑ % COMP E _ _ // c_ .-7—f / /1 -3f ter 2z e 3 deP ,7 • %' o,-.7c,,. 'e,4. 'ee:://a;fz),7 d # ,e,,17," ,-- /-e-/a-14.7,Z/ / c--r-47/: To the best of my knowledge, the above WAS NOT performed In accordance with the a• cued plans,specifications, and regulatory requirements Superintendent/Representative: Techni / /2 ,7 - . / / l '- 215 West Dakota Avenue.Clovis,CA 93612 • (559)348-2200 4221 E.8' i Si,Ontario,CA 91761 • (909)974-4400 2205 Coy Avenue,Bakersfield,CA 93307 • (661)837-9200 43379 . . ss Park Dr.,Ste.300,Temecula,CA 92590 (931)694-0601 448 Mitchell Rd.,Ste.C.Modesto,CA 95354 • (209)572-2200 922 Valley Ave NW,Ste. 101,Puyallup, WA 98371 •• (253)939-2500 6711 Sierra Court Ste.B,Dublin, CA 94568 • (925)307-1160 1230 Finn Hill Road NW,Ste.A,Poulsbo, WA 96370 (360)598-2126 5044 Bailey Loop,McClelbn,CA 95652 • (916)564-2200 11715 N Creek Pkwy South,Ste.C106,Sof hell, WA 98011 • (425)485-5519 2979 W.Fairmount Avenue.Phoenix,A2 65017 • (602)265.7090 1161E1.Montgomery Dr.,sit 31,Spokane Valley,WA 99706 • (509)534-9711