09110031Acrylic An Acrylic Latex Sealant Product Description TREMstop Acrylic is a gunnable acrylic latex sealant designed for use in firestop applications, including both joints and through -penetrations. Basic Uses TREMstop Acrylic is for use on metal pipe, plastic pipe, insulated pipe, cables, cable trays, ducts, static joints and dynamic joints in fire -rated concrete, wood floor/ceiling and gypsum wall assemblies. TREMstop Acrylic can also be used on sound rated assemblies. Features and Benefits TREMstop Acrylic is an easy to apply, all-purpose sealant that accepts paint once fully cured. It features excellent movement and superb unprimed adhesion to a wide range of substrates. When installed in accordance with a tested firestop system, it affords code compliance for both through -penetrations and fire -rated joints. Applicable Standards UL 1479 (ASTM E-814) UL 263 (ASTM E-119) UL 723 (ASTM E-84) UL 2079 (ASTM E-1966) ASTM E-1399 CAN4-Sl l 5M CAN/ULC-5101 M Packaging 10.1 oz (300 mL) cartridge, 20 oz (600 mL) sausage, 28.7 oz (850 mL) quart cartridge, 5 gal (19L) pail Color Rust Red,`Whit2, Limestone. Custom colors available upon request. Availability TREMstop Acrylic is readily available from your local Tremco Distributor or Sales Representative throughout the United States and Canada. DryTime At 77°F (250C), 50% RH, TREMstop Acrylic is tack free in 30 — 60 minutes and dries at a rate of about 1/8" per day. As the temperatures decrease, the dry time of TREMstop Acrylic will increase, generally one additional day for every 10°F decrease in temperature. Surface Preparations For good adhesion, the substrate must be sound, clean and dry. Any surface damage, dirt, dust, loose particles or other contaminants that may inhibit adhesion must be removed from the surfaces prior to application of the sealant. Tremco recommends that surface temperatures be 40°F (5°C) or above at the time the sealant is applied. If sealant must be applied in temperatures below 40°F, please refer to the Tremco Guide for Applying Sealants in Cold Weather that can be found on our web site at www.tremcosealants.com. r( I �1 Priming Priming is not required. n � n l� Joint Design TREMstop Acrylic has been successfully tested in one, two, three, and four hour fire -rated joints when applied at a thickness of 1/4" (6.3 mm) over proper backing materials. R_F�' Please refer to the appropriate firestop system for proper installation. For a list of Tremco systems, please visit www. tremcosealants.com/commercial/firestop. (� Joint Backing Mineral wool, closed cell, or reticulated polyethylene backer rod is recommended as joint backing to control sealant depth and insure intimate contact of sealant with cavity wall when tooling. Certain types of backing material may be required by system. For additional information on firestop system components, please visit www.tremcosealants.com/commercial/ firestop. Application/installation TREMstop Acrylic is used in firestop systepv— 0 sop at" assemblies. It is easy to apply using conventional caulkirf equipment. NOV 0 5 2009 Clean Up Excess sealant and smears can be cleaneMrremoved-with— soapy emoved withsoapy water before sealant skins. Any utensils used for tooling can also be cleaned with soapy water. Limitations • Not recommended for use with passive fire containment systems not listed or approved by Tremco. Warranty Tremco warrants its Firestop Materials to be free of defects, but makes no warranty as to appearance or color. Since methods of application and on-site conditions are beyond our control and can affect performance, Tremco makes no other warranty, expressed or implied, including warranties of MERCHANTABILITY and FITNESS FOR A PARTICULAR PURPOSE with respect to Firestop Materials. Tremco's sole obligation shall be, at its option, to replace or to refund the purchase price of the quantity of the Firestop Materials proved to be defective and Tremco shall not be liable for any loss or damage. www.tremcesealants.com Page 1 of 3 Commonly UsedTremco Systems System No. FF -D-1085 System No. FW -D-1069 August 19, 2008 August 19, 2008 Assembly Rating — 2 Hr Assembly Rating — 2 Hr L Rating at Ambient — Less than 1 CFM/Lin. Ft. L Rating at Ambient — Less than 1 CFM/Lin. Ft. L Rating at 400' F — Less than 1 CFM/Lin. Ft. L Rating at 400' F — Less than I CFM/Lin. Ft. Nominal Joint Width — 3 In. Nominal Joint Width — 31n. Class II Movement Capabilities — 33% Compression and Extension Class II Movement Capabilities — 33% Compression and Extension (ULIcUL) (ULIcUL) TYPICAL PHYSICAL PROPERTIES Property Test Method Results Flame Spread ASTM E-84 15 Smoke Develop ASTM E-84 0 STC Rating ASTM E-90 Restored to 56 in a U411 Wall Movement Capability UL 1079; class I, II, III +/-33% pH . 7-9 VOC Content EPA Method 310 35 g/L Shelf Life 116111 Min. 1 year when stored at 40°-100T (5'-43'C) Hardness; Shore ASTM C-2240 15-20 Peel Strength, pli ASTM C794 _ 15-25 substrate dependent Antifungal Contains antifungal additive Commonly UsedTremco Systems System No. FF -D-1085 System No. FW -D-1069 August 19, 2008 August 19, 2008 Assembly Rating — 2 Hr Assembly Rating — 2 Hr L Rating at Ambient — Less than 1 CFM/Lin. Ft. L Rating at Ambient — Less than 1 CFM/Lin. Ft. L Rating at 400' F — Less than 1 CFM/Lin. Ft. L Rating at 400' F — Less than I CFM/Lin. Ft. Nominal Joint Width — 3 In. Nominal Joint Width — 31n. Class II Movement Capabilities — 33% Compression and Extension Class II Movement Capabilities — 33% Compression and Extension (ULIcUL) (ULIcUL) llltll llilll ° Illlll llilll. � ' Illlll Illlll Illlll Illlll ° � , lll�l llltll •� �°. .. ill• l llilll ° - ' 111 Il llilll ° � 2 3g e, n J . ' llltll Illlll a �� Illlll Illlll . n °<.� Illlll Illlll '. ' Illlll Illlll 1111 1 111111 111#1 Illlll It IIItl a a 4 3A System No. WW -D-1077 August 19, 1008 Assembly Rating — 2 Hr L Rating at Ambient — Less than 1 CFM/Lin. Ft. L Rating at 400" F — Less than 1 CFM/Lln. Ft. Nominal Joint Width — 3 In. Class II Movement Capabilities — 33% Compression and Extension (ULIcUL) 08 > IL v . Illlll iltill Illlll llll .� J Illlll llltll � ' IItIJt 11111 . 111' 1 I!!iil ` 1 llltll llilll ° Illlll llilll. � ' Illlll Illlll Illlll Illlll ° � , lll�l llltll •� �°. .. ill• l llilll ° - ' 111 Il llilll ° � 2 3g e, n J . ' llltll Illlll a �� Illlll Illlll . n °<.� Illlll Illlll '. ' Illlll Illlll 1111 1 111111 111#1 Illlll It IIItl a a 4 3A System No. WW -D-1077 August 19, 1008 Assembly Rating — 2 Hr L Rating at Ambient — Less than 1 CFM/Lin. Ft. L Rating at 400" F — Less than 1 CFM/Lln. Ft. Nominal Joint Width — 3 In. Class II Movement Capabilities — 33% Compression and Extension (ULIcUL) 08 A) 29) Page 2 of 3 IL v . Illlll iltill Illlll llll .� J Illlll llltll � ' IItIJt 11111 . 111' 1 I!!iil ` 1 116111 Illlll > A) 29) Page 2 of 3 System No. HW -D-0017 March 12, 2004 Assembly Rating — 2 Hr Nominal Joint Width — 1 In. Class II and III Movement Capabilities — 25% Compression (UL/cUL) System No. HW -D-1072 August 19, 2008 Assembly Rating – 2 Hr L Rating at Ambient – Less than 1 CFM/Lin. Ft. L Rating at 400' F – Less than 1 CFM/Lin. Ft. Nominal Joint Width – 3 In. Class II Movement Capabilities – 33% Compression and Extension (UL/cUL) System No. HW -D-0256 September 13, 2006 Assembly Ratings - 1 and 2 hr (See Items 2 and 3) Nominal Joint Width - 112 in. Class II and III movement capabilities - 25 %compression or extension (See Items 2 and 3) (UL7cUL) -, C1 >/ —zT 1 �I �1 t SECTION A -A i "_-; L— A System No. HW -D-0016 July 22, 2005 Assembly Ratings – t and 2 Hr (See Item 2) Nominal Joint Width – t In. Class II and III Movement Capabilities – 25% Compression (See Item, (UL/cUL) i 4�pss)s�Fo PEN TRATION FIILL, VOID OR ARESTOP SYSTEMS AND/OR OINTVITY MATERIAL FOR USE IN OUGH- ouL. C u` OS SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY An TO Company NoV 0 5 2009 Tremco Commercial Sealants & Waterproofing 3735 Green Road, Beachwood, OH 44122 /1 Phone: 216.292-5000 // 800.321.7906 220 Wcksteed Avenue, Toronto, ON Milli 1G7 I1 Phone: 416.421.3300 /1800,363.3213 1451 Jacobson Avenue, Ashland OH 44805/1 Phone: 419.289.2050 // 800.321.6357 www.tremcosealants.com 0309/TSAPDS Page 3 of 3 NE„ FRAME, WHITE NEW DOOR, WHITE , VISION -LITE THROUGH -BOLT HEAD, TYP. SS DOOR PULL O n DOOR LL EQ., \ N U INACCORDAN(1 NJIIH THE CUPERTINO CO 'S AND ORI EQ. 1' TE 3"r rhis set or phiVs—adtlspecilicatic be kept on the job at all times .: •-awful to make any changes or ,n same without written permis; Building Department. City of 1 3 .tamping of this plan and spe ''ALL NOT be held to permit or (_q ., roval of the vrolahon of any p ,I any City Ordinance a Start 1 3'- 61/2" EDGE OF DOOR TO EDGE OF DOOR V.I.F 2 TYPICAL SPRAY BOOTH DOOR ELEVATION SCALE: WC - T -W MITERED KNOCK -DOWN REPLACE DOOR FRAME EXISTING ---------------------------------- -------------- 1 -HR ----- RATED NEW FULL -MORTISE _-________ ,'`rJ DOOR HINGES, REMOVE --' EXISTING HINGES -, NEW DOOR SADDLE 2g . I .acct:: Ir=ra• - - -; I I ------------ r ,E: OF ICES •------ -------- -----"- L �' VISION PANEL FRAME EDW h' `DOOR IUSTFIRE RATED .SA_DDLE lis itions SEALANT C rom ;"tio s LAMINATED /SOVkzb �5 can FIRE -RATED BY: 200S '°"s GLASS v s � 2 REPLACE �—NEW DOOR - EXISTING SADDLE Sim. 1 -HR SPRAY BOOTH PLAN RATED 1suLe: v.•=1a DOOR Supplemental Drawing 6 Apple Computer - Industrial Design Studio DAR ARcy�'F Field Order 45 D� 6/30/2009 aebrem Drewbq Rabam oasso 2 Infinite Loop Cupertino, CA v JON C. Bohlin Cywinski Jackson I D®w9g Deeplptl Dmwbrp Nu r Architecture Planning Intenor Design 49 Geary Street, Suite 300 N 1 New S ra Booth Doors: Plan and Elevation p Y ASK -89 San Francisco, California 94108 tel: 415-989.2100 (":415.989-2101 2 354 ---------------------------------------------------------------------------------- II 211 a 2/�Z SPRAY BOOTH PLAN DETAIL scAtF. e• = ro- EXTENT OF REFRAMED WALL AREA FULL-MORTISE HINGE NEW SS DOOR PULL. TYP. REVEAL SMOKE SEAL, TY NEW SINGLE RABBET DOOR FRAME. WHITE NOTES i. REFRAM=D GWB AND STUD WALL AREA, DOOR FRAME AND SPRAY BOOTH INTERIOR WALL ARE TO BE P UMB AND PARALLEL TO ALLOW FOR A CONSISTENT �' FIRE SEAL. GWBOWALL F EW7yp CLOSED. TO ALIGN WITH EXTERIOR '/4" FIRE-SEALANT,WHITE EXISTING SPRAY BOOTH METAL PANEL WALL NEW �/8" CHANN L, PAINT WHITE, RIVET INSTALL !1 EXISTING DOOR ANGLE FRAME � AND PANEL IRA= ,< FLANGE TO NEW DOOR—,,,EXTENT OF BYPREMOVED, rr IN SADDLE REFRAMED WALLcE AREA xVED NOV 0 5 2009 — ALIGN ----- ----------------I `i I I— ALIGN $Y• AS SPRAY BOOTH DOOR PLAN NECESSARY 2i/Z" STUD 21/2" C -H STUD Supplemental Drawing aSEp AR 'A Gk. �` 1w mr Field Order 45 Dem 06/30/2009 a.re.� o aneg �rem� v J kC olaxo Bohlin Cywinski Jackson D.*M [M=fipe Drewmg PfumW, Architecture Planning Interior Design Architecture Lt%71A New Spray Booth Door + Frame 49 Geary Suite uite 300 uitmie Sen Francisco, 04108 lel: 415-999-2100 Iex:415-999-2101 1M TYPICAL SPRAY BOOTH DOOR INTERIOR ELEVATION 2 SCALE', 31V a V -V -LITE JGH-BOLT TYP. CAP CHANNEL METAL DOOF FACE NEOPRENE DOOR SHOE FULL SCALE FASTENER DOOR BOTTOM CHANNEL NEW DOOR SADDLE TYP. NOTCH FRAME AND CAP CHANNEL BEYOND FOR DOOR SADDLE ?' - o IYL... D O O R SADDLE 3 SPRAY BOOTH DOOR BOTTOM SECTION SCALE: 6' - 1'-0' By NOV 0 52009 E� DOOR CLOSER NEW LOCATION OF LIMIT SWITCH MATCH EXISTING DIM t SPRAY BOOTH DOOR THRESHOLD RCP SCALE: N4'- 1'-0' EXISTING LIMIT SWITCH Supplemental DrawingD AR ��SE Cy�Tc� Apple Computer - Industrial Design Studio .� JON o, Is d for Field Order 45 D� 6/30/2009 Reeerce OA4p Reeam ori 2Infinite Loop Cupertino, CA CK ON - Bohlin Cywinski Jackson DMMW D,rsaiptl DraWr,p N=Wr C27354 Architecture Planning Interior Design Mt�xF New Spray Booth Doors: Int. Elev., RCP, Details P y ASK -91 49 Geary Street, Suite 300 03 31pct Sen Francisco. Celilomia 94108 tel: 415-989-2100 fm:415-989-2101 �F CAMEO Subject: Evaluation for the modification of the AFC Finishing, Model SDDX 1208CSB Paint Spray Booth to the requirements contained in the Standard for Spray Application Using Flammable or Combustible Materials (NFPA 33 -Issue: 08/17/06, Ed:2007). Dear Mr. Daniel, This letter concludes our evaluation the above referenced equipment to the requirements contained in the Standard for Spray Application Using Flammable or Combustible Materials (NFPA 33 -Issue: 08/17/06 Ed:2007). The equipment was installed and evaluated at the installation site: Apple Computer Industrial Design Studio 2 Infinite Loop Cupertino, CA. The Scope of the project is to verify the modifications to the Listed AFC Finishing Inc. Model SDDX 1208CS6 Paint Spray Booth.; The modifications involves the changes to the existing doors of the Paint Spray Booth. The door interlocks were also re -installed to the modified doors. Attached are copies of the modification drawings. After verifying the actual modifications to the referenced equipment. It was determined that the equipment continues to meet the requirements of the referenced Standard. The evaluation was authorized by Quote No. Q500142314 and P.O. # 144398, dated 03/31/09. The modified equipment was evaluated the installation site indicated above. This completes our evaluation covered by Intertek Project No 3177330. Completed by: Ernie Fernandez Title: Sr. Staff Engineer Signature: Date 01/04/2010 Reviewed by: 0 9110.0 31 Title: Technical Manager Signature Menlo Park. CA 94025 Date: 01/04/2010 Telephone- (650) 463-2900 Facsimile: (650) 463-2910 www. mtertek-etlsemkoCom January 4, 2010 Letter Report No. 317733OMPK-001 LTR ® Project No. 3177330 Mr. Chris Daniel Ph: (408) 792-2292 ICOM, Inc. 477 Burke Street s Fax: (408) 292-4968 /p Email: chrisd@icominc.com San Jose, CA 95112 USA /Q Subject: Evaluation for the modification of the AFC Finishing, Model SDDX 1208CSB Paint Spray Booth to the requirements contained in the Standard for Spray Application Using Flammable or Combustible Materials (NFPA 33 -Issue: 08/17/06, Ed:2007). Dear Mr. Daniel, This letter concludes our evaluation the above referenced equipment to the requirements contained in the Standard for Spray Application Using Flammable or Combustible Materials (NFPA 33 -Issue: 08/17/06 Ed:2007). The equipment was installed and evaluated at the installation site: Apple Computer Industrial Design Studio 2 Infinite Loop Cupertino, CA. The Scope of the project is to verify the modifications to the Listed AFC Finishing Inc. Model SDDX 1208CS6 Paint Spray Booth.; The modifications involves the changes to the existing doors of the Paint Spray Booth. The door interlocks were also re -installed to the modified doors. Attached are copies of the modification drawings. After verifying the actual modifications to the referenced equipment. It was determined that the equipment continues to meet the requirements of the referenced Standard. The evaluation was authorized by Quote No. Q500142314 and P.O. # 144398, dated 03/31/09. The modified equipment was evaluated the installation site indicated above. This completes our evaluation covered by Intertek Project No 3177330. Completed by: Ernie Fernandez Title: Sr. Staff Engineer Signature: Date 01/04/2010 Reviewed by: Paul Breder Title: Technical Manager Signature Date: 01/04/2010 Page 1 of 1 This report is for Ne exdmi" use of Intertek's Client and is provided pursuanl to the agreanent between Intertek and its Glen. Intertek's responaibibty and liablity am hinted to Ne tame and xind bons of Ne agreement. Intertek assumes no liability to any parry, other than to Ne Client in accordance win Ne agreement, for any loss, expense or damage occasioned by Na use M We report Only Ne Client is authorized to permit copying or distnbuton of this report and Nen otly in its enbrey. Any use of the Inlenek name or one Was marks for Ne sale or advertaament of Na tested materiel, Product or service must first be approved in wnbng by Intertek The obsemabom and lest results in Nis report are relevant only no sample tested This report by itself does not Imply Nat Na material, product or sera® is or has ever been under an Intedek rerascaaon program Intertek Testing services NA, Inc. .SD 12.1.2 (6/19/06) Informative U U&A C E r:o. (TE / C53 O BEAD saero••e r-\ ~e Tm monr \l.0 — . so worn ASN- WIYAOB BmF CY*IA 1� a�r� m��yemr�is r�.�ae�•m vniara�o� sw"tlami DM-F�- DOCR CLOSER in T [EDGE OF END C-ANNEL TO EDGE 0: END C-:ANNEL W7i EUV m coon WlElIX1R IlfV1IlON `. ra %[.`N CHMNEL, RIVET CONNECTIONS iN TCH f SWITCH �I, $RMVmrH ODOR iRRE5R0.0 ACP `. .> I— Apple Computer - Industrial Design Studio �,�. ° Dwr PLdI rnenoou ] FRb lqp ppq¢ G W SNAP B"NO : PIN"am jo, N O_ W NEW —NEW FRAME, PAINT PANT THROUGH BOLT — HEAD. TYP. NEW PULL (2 rwrx aaAr moix oaw EEtv�nox VIIERED 3NCCK-DCW'N DOOR FRAVE NEW FULL -MORTISE SINGES, REMOVE E%ISTING HINGES SS VIS'ON PAN FRAME FIRE - RAT - D SEALA\T - LAVNATED FIRE -RA -ED CLASS /,l SMY 800� aux a�+0 M• PLC b Apple Computer - Industrial Design Studio opoan I DO0` y`YO0° a'ry� Yam �� `b/Si�eY BO]l+D�v6' am," EJovtIT M Ir�Y,S4l�M�O Yk��fOSm Q�,f�)ia�