12080189CITY OF CUPERTINO BUILDING PERMIT
Ii1111.DING ADDRESS: 20650 VALLEY GREEN DR
CONPRACFOR: STATEWIDC ROOFING
PERMITNO: 12080189
INC
OWNEWSNAME: SI50LI.0
5542 MONTEREY RD
DATE ISSUED: 08 /172012
OWNER'S PIIONF: 4089961010
SAN JOSE, CA 95138
PlIONE NO: (408)288 -8680
❑ LICENSEID CONI'RACI'OR'S DECLARATION
.1011 DESCRIPTION: RF.SIDEls"HAL El COMMERCIA1
( Z 6
License Class Lie. N
�-- 2 �i
COMM. RE -ROOF 29,900 SQ FT INSTALL 60 MILL TPO
G �9
Contactor -- rf">�`Q.�tf� F\..r� Date `6 I
SINGLE PLY OVERLAY ROOFING SYSTEM
hereby affirm that I am licensed under the provisions of Chapter 9
(commencing with Section 7000) of Division 3 of the Business & Professions
Code and that tar license is in full force and effect.
I hereby affirm under penalty of perjury one of the following two declarations:
I have mud will maintain a certificate of consent to self-insure for Worker's
Compensation, as provided for by Section 3700 of the Labor Code, for the
Sq. FI Floor Area:
Valuation: $29900
performance of the work for which this permit is issued
1 have and will maintain Worker's Compensaion Insurance, as provided for by
Section 3700 ofthe Labor Code, for the performance of flue work for which this
AI'N Number: 32610053.00
OecupanO. Type:
permit is issued.
APPLICANT CERTIFICATION
I certify that I have read tliis application and state that the above information is
PERMIT EXPIRES IF WORK IS NOT STARTED
correct. I agree to complywith all city and county ordinances mid state laws relating
WITHIN 180 DAYS OF PERMIT ISSUANCE OR
to building construction; and hereby authorize representatives of this city to enter
upon the above mentioned property for inspection purposes. (We) agree to save
180 DAYS FROM LAST CALLED INSPECTION.
indemnify and keep harmless the City of Cupertino against liabilities, judgments,
costs, and expenses which may aceme against said City in consequence of tie
Issued by: ! % / ` Date: U 2
granting of this permit. Additionally, the applicant understands and will comply
with all non-po source regulatims p c he Cupertino bunicipal Code, Section
9.18.
I2P: ROOFS
Signature Date? 2
All roofs shall be inspected prior to any roofing material berg installed If u roof is
installed without first obtaining an inspection, I agree to remove all new materials for
inspection.
❑ OWNER-BUILDER DECLARATION
/•!�"�'`
Signature of ApplicthnC ` -C L/ tea[,
I hereby affirm that 1 um exempt from the Contractor's License Law for one of
/ (
the following boo reasons:
ALL ROOF COVERINGS "r0 ta" .ASS "A" OR 11 VI-1 ER
1, as owner ofthe property, or my employees with wages as their sole comfunsation,
will do the work, and the structure is not intended or offered for sale (Sec.7044,
Business d Professions Code)
I, as owner ofthe property, am exclusively contracting with licensed contractors to
11\%\RDOIIS MATERIALS DISCLOSURE
construct the project (Sec.7044, Business & Professions Code).
I have read the hazardous materials requirements under Chapter 6.95 of the
California Ilealth & Safety Code. Sections' - 5505.25533, and 25534. 1 will
1 hereby affirm under penalty of perjury one of the following three
maintain compliance with the Cupertino Municipal Code. Chapter 9.12 and the
declarations:
Ilealth & Safety Code. Section 25532(x) should I store or handle hazardous
I have mid will maintain a Certificate of Consent to self-insure for Worker's
material. AJditionally..should 1 use equipment or devices which emit hazardous
Compensation, as provided for by Section 3700 ofthe Labor Code, for the
air contaminants as defined by the Isay Area Air Quality Management District
performance ofthe work for whichthis permit is issued.
will maintain compliance with the Cupertino Municipal Code, Chapter 9.12 and
I have and will maintain Worker's Compensation Insurance, as provided for by
Section 3700 ofthe Labor Code, for the performance of tin work for which this
(he Ilydlh & Safety Code, Sect Its 25505, 255" 1 iJ 25534.
/2
Owner or authorized agent--^ Date:
permit is issued.
I certify that in the performance ofthe work for which this permit is issued, I shall
not employ any person many manner so as to become subject to the Worker's
Compensation laws of California. If,, after making this certificate of exemption, I
CONSTRUCHON LENDING ACH;NCI'
become subject to the Worker's Compensation provisions of the Labor Code, I must
I hereby affirm that there is a construction lending agency for the performance of
forthwith comply with such provisions or this permit shall be deemed revoked,
work's for which this permit is issued (Sec. 3097, Civ C.)
Lender's Name
.U'I'LIC. \N I'CI ?R'I'IPIC. \'1'10N
Lender's Address
1 cenifv that I have read this application and state that the above information is
correct. I agree to comply with all city and county ordinances and state Imes relating
to building construction, and hereby authorize representatives of this city to enter
upon the above mentioned property for inspection purposes. (We) agree to save
indemnify and keep harmless the City of Cupenino against liabilities, judgments,
,U2CI11'I'F:('I "S I1F.CLAIL \'f10N
costs, and expenses which may accrue against said City in consequence of the
I understand my plans shall be used as public records.
gaming of this permit. Additionally, the applicant understands and will comply
with all non -point source regulations per tat Cupenino Municipal Cade, Section
Licensed Professional
9.18,
Signature Date
CITY OF CUPERTINO
FEE ESTIMATOR - BUILDING DIVISION
W
20650 valleuy green dr.
IAPN:
DATE: 08117/2012
REVIEWED BY: bobs.
NADDRESS:
Plumb. Permit Fee:
BP #:
'VALUATION:
$29,900
'PERMIT TYPE: Building Permit
PLAN CIIECR TYPE: Alteration / Addition / Repair
PR11 LAR1'
USE: Commercial Building
Elect Insp. I, ew:
PENTA MATION
PERMITTYPE: 1COMMLROO i
WORT:
install a 60 mil TPO single ply overlay roofing system.
SCOPE
$0.00
NOTE: This estimate rocs not include fees due to other Departments (i.e. Planning, Public Works, Fire, Sanitary Sneer District, School
District, etc.). These lees are based on the prelindnan• information available and are mill, an estimate. Contact the Dent for aildn'I info.
FEE ITEMS (Fee Resolution I/- Eff 7 /l /!U
Nech. Plan Check
Plumb. Plan Check
Elec.. flan Check
Wech. Permit Fee:
Plumb. Permit Fee:
Efec. Permit Fee:
Other ,ilech. tarp.
Other Plumb Inep.
Other Etc,,. Lisp. El
Mech. lay. Few:
Plumb. Inp. Fee:
Elect Insp. I, ew:
NOTE: This estimate rocs not include fees due to other Departments (i.e. Planning, Public Works, Fire, Sanitary Sneer District, School
District, etc.). These lees are based on the prelindnan• information available and are mill, an estimate. Contact the Dent for aildn'I info.
FEE ITEMS (Fee Resolution I/- Eff 7 /l /!U
FEE
QTY /FEE
MISC ITEMS
Plan Check Fee:
$0.00
29,900 S. f..
$2,037.00
Re roof
IRF-ROOFC0,11
Suppl. PC Fee: (D Reg. Q OT
0.0
-its-
$0.00
PME Plan Check:
$0.00
Permit Fee:
$0.00
Suppl. Insp. Fee:Q Reg. Q OT
1 0.0
1 hrs
$0.00
PME Unit Fee:
$0.00
PME Permit Fee:
$0.00
Construction Tax:
Administrative Fee:
O
E)
Work Without Permit? 0 Yes 0 No
$0.00
Advanced Plannine Fee:
$0.00
Select a Non - Residential
Building or Structure
G
0
i
Trace/ Docutnenmrion Fees:
Strong Motion Fee: IBSEISAIICo
$6.28
Select an Administrative Item
Blda Stds Commission Fee: IBCBSC
$2.00
SUBTOTALS:
$8.281$2,037.001
TOTAL FEE:
$2,045.28
Revised: 07/01/2012
Electrical
Excavation
CUPERTINO
REROOF PERMIT APPLICATION
COMMUNITY DEVELOPMENT DEPARTMENT • BUILDING DIVISION
10300 TORRE AVENUE • CUPERTINO, CA 95014 -3255 Q OI
(408) 777 -3228 • FAX (408) 777 -3333 • buildino(7a cuoertino.oro \ 00
PROJECT ADDRESS 20650 Valley Green Drive
APNp Z(p 10 x.53
OWNER NAME Apple, Inc.
PHONE 408- 996 -1010
E.MAII.
STREHrADDRF_SS 1 Infinite Loop
CITY, STATE ZIP Cupertino, CA 95014
FAX
CONTACT NAME Mike Courtney
PHONE
E -MAIL
STREhTADDRFSS
CITY, STATT ZIP
FAX
❑ OWNER ❑ OWNFA- BUIDER ❑ OWNERAGDIT Lt CoN1RACr0R ❑ CON RALTOR AGI'XT ❑ ARCFNn:Cr ❑ ENGIND'R ❑ DEVELOPER ❑ TENANT
CONTRACTOR NAME Mike Courtney
LICFNSENUMBER 803926
LICENSE TYPE C39
BUS. LIC.H
COMPANYNAME Statewide Roofing, Inc.
E -MAII- mbotill @swroof.net
FAX 408- 286 -7820
SI'REITADDRESS 5542 Monterey Road, #201
CITY,STAmziP San Jose, CA 95138
PIIONE408- 286 -7828
ARCHn'ECmNGINEER NAME N/A
LICENSE NUMBER
BUS. LIC. 0
COMPANY NAME
E -MAIL
FAX
STREETADDRTS.S
CITY, STATE ZIP
PHONE
USE OF ❑ SI'D or Duplex ❑ Multi - Family
STRUcrum: [N Commercial
ROOF ARM:
29,900 sf
VALUATION:
$87,000
EXISTING ROOFTYPE IKBUILT- UPROOF ❑ASPHALTSDINGLES ❑WOODSIIAKES 0WOODSHINGW3 ❑OTIIF:R(SPFCIP\)
REmovrmEPLACE OYES
L'l NO
IF NO.
I H LAYERS:
PLYWOOD ❑ Y." ❑ _
THICKNESS: ❑ W
PLYWD ❑ OSB
"TYPE. ❑ COX
PI'rCIE
—:12
ROOF
CLASS: A
,yy
PROPOSEDROOFTYPE ❑BUILT- UPROOF ❑ASPHALTSHINGLES 13 WOOD SHAKES 11 WOOD SHINGLES ff OIT11:R Overlay
ITC -ES REPORT#
DESCRIPTION OF WORK: Install a 60 mil TPO single ply overlay roofing system.
By my signature below, I certify to each of the following: I= the property owner or authorized agent to act on the property owner's behalf. I have lead this
application and the information I have provided is correct. I Description of Work and verify it is accurate. 1 agree to comply with all applicable local
ordinances and state laws relaim g co ze representatives orCuperlino to enter the above- identi lied properly for inspection purposes.
Signature of ApplicanUAgcnt: Date: 8/15/12
SUPPLEMENTAL INFORMA'T'ION RE -
_ If building is associated with a I lome Owner's Association, provide letter
of approval from I -IOA.
PTOVI 'Plannl0g approval f0 VCDIy If there tiny restrictions.
rovldc copy of Manufacturer's Installation Specifications.
-.' Frovide signed copy of Cupertino's Tear -Off Policy.
OFFICE
USE ONLY '
PI1 N CHECK 1YPF.
SRoIrri,CC SI.EP
Q— rrvER= rIIE -r.o IjN t :R
❑ 41 \PREtiti
❑ s•rANDARo
, �
n BIBI,IIING PIAN REVIEW
❑ PIANNIh'C PL \N RE \'IF. \ \'
❑ FIRF. DKPr
❑ oIT1ER:
Reroofilpp_201l.doc revised 03116111
44F.
NEW CONSTRUCTION
, - I
90=
�G6a
rrF
E • r
CARLISLE'S
1 pical Application
OSure -Weld Reinforced
Membrane
® Carlisle Fasteners and Plates
Acceptable Insulation
® Approved Roof Deck
System features and benefits include:
saw • Ileac- weldable membranes
�,- _ = •O ` h— (((�� • Iligh wind uplift performance
• Ilail and high puncture resistance
I L • Top ply membrane thickness adds improved
' long -teen weatherability and durability
• Sure-Weld membrane meets
FARGY STAR° guidelines
�Ci�, IT Sure -Weld Membrane for Mechanically- Fastened
i.E) Systems is available in the following:
AUG 1 g 2012 Colors: white, Grae,'lan
Thickness (mils): 45, 60, i? and SO
Standard Widths: 6', 3', 10' and 12'
Standard Lengths: 100'
FOR TEAR OFF OPTIONS REFER TO NEW CONSTRUCTION ABOVE. ' Reler to Carlisle's Sure -Weld Design Criteria Portion
For current Code Approvals and Warranties, visit Carlisle's wehsite, of the Current Specification
or contact a Design Analyst.
SML,,l ROOFING AMERICA: OVER 40 YEARS AND 10 BILLION SQUARE FEErT.
/ BoSpree 80O -4-SY C P.O. 00C Incorporated 013
www.carlisle- syntec.com Fax:717.2aF71G3
markelOWlee.arlesle.com
Carlisle SynTec Incorporated
NEW CONSTRUCTION
REROOFING
90=
�G6a
rrF
E • r
r &
r
11
rrE
�`{�,t,,C{�
I173u13�'I7•F' '
rF
DECK OVE N7
INSULATION
NO
NO
HP MAT
INSULATION
INSULATION
NO
INSULATION
*REFER TO
REQUIRED IflEO
SPECS
RECOMMENDED
CARLISLE POLYISO, CARLISLE HP RECOVERY BOARD OR
f REFER TO NEW CONSTRUCTION
INSULATIONS
CARLISLE HP RECOVERY BOARD OVER POLYSTYRENE
INSULATION
CARLISLE FASTENERS AND PLATES
f REFER TO NEW CONSTRUCTION
ATTACHED BY
HIM
Fin
MEMBRANE
FASTENERS/
PIRANHA
FASTENERS/
RPANHA
LT.WT. DECK
CD -ID/
PIRANHA PLATES;
HP -X
FASTEIIERSI
I.T.W.
DECK
ATTACHED BY
PLATES:
HPXTPA FAST/
PLATES;
HPXTRA FAST/
FASTENERS/
PLATES
HO 1140
PIRANHA
FASTENERS/
TO NEW CONSTRUCTION
NHANHA
PIRANHA
FASTENERS
PLATES
PLATES
XTRA PLATE
XTRA PLATE
FOR TEAR OFF OPTIONS REFER TO NEW CONSTRUCTION ABOVE. ' Reler to Carlisle's Sure -Weld Design Criteria Portion
For current Code Approvals and Warranties, visit Carlisle's wehsite, of the Current Specification
or contact a Design Analyst.
SML,,l ROOFING AMERICA: OVER 40 YEARS AND 10 BILLION SQUARE FEErT.
/ BoSpree 80O -4-SY C P.O. 00C Incorporated 013
www.carlisle- syntec.com Fax:717.2aF71G3
markelOWlee.arlesle.com
Carlisle SynTec Incorporated
CARLISLE'S
SURE -WEB®
The Sure -Weld Mechanically -
Fastened hoofing System now
offers wider membrane
options: 6, 8', 10' and 12'.
y- Fasten :d
• Sure - Weld's « Ilectivity values exceed
other heat- welded membranes
• Membranes are eco- friendly as they do not
contain chlorine or plasticizers
• Sure - Weld's top -ply surface is thicker and smoother
than other membranes in the market, providing
better welding results and reduced din pickup
System Codes
Project Information • UI. Class A. Band Universal Slope ratings are available
This Sure -Weld Roofing System is being installed for the project named over anv deck type
below: • FM Uplift values up to 135 psf can be achieved
name:
cirv:
stale:
The Carlisle Authorized Roofing Contractor is:
company name:
address:
ciw:
state:
zip:
Installation
Carlisle's Sure -Weld Mechanically- Fastened Roofing System utilizes
white, gray or tan membranes in standard reinforced 45- or 60 -mil
thickness- or 72- or 80 -mil thick reinforced Sure -Weld EXTRA"
Insulation is mechanically fastened to an acceptable roof deck. Sure -Weld
membrane sheets are mechanically fastened to the deck Hill Carlisle 11M
or I U'Stra Fasteners and appropriate Piranha Plates. Adjoining sheets are
overlapped and joined together with a minimum I %" aide hot air weld.
The above information represents a typical Carlisle Sure-Weld
Mechanically- Fastened Roofing System. Refer to Carlisle's published
specifications and details for more complete information.
Sure -Weld Membrane Strengths
• Sure -Weld membrane is available in white, gray and tan;
6'-, 8' -, 10'- and 12'- widths
• When tested for puncture resistance. Sure-Weld results were
better than competitive heat weldable membranes (PVC and
Iiypalon)
• Because Sure - Weld's rellectivity values exceed indusup
standards, the membrane meets the criteria for the E A's and
DOE 's ENERGY STAR• Program
For code specifics, refer to Carlisle's SW Code Approval Guide.
Quality Assurance
Carlisle Authorized Roofing Contractors have received training to install
Carlisle's Sure -Weld Roofing Systems.
Inspection
Upon installation completion, and prior to the issuance oft membrane
systeni warranty, an inspection will be conducted by a Carlisle
Technical Representative.
Warranty
Consult your roofing contractor or Carlisle Manufacturer's
Representativ e/Distributor for associated warranty charges.
This system, properly installed and inspected on a commercial project
may receive.
• A 5- or 10 -year Membrane System Warranty; peak gust wind
speed coverage up to 55 mph
• A 10 -year Total System or 15 -year Golden Seal Warramy may be
requested when all materials used for die roofing installation are
manufactured or marketed by Carlisle
• A 20 -vrar Golden Seal \1Warruuv is salable with Sure - Weld's
72- and SO -mil LC RA T1'0 membranes
• Higher wind speed warranties (up to 100 mph peak gust wind
speed) available upon revieny by Carlisle
• A l0 -vear Re ctivity \CWammry (based on 15CIiRG1' STAR° criteria)
available in white mcnibrume
• A 10 -, 15-, 20 -year Puncture Warranty with Sure -Weld 72- 80 -111il
For more specifics or for International warranty programs, contact
Carlisle.
1 WUL \.SSIF /
3ME,,1 ROOFING AMERICA: OVER 40 YEARS AND 10 BILLION SQUARE FEET,.
8UUA�(1� � Carlisle aM S.EWeln, FAST Mhmive REPRINT REQUEST Ceer '�
Q -4 J art CaAale vaJenurin. 600148 - -SW -MF Syslc Subm:aal SAen' -042505
www.carlisle- syntec.COM ENERGY STAR samgk wvxly C2008 Wale SynT%.mmmm Carlisle SynTec Incorporated
amed"USIIMMMm Ponied In USA.
CARLISLE'S
SUREmWELD° REINFORCED
TPO MEMBRANE
Overview
Carlisle Sure -Weld membrane is a premium heat - weldable single -ply
thermoplastic polyolerin (TPO) sheet designed for new roof construction
and re- roofing applications. Sure -Weld High Slope (HS) membrane is
formulated with additional Flame retardant (compared to Standard) for
higher -slope fire code approvals. Sure -Weld EXTRA is 72- and 80 -mil
thicknesses for significantly higher strength and weatherability.
Carlisle's Sure -Weld TPO membrane is based on advanced
polymerization technology that combines the flexibility of ethylene -
propytene (EP) rubber with the heat weldability of polypropylene. All
Sure -Weld TPO membranes include OctaGuard XTTM, an industry-
leading, state-of-the-art weathering package. OctaGuard XT technology
enables Sure -Weld TPO to withstand extreme weatherability testing
intended to simulate exposure to sever climates.
Physical properties of the membrane are enhanced by a strong
polyester fabric that is encapsulated between the TPO -based top and
bottom plies. The combination of the fabric and TPO plies provides
Sure -Weld reinforced membranes with high breaking strength, tearing
strength and puncture resistance. The relatively smooth surface of
Sure -Weld membrane produces a total surface fusion weld that creates
a consistent, watertight monolithic roof assembly. The membrane is
environmentally friendly and safe to install.
Sure -Weld Standard and HS products are available in highly reflective
white, tan and gray, in both 45 -mil and 60 -mil thicknesses. Sure -Weld
E(TRA products (including HS) are available in 72 -mil and 80 -mil
thicknesses in white, gray and tan. Sixteen special colors are also
available (see Carlisle's TPO Color Palette brochure). Available widths
are 4-, 5- and 6 -ft perimeter sheets and 8-, 10- and 12 -ft field sheets.
In Roofing Solaf Eons for Over 45 Years
Carlisle's Sure -Weld tan and white TPO membrane can contribute toward
LEED• (Leadership in Energy and Environmental Design) credits. Tan
and white Sure -Weld are ENERGY STAR°'- qualified and California Titre
24 compliant.
Features and Benefits
• Outstanding puncture resistance
• Chlorine -free with no halogenated flame retardants
• Plasticizer -free; does not contain liquid or polymeric plasticizers
• Excellent low temperature impact resistance
• Excellent chemical resistance to acids, bases and restaurant
exhaust emissions
• Exceptional resistance to heat, solar UV, ozone and oxidation
• Low water vapor permeance and water absorption
• Hot -melt extrusion processed for complete scrim encapsulation
• Warp- knitted fabric (not woven) for smooth surface and greater
thickness over scrim
• Sure -Weld is 100% recyclable
(refer to Carlisle's Recyclability Statement)
Installation
Sure -Weld Roofing Systems are quick to install as minimal labor and
few components are required. The systems may be installed utilizing
labor- saving devices that make sheet welding fast, clean, consistent
and easy to learn, while reducing strain on the roofing technician.
The Carlisle Mechanically Fastened Roof System installation starts
with the insulation fastened with a minimum of 5 fasteners per 4
by 8 ft. board. The Sure -Weld reinforced membrane is mechanically
fastened to the deck using HP -XT"' Fasteners and Piranha PlatesTM
or HP -XTRA Fasteners and Piranha XTRA Plates. Adjoining sheets of
Sure -Weld membrane are overlapped over the fasteners and plates and
joined together with a minimum 114- inch -(4 cm) wide hot -air weld.
The Carlisle Fully Adhered Roofing System application begins
with the insulation fastened at the required density (max.1 every 2
sq ft) necessary to resist the appropriate wind load. The substrate
and membrane are coated with an appropriate Sure -Weld Bonding
Adhesive and the membrane is rolled into place.
CONSULT CARLISLE SPECIFICATIONS FOR COMPLETE
INSTALLATION INFORMATION.
Box 7000 • Carlisle, PA 17013 • Fax: 717- 245 -7053 • www.carlisle- syntec.com
Carlisle SynTec
CARLISLE'S
SUREoWELD REINFORCED
TPO MEMBRANE
Precautions
1. Sunglasses that filter out uttraviolet light are strongly
recommended as tan and white surfaces are highly reflective.
Roofing technicians should dress appropriately and wear
sunscreen to protect skin.
2. Surfaces may become slippery due to frost and ice buildup.
Exercise caution during cold conditions to prevent falls.
3. Care must be exercised when working close to a roof edge when
surrounding area is snow- covered as the roof edge may not be
clearly visible.
Properties and Characteristics'
4. Use proper stacking procedures to ensure sufficient stability
of the rolls.
5. Exercise caution when walking on wet membrane. Membranes
may be slippery when wet.
6. Store Sure -Weld membrane in the original undisturbed plastic
wrap in a cool, shaded area and cover with light- colored,
breathable, waterproof tarpaulins. Sure -Weld membrane that has
been exposed to the weather must be prepared with Weathered
Membrane Cleaner prior to hot -air welding.
Physical Property ASTM 06878 Requirement 45 -mil 60 -mil 72 -mil EXTRA 80 -mil EXTRA
Tolerance an nominal thickness, % 15,-10 -10 - 10 - 10 - 10
Thickness over scrim, in. (mm)
0.012 min
0.018 typ
0.024 typ
0.030 typ
0.034 typ
ASTM 06878 optical method.
(0.305)
(0.457)
(0.610)
(0.762)
(0.864)
average of 3 areas
0.10 max
0.10 max
ASTM E96 uac. B
0.05 typ
0.05 typ
Breaking srergtn. mf W
220 (976 M
225 (1.0) min
250 (1.1) min
350 (la) min
35011.6) min
ASTM 0751 grab method
min
320 (1.4) typ
360 (1.6) typ
400 (1.8) typ
425 (1.9) typ
Elongation break of reinforcement, %
15 min
15 min
15 min
15 min
15 min
. ASTM D751 grab method
25 typ
25 typ
25 typ
25 typ
Tearing strength, lot (N)
55 (245) min
55 (245) min
55 (245) min
55 (245) min
55 (245) min
ASTM 0751 proc. B 8 in. x 8 in.
90 min
130 (578) typ
130 (578) typ
130 1578) typ
130 (578) typ -
Brittleness point, °F ( °q
-40 ( -40) max
-40 (40) Max
- 40(.40) Max
-40 (40) Max
-40 ( -40) max
,ASTM D2137
- 1.0 max
-50 ( -46) typ
. 501-461 ryp
-50 (.46) typ
-50 ( -46) typ
linear dimensional change, %
- 1 max
- 1 max
- 1 max
- 1 max
z 1 max I
ASTM D1204, 6 nouns at 158 °F
particular property of
-0.2 typ
-0.2 typ
-0.2 typ
-0.2 typ
',Ozone Resista al, no cracks 7X
PASS
PASS
PASS
PASS
PASS 1
ASTM 01149. 100 ephm, 168 hm
water absorplum resistance, mass %
- 3.0 max
- 3.0 max
- 3.0 max
e: 3.0 max
c 3.0 max
ASTM 0471 top surface Only
2.0 typ
2.0 typ
2.0 typ
2.0 typ
,166 hours at 158 °F vrater
Factory seam strength, IbMn Wm)
66 (290) min
66 (290) min
66 (290) min
66 (290) min
66 (290) min '
'Feld seam Strength, IblAn (kN1m) No requirement
25 (4.4) min
25 (4.4) min
40 (7.0) min
40 (7.0) min
ASTM D1876 tested in peel
50 (8.8) typ
60 (105) typ
65 (11.4) typ
70 (12.31 typ
Water vapor penneance, Perms No requirement
0.10 max
0.10 max
0.10 max
0.10 max
ASTM E96 uac. B
0.05 typ
0.05 typ
0.05 typ
0.05 typ 1
Puncture resistance, ml (kN) No requirement
250 (1.1) min
300 (1.3) min
350 (1.6) min
400 (1.8) min I
'FTM 101 C, method 2031
325 (14) typ
350 (1.6) typ
400 (1.8) typ
45012.0) typ
(see supplemental section)
Pmpert es after heat aging
ASTM 0573, 670 hours ® 240 °F
'Breaking strength, %retained 90 min
90 min
90 min
90 min
90 min
,Elongation reml., % retained 90 min
90 min
90 min
90 min
90 min
Tearing Strength, %retained 60 min
60 min
60 min
60 min
60 min
Weight ct ange. % - 1.0 max
- 1.0 max
- 1.0 max
- 1.0 max
- 1.0 max
Typical Weights
0.23 U112 (1.1 kglmr)
0.29(l.4)
0.35(l.7)
040 (2.0)
Typical properties and characteristics are based on samples tested and are not guaranteed for all samples of this product.
This data and information is intended as a guide and does not reflect the specification range for any
particular property of
this product.
Invesfing In Roofing Solutlons for Over 45 Years
800- 479 -6832 • P.O. Box 7000 • Carlisle, PA 17013 • Fax: 717- 245 -7053 • www.Carlisle- syntec.com
Carlisle SynTec
CARLISLE'S
SUREmWELD REINFORCED
TPO MEMBRANE
Extreme Testing For Severe Climates
ASTM Standard 06878 is the material specification for Thermoplastic Polyolefn Based Sheet Roofing. It covers material property requirements for
TPO roof sheet and includes initial and aged properties after heat and xenon -arc exposure. As stated in the scope of the standard, "the tests and
property limits used to characterize the sheet are values intended to ensure minimum quality for the intended purpose." Carlisle's goal is to produce
TPO that ensures maximum performance for the intended purpose of roofing membranes. Maximum performance requires the membrane to far
exceed the requirements of ASTM D6878. For severe climates like Miami, FL and Phoenix, AZ, EXTREME testing is required.
Heat Aging accelerates the oxidation rate that roughly doubles for
each 10•C (18 °F) increase in roof membrane temperature. Oxidation
(reaction with oxygen) is one of the primary chemical degradation
mechanisms of roofing materials.
Carlisle Extreme Testing Aging
ASTM REQUIREMENT SURE -WELD REQUIREMENT
ASTM TEST 240 °F 60 hours or 4 weeks 5,376 hours or 32 weeks*
Carlisle 275 °F
Extreme T851 N/A 1,344 hours or 8 weeks
Extreme
'-Compaattle to 1,024 weeks (20 yrs) at 185 °F for 6 ors/day.
• Test specimen is 1" by 4" piece of 45-mil membrane unbacked,
placed in circulating hot -air oven.
• Criterion — no visible cracks after bending aged test specimen
around 0.25 " - diameter mandrel.
Xenon -Arc exposes the membrane samples to the combined effect
of ultraviolet, visible and infrared radiation as well as ozone, heat and
water spray, to greatly accelerate the effects of outdoor weathering.
The radiation dose is measured in kilojoules per square meter (kJ /m)
at 340 nm machine W wavelength. The irradiance power of the xenon -
arc lamp is measured in Watts per square meter (W /m).
'Carlisle Extreme Testing — Xenon-Arc
' SURE -WELD RESULTS j
ASTM TEST ASTM 06878 60 -MIL 80 -MIL 45 -MIL 72 -MIL
REQUIREMENT
kJ /meat 340 nm 10.080 20,160 27,720 17,640 25,200
• Test specimen is 2.75" by 5.5" piece of membrane, unbacked,
weathering side facing arc lamp.
• Criterion — no visible cracks viewed under I Ox magnification
while wrapped around 3 "- diameter mandrel.
In Rooflng Soluflons for Over 45 Years
800- 479 -6832 • P.O. Box 7000 • Carlisle. PA 17013 • Fax: 717- 245 -7053
Environmental Cycling subjects the membrane to repeated cycles
of heat aging, hot -water immersion or acid fog followed by xenon -arc
exposure. The acid fog accelerates acid etching that may occur from
acid rain if the roof membrane is not resistant to acidic conditions.
• ASTM requirement — none
• Carlisle EXTREME test':
• 10 days heat aging at 240•F (116 °C) followed by
• 5 days water immersion at 158•F (700C) or with another
specimen set
• 5 eight -hour cycles in Kesternich sulfur dioxide chamber
(sulfurous acid fog) followed by
• 5040 kJ /m, (2000 his at 0.70 W /m= irradiance) xenon -arc
exposure
'Test specimen is 2.75" by 5.5" piece of membrane with edges sealed.
'Criterion — after 3 complete cycles, test specimens shall remain
flexible and not have any cracking under IN magnification while
wrapped around a 3 "- diameter mandrel.
Carlisle SynTec
CARLISLE'S
ouQm��Jwm[D Eimp@M(n[D
rww 4p0 b&P.P& B N
Supplemental Approvals, Statements 3. Sure -Weld TPO membranes conform to requirements of the
and Characteristics: U.S.E.P.A. Toxic Leachate Test (40 CFR part 136) performed by
1. Sure -Weld TPO meets or exceeds the requirements of ASTM an independent analytical laboratory.
06878 Standard Specification for Thermoplastic Polyolefin Based
Sheet Roofing.
2: Radiative Properties for ENERGY STAR, Cool Roof Rating Council
(CRRC) and LEED.
Solar Reflectance Index (SRI) is calculated per ASTM E1980. The SRI is
a measure of the roof's ability to reject solar heat, as shown by a small
temperature rise. It is defined so that a standard black (reflectance
0.05, emittance 0.90) is 0 and a standard white (reflectance 0.80,
emihance 0.90) is 100. Materials with the highest SRI values are the
coolest choices for roofing. Due to the way SRI is defined, particularly
hot materials can even take slightly negative values and particularly
cool materials can even exceed 100.
rG&
Test Method
White
TPO
Tan
TPO
Gray
TPO
'ENERGY STAY
initial solar reflectance
Solar Spectrum
Reflectometer
0.87
0.68
WA
i
'I ENERGY STAR inidal
solar reflectance
!after 3 years
solar Spectrum
Reflectometer
(after cleaning)
0.83
0.64
WA j
1
CRRC Initial
solar reflectance
ASTM C1549
0.79
0.71
046
•CRRC solar reflectance
,after 3 years
ASTM C1549
(uncleared)
0.70
0.64
0.43
;CRRC initial
,thermal emittance
ASTM C1371
0.90
0.86
0.90 i
CRRC inermal
emihance after 3 years
ASTM C1371
(uncleared)
0.86
0.87
0.88
l
I
LEED thermal emittance
ASTM E408
0.95
0.95
0.95 '
:SRI (Solar Reflectance Index)
ASTM E1980
110
Be
55 1
Solar Reflectance Index (SRI) is calculated per ASTM E1980. The SRI is
a measure of the roof's ability to reject solar heat, as shown by a small
temperature rise. It is defined so that a standard black (reflectance
0.05, emittance 0.90) is 0 and a standard white (reflectance 0.80,
emihance 0.90) is 100. Materials with the highest SRI values are the
coolest choices for roofing. Due to the way SRI is defined, particularly
hot materials can even take slightly negative values and particularly
cool materials can even exceed 100.
rG&
'Pre- consumer Recycled Content
10%
Post- consumer Recycled Content
0%
Manufacturing Location
Senatobu, MS
Tocele, UT
Solar Reflectance Index 110
In Roofing Soluffons for Over 45 Years
4. Sure -Weld reinforced TPO was tested for dynamic puncture
resistance per ASTM D5635 -04 using the most recently modified
impact head. 45 -mil was watertight after an impact energy of
12.5 J (9.2 h -lbf) and 60 -mil was watertight after 22.5 J (16.6
ft -lbQ. Both 72 -mil and 80 -mil EXTRA products were watertight
after an impact energy of 30.0 J (22.1 ft- I151).
Cafte. Sure -Wtld, edaguaN XT. PlraMa Plans and w -x are tradmwW of Carlisle.
ENERGY STAR is a repNared trademark awned by me OS. Govemment. LEED Is a trmemark of me US. Preen annotate Connell. Carlisle SynTec
•DOGY STAR RuaelkaWn Is any wild In me OS.
REPRINT CODE: 600515 - 'Sum-Weld ReiNmced TPO Membrane Product Data Stan' - 0505110 2011 Carlisle.
ICC -ES Evaluation Report ESR -1463
V L ICC -ES /UL
Dual Report
Click on the logo to access UL Certification
Reissued August 1, 2012
This report is subject to renewal October 1, 2014.
www.icc- es.org 1 (800) 423 -6587 1 (562) 699 -0543 A Subsidiary of the International Code Council®
DIVISION: 07 00 00— THERMAL AND MOISTURE
PROTECTION
Section: 07 53 23— Ethylene - Propylene - Diene- Monomer
Roofing
Section: 07 54 19— Polyvinyl- Chloride Roofing
Section: 07 54 23— Thermoplastic - Polyolefin Roofing
REPORT HOLDER:
CARLISLE SYNTEC INCORPORATED
PO BOX 7000
CARLISLE, PENNSYLVANIA 17013
(717) 245 -7000
www.carlisle-syntec.com
EVALUATION SUBJECT:
CARLISLE EPDM, PVC AND TPO SINGLE -PLY ROOFING
MEMBRANES
ADDITIONAL LISTEES:
VERSICO INCORPORATED
POST OFFICE BOX 1289
CARLISLE, PA 17013
MULE -HIDE PRODUCTS COMPANY, INC.
1195 PRINCE HALL DRIVE
BELOIT, WISCONSIN 53511
WEATHERBOND
P.O. BOX 251
PLAINFIELD, PENNSYLVANIA 17081
KELLY COMPANY /2001 INC.
325 THOMASTON AVENUE
WATERBURY, CONNECTICUT 06702
1.0 EVALUATION SCOPE
Compliance with the following codes:
■ 2006 International Building Code® (IBC)
■ 2006 International Residential Code® (I RC)
2.0 USES
Carlisle ethylene propylene diene monomer (EPDM),
polyvinyl chloride (PVC) and thermoplastic polyolefin
(TPO) single -ply roofing membranes are used as roof
coverings in adhered and mechanically fastened
membrane roofing systems.
3.0 DESCRIPTION
3.1 General:
The EPDM, PVC and TPO Membrane Roofing Systems
described in this report consist of single -ply roofing
membranes, insulation where used, barrier board or slip
sheet where used, flashing, mechanical fasteners and
adhesives that are installed on a combustible or
noncombustible deck. See Table 1 for Carlisle product
trade names and corresponding product names for
Mule -Hide Products Company, Inc., WeatherBond, Versico
Incorporated and Kelly Company /2001 Inc., the additional
listees.
3.2 EPDM Membranes:
3.2.1 Sure -Seal: Sure -Seal is a black, nonreinforced
EPDM membrane available in 45-, 60- and 90-mil
(1.14, 1.52, and 2.29 mm) thicknesses.
3.2.2 Sure -Seal FR: Sure -Seal FR is a black,
nonreinforced EPDM membrane with fire retardants,
available in 45 -, 60- and 90 -mil (1.14, 1.52, and 2.29 mm)
thicknesses.
!R33,2:3-';Sure- White: Sure -White is a white, nonreinforced
E membrane available in a 60- and 90 -mil (1.52 and
@11�2�f29 mm) thickness.
Ei 3:2.4 Sure - Tough: Sure -Tough is a black, reinforced
membrane consisting of a polyester reinforcement
�en�capsulated between two EPDM membrane plies. It is
�savailable in 45- to 75-mil (1.14 to 1.90 mm) thicknesses.
" ?3.2.5 Sure -Tough FR: Sure -Tough FR is a black,
reinforced membrane consisting of a polyester
re0orcement encapsulated between two EPDM
membrane plies with fire retardants. It is available in 45 to
60-mil (1.14 to 1.52 mm) thickness.
■ Other Codes (see Section 8.0) 3.2.6 Sure -Seal FleeceBACK: Sure -Seal FleeceBACK is
Properties evaluated: a.45 -, 60- or 90 -mil (1.14, 1.52 or 2.29 mm) non - reinforced
EPDM bonded to a 5.5- ounce -per- square -yard (0.18
• Weather resistance - _ kg /m2) polyester fleece.
• Roof covering fire classification 3.2.7 Sure -White FleeceBACK: Sure -White FleeceBACK
• Wind uplift resistance CEI`%�+ is a 60- or 90 -mil (1.52 or 2.29 mm) nonreinforced white
EPDM bonded to a 5.5- ounce -per- square -yard (0.18
• Impact resistance AUG 16 201Z kg /m2) polyester fleece.
v.
as an a darren in, fthens je no! th he port or a eyremu tiorj r as us•ermMbs no .- nhmes in- spec wtuat o. Service oar are they to be construed
as an rndorsrmenr ofrhe subject of the upon or a recommendation for its um. 7ilerr is no e�armnn• hr lCC E�nluarian Service. Lf.C. atrpreca or implied, as IM 11=11
toan)•frnaing or other matter in thisreport,orm toanyproduct coveredby her"". �•� - --
copyright 0 2012 Page 1 of 10
ESR -1463 I Most Widely Accepted and Trusted Page 2 of 10
3.2.8 Sure -Seal AFX: Sure -Seal AFX is a 45-, 60- or
90 -mil (1.14, 1.52 or 2.29 mm) non - reinforced EPDM
bonded to a 7.5- ounce -per- square -yard (0.25 kg 1m2)
polyester fleece.
3.2.9 Sure -Seal AFX PLUS: Sure -Seal AFX PLUS is a
60 -mil (1.52 mm) non - reinforced EPDM bonded to a
7.5- ounce -per- square -yard (0.25 kg /M2) polyester fleece.
3.3 PVC Membranes:
3.3.1 Sure -Flex and Sure -Flex Elvaloy: Sure -Flex and
Sure -Flex Elvaloy are 50-; 60-, or 80 -mil (1.27, 1.52, or
2.03 mm) membranes consisting of a polyester
reinforcement encapsulated between two plies of PVC.
The membrane is available in white, gray or custom colors.
3.3.2 Sure -Flex FRS and Sure -Flex Elvaloy FRS: Sure -
Flex FRS and Sure -Flex Elvaloy FRS are 50-, 60 -, or
80 -mil (1.27, 1.52, or 2.03 mm) membranes consisting of a
fiberglass reinforcement encapsulated between two plies
of PVC. The membrane is available in, white, gray or
custom colors.
3.3.3 Sure -Flex FRS FleeceBACK and Sure -Flex
Elvaloy FRS FleeceBACK: Sure -Flex FRS FleeceBACK
and Sure -Flex Elvaloy FRS FleeceBACK are the Sure -Flex
FRS membrane and the Sure -Flex Elvaloy FRS
membrane, described in Section 3.3.2 with a laminated
5.5- ounce -per- square -yard (0.18 kg /my) polyester fleece
backing.
3.4 TPO Membranes:
3.4.1 Sure -Weld: Sure -Weld is a 45- or 60 -mil (1.14 or
1.52 mm) membrane consisting of a polyester
reinforcement encapsulated between two plies of TPO.
The membrane is available in white, gray, tan or custom
colors.
3.4.2 Sure -Weld HS: Sure -Weld HS is the Sure -Weld
membrane formulated with an additional flame retardant
for fire resistance at higher slopes. It is manufactured in
45- and 60 -mil (1.14 or 1.52 mm) thicknesses, and is
available in white, gray, tan or custom colors.
3.4.3 SAT -TPO: SAT -TPO is a self- adhered version of
Sure -Weld HS membrane with adhesive.
3.4.4 Sure -Weld EXTRA: Sure -Weld EXTRA is the same
formulation as the Sure -Weld ,membrane but comes in
72- and 80 -mil (1.83 and 2.03 mm) thicknesses.
3.4.5 Sure -Weld HS EXTRA: Sure -Weld HS EXTRA is
the same formulation as the Sure -Weld HS membrane but
comes in 72- and 80 -mil (1.83 and 2.03 mm) thicknesses.
3.4.6 Sure -Weld FleeceBACK: Sure -Weld FleeceBACK
is the Sure -Weld HS membrane, 45 or 60 mils (1.14 or
1.52 mm) thick with a laminated 5.5- ounce - per - square-
yard (0.18 kg /m�) polyester fleece backing.
3.4.7 Sure -Weld AFX: Sure -Weld AFX is the 45 -mil
(1.14 mm) Sure -Weld HS membrane with a laminated
10- ounce -per- square -yard (0.34 kg /m2) polyester fleece
backing.
3.4.8 Sure -Weld AFX PLUS: Sure -Weld AFX PLUS is
the 60 -mil (1.52 mm) Sure -Weld HS membrane with a
laminated 10- ounce -per- square -yard (0.34 kg /M2)
polyester fleece backing.
3.4.9 Spectro -Weld: Spectro -Weld is the Sure -Weld
membrane, described in Section 3.4,1, and Sure -Weld
EXTRA membrane, described in Section 3.4.4, formulated
with a brighter white color. It is manufactured in 45-, 60-,
72- or 80 -mil (1.14 -, 1.52-, 1.83- or 2.03 -mm) thicknesses.
3.4.10 Spectro -Weld FleeceBACK: Spectro -Weld
FleeceBACK is the Spectro -Weld membrane with a
laminated 5.5- ounce -per- square -yard (0.18 kg /m2)
polyester fleece backing.
3.5 Insulation:
See Tables 2 through 4 for insulations for use with specific
roofing systems. Foam plastic insulation, where used, must
have a flame - spread index of not more than 75 when
tested at the maximum thickness intended for use in
accordance with ASTM E 84.
3.6 Barrier Board:
Barrier board, where used, must be either minimum
'/4- inch -thick (6.4 mm? G -P Gypsum Corporation
"DensDeck," minimum /4- inch -thick (6.4 mm) Owens
Corning "Slrataguard ", minimum '/4- inch -thick (6.4 mm)
USG "Securock," or minimum '/2- inch -thick (12.7 mm)
gypsum board. Barrier board must be UL- listed for roofing
applications or UL- classified gypsum board.
3.7 Slip Sheet:
The slip sheet, where used, must include Carlisle "FR
Base Sheet 1S or 2S," Elk "VersaShield Underlayment,"
Elk "VersaShield FB -1S or FB -2S, or Atlas FR 10 or
FR 50."
3.8 Flashing:
Flashing must be provided in accordance with IBC Section
1503.2 or IRC Section R903.2, as applicable. Where
flashing is of metal, the metal must be corrosion - resistant,
minimum No. 26 gage [0.019 inch (0.483 mm)] galvanized
steel.
3.9 Fasteners:
Fasteners, used to mechanically attach insulation and
membranes to the roof deck, must be corrosion - resistant,
and must be Cadisle fasteners, plates or fastening bars,
unless otherwise noted in this report. Refer to Table 4 for
spacing of fasteners.
3.9.1 Sure -Seal HP Fastener: This is an epoxy - coated
steel screw used in combination with Carlisle's fastening
plates or bars to mechanically attach roofing insulation and
membranes to steel or wood substrate. Fastener length
must be selected to penetrate through the steel deck a
minimum Of inch (19.1 mm), and into the wood deck a
minimum of 1 inch (25.4 mm).
3.9.2 Sure -Seal HP Purlin Fastener: This is an epoxy -
coated steel screw used in combination with Carlisle's
fastening plates or bars to mechanically attach roofing
insulation and membranes to structural steel members.
Fastener length must be selected to penetrate through the
steel member a minimum of 3/a inch (19.1 mm.)
3.9.3 Sure -Seal HD 14 -10 Fastener: This is a heavy -
duty, epoxy- coated steel screw used in combination with
Carlisle's fastening plates or bars to mechanically attach
roofing insulation and membranes to concrete roof deck.
Fastener length must be selected to penetrate into the
concrete deck a minimum of 1 inch (25.4 mm).
3.9.4 Sure -Seal HP Polymer Seam Plate: This is a
2 -inch- diameter (50 mm) polymer plate designed to be
used with Sure -Seal HP and Sure -Seal HD 14 -10
fasteners to mechanically attach roofing membranes to the
roof deck.
3.9.5 Sure -Tite Fastener and ST Fastening Bar: This is
a heavy -duty, epoxy- coated steel screw and bar used to
secure reinforced EPDM membranes to steel or wood
deck. The bar is 1- inch - wide -by- 0.040- inch - thick- by -10-
foot -long (25.4 mm by 1.1 mm by 3.1 m) galvalume- coated
steel with prepunched holes 6 inches (150 mm) on center.
ESR -1463 I Most Widely Accepted and Trusted Page 3 of 10
3.9.6 HP -X Fastener: This is an epoxy- coated carbon
steel screw used in combination with the Piranha
Fastening Plate to mechanically attach TPO membranes to
steel or wood substrate. Fastener length must be selected
to penetrate through the steel deck a minimum of 3/4 inch
(19.1 mm), and into the wood deck a minimum of 1 inch
(25.4 mm).
3.9.7 Piranha Fastening Plate: This is a 23/s -inch-
diameter galvalume- coated steel plate designed to be used
with HP -X fasteners to mechanically attach PVC and TPO
membranes to the roof deck.
3.9.8 HP -XTRA Fastener: This is an epoxy- coated
carbon steel screw used in combination with the Piranha
XTRA Fastening Plate to mechanically attach PVC and
TPO membranes to steel or wood substrate. Fastener
length must be selected to penetrate through the steel
deck a minimum of 314 inch (19.1 mm) and into the wood
deck a minimum of 1 inch (25.4 mm).
3.9.9 Piranha XTRA Fastening Plate: This is a
23/8- inch - diameter galvalumecoated steel plate designed
to be used with HP -XTRA fasteners to mechanically attach
PVC and TPO membranes to the roof deck.
3.9.10 OMG Inc. Rhino Bond Plate: The RhinoBond Plate
is a 3- inch - diameter (76.2 mm), 0.028- inch -thick (0.7 mm)
galvalume- coated steel plate, coated with a proprietary
adhesive and used with the HP -X fastener to mechanically
attach PVC and TPO membranes to the roof deck. The
adhesive bonds the plate to the underside of the
membrane.
3.10 Adhesives:
3.10.1 Sure -Seal 90- 8.30A: Sure -Seal 90 -8 -30A is a high -
strength, solvent -based contact adhesive used to adhere
EPDM membranes to the insulation or substrate. It has a
coverage rate of approximately 60 square feet per gallon
(1.5 m /L). The adhesive is supplied in 5- gallon (18.9 L)
containers and has a shelf life of one year.
3.10.2 Sure -Seal Aqua Base 120: Sure -Seal Aqua Base
120 is a high- strength, water -based contact adhesive used
to adhere EPDM and TPO membranes to the insulation or
substrate. It has a coverage rate of approximately 120
square feet per gallon (3 m2/L). The adhesive is supplied in
5- gallon (18.9 L) containers and has a shelf life of
one year.
3.10.3 Sure -Flex PVC Bonding Adhesives: Sure -Flex
PVC and Sure -Flex Low VOC PVC Bonding Adhesives are
high - strength, solvent -based contact adhesives used to
adhere PVC membranes to an insulation or substrate.
They have a coverage rate of approximately 60 square feet
per gallon (1.5 m /L). The adhesives are supplied in
5- gallon (18.9 L) containers with a shelf life of one year.
3.10.4 Sure -Weld Bonding Adhesive: Sure -Weld
Bonding Adhesive is a high - strength, solvent -based
contact adhesive used to adhere TPO membranes to an
insulation or substrate. It has a coverage rate of
approximately 60 square feet per gallon (1.5 m2 /L). The
adhesive is supplied in 5-gallon (18.9 L) containers with a
shelf life of one year.
3.10.5 Low VOC Bonding Adhesive: Low VOC Bonding
Adhesive is a high- strength, solvent -based contact
adhesive used to adhere membranes to an insulation or
substrate. It has a covera�e rate of approximately 60
square feet per gallon (1.5 m9/ L). The adhesive is supplied
in 5- gallon (18.9 L) containers with a shelf life of one year.
3.10.6 FAST Adhesives: FAST 100, FAST 100LV, FAST
Adhesive Dual Cartridge, FAST Adhesive Box Sets,
Flexible FAST and FAST Bag -in -a -Box Adhesives are
two- component polyurethane adhesives used to adhere
FleeceBACK membranes and insulations to various
substrates. The adhesives have a coverage rate of
approximately 100 square feet per gallon (2.5 mZ /L). The
adhesives are supplied in 15- gallon (56.7 L) and 50- gallon
(189 L) drums, cartridge tubes or cylinders, and have a
shelf life of one year.
3.11 Impact Resistance:
The EPDM, PVC, and TPO roofing membranes described
in this report meet requirements for impact resistance in
IBC Section 1504.7, based on testing in accordance with
FM 4470.
4.0 INSTALLATION
4.1 General:
Installation of the EPDM, PVC, and TPO roofing
membranes described in this report must comply with the
applicable code, the manufacturer's published installation
instructions and this report. The manufacturer's published
installation instructions must be available at all times on
the jobsite during installation.
The substrate to which the membrane is to be applied
must be clean, dry, and free of frost, loose fasteners, and
other protrusions or contaminates that will interfere with the
adhesion or attachment of the membrane or that will
puncture the membrane. All materials must be protected
against contact with incompatible materials. Where
gypsum board is used as barrier board in the roofing
assembly, weather protection must be provided to prevent
damage to the gypsum board prior to application of the
roofing membrane.
The slope of the roof on which the single -ply membranes
are installed must not be more than the maximum slope
indicated for the particular assembly as listed in Tables
2 and 3.
Penetrations and terminations of the roof covering must
be Flashed and made weather tight in accordance with the
requirements of the membrane manufacturer and the
applicable code.
4.2 Fire Classification:
4.2.1 New Construction: The adhered and mechanically
fastened EPDM, PVC, and TPO single -ply membrane
roofing systems, when installed in accordance with this
report, are Class A, B or C roof covering systems in
accordance with ASTM E 108 and UL 790, as noted in
Tables 2 and 3.
4.2.2 Reroofing: The existing deck must be inspected to
verify that the structure to be reroofed is structurally sound
and adequate to support and secure the roofing
membrane. Prior to installation of new roof coverings,
inspection by and written approval from the code official
having jurisdiction must be required.
Class A, B or C roof covering systems may be installed
over existing classified roof covering systems under the
following conditions without additional roof classification
tests, provided the resulting classification is the lower of
the new or existing roofing classification:
■ New uninsulated systems installed only over existing
uninsulated assemblies.
■ New insulated systems installed over existing
uninsulated systems only.
4.3 Wind Resistance:
4.3.1 New Construction: The allowable wind uplift
pressures for the EPDM, PVC, and TPO roofing
membranes as parts of roof assemblies are noted in
Tables 4 and 5.
ESR -1463 I Most Widely Accepted and Trusted Page 4 of 10
Metal edge securement for roofing systems must be
designed in accordance with ANSI /SPRI ES -1, complying
with IBC Section 1504.5. The edge securement for
mechanically attached membranes was tested in
accordance with ANSI /SPRI ES -1 Test RE -1, using
Carlisle SecurEdge 300 (0.050 -inch (1.27 mm) 3003
aluminum] and Carlisle SecurEdge 3000 [0.040 -inch
(1.02 mm) 3003 aluminum] fascia systems. The maximum
allowable load for Carlisle SecurEdge 300 is 234 plf
(348 kglm). The maximum allowable load for Cadisle
SecurEdge 3000 is 200 plf (298 kg /m).
4.3.2 Reroofing: Mechanically anchored systems may
be accepted based on the adequacy of anchors
penetrating through existing roof coverings into structural
substrates. Since the composition and /or condition of any
particular existing underlying material may vary widely,
reroofing with adhered systems is outside the scope of this
report.
5.0 CONDITIONS OF USE
The single -ply EPDM, PVC, and TPO roofing membranes
described in this report comply with, or are suitable
alternatives to what is specified in, those codes listed in
Section 1.0 of this report, subject to the following
conditions:
5.1 Installation must comply with the applicable code, the
manufacturer's published installation instructions and
this report. The instructions within this report must
govern if there are any conflicts between the
manufacturers installation instructions and this report.
5.2 The adhered and mechanically fastened single -ply
membrane roofing systems must be installed by
professional roofing contractors who are trained and
approved by the manufacturer.
5.3 Foam plastic insulation must be separated from the
interior of the building by an approved thermal barrier
in accordance with IBC Section 2603.4.1.5 or IRC
Section R314.4, as applicable.
5.4 Foam plastic insulation, where used, must bear the
label of an approved agency indicating that the foam
plastic has a flame - spread index of not more than 75
when tested at the maximum thickness intended for
use in accordance with ASTM E 84, subject to the
approval of the code official.
5.5 Design wind uplift pressure on any roof area,
including edge and corner zones, must not exceed
the allowable wind uplift pressure for the system
installed in that particular area. Refer to allowable
wind uplift pressures for systems as listed in Table 4.
5.6 The allowable wind uplift pressures listed in Table 4
are for the roof covering system only. The deck and
framing to which the system is attached must be
designed for the applicable components and cladding
wind loads in accordance with the applicable code.
5.7 When application is over existing roofs,
documentation of the wind -uplift resistance of the
composite roof construction must be submitted to the
code official for approval at the time of permit
application.
5.8 The roofing membranes are manufactured at Carlisle,
Pennsylvania; Greenville, Illinois; Tooele, Utah; and
Senatobia, Mississippi, under a quality control
program with inspections by UL LLC (AA -668).
5.9 For buildings under the IBC, above -deck thermal
insulation board must comply with the applicable
standards listed in Table 1508.2 of the IBC.
6.0 EVIDENCE SUBMITTED
Data in accordance with ICC -ES Acceptance Criteria for
Membrane Roof Covering Systems (AC75), dated April
2007, (corrected December 2008).
7.0 IDENTIFICATION
Each roll of the roofing membrane must bear a label noting
the product name, the manufacturer's name (Carlisle
SynTec Incorporated) or the name of the additional listee,
the manufacturer's address or plant code, the ICC -ES
evaluation report number (ESR- 1463), and the name or
label of the inspection agency (Underwriters Laboratories
Inc.).
8.0 OTHER CODES
In addition to the codes referenced in Section 1.0, the
products in this report were evaluated for compliance with
the requirements of the following codes:
■ BOCA® National Building Code /1999 (BNBC)
■ 1999 Standard Building Code° (SBC)
■ 1997 Uniform Building Code'* (UBC)
For compliance under the above codes, see Sections 2
through 7 of this report, except revise the following
sections to read as follows:
3.8 Flashing:
Flashing must be provided in accordance with SBC
Section 1503.2, BNBC Section 1508.1 and UBC Section
1509, as applicable. Where flashing is of metal, the metal
must be corrosion- resistant, minimum No. 26 gage [0.019
inch (0.483 mm)] galvanized steel.
3.11 Impact Resistance:
The EPDM, PVC, and TPO roofing membranes described
in this report meet requirements for impact resistance in
BNBC Section 1505.4.2, and SBC Section 1504.6, based
on testing in accordance with FM 4470.
4.3.1 New Construction: The allowable wind uplift
pressures for the EPDM, PVC, and TPO roofing
membranes as parts of roof assemblies are noted in
Tables 4 and 5.
5.0 CONDITIONS OF USE
The single -ply EPDM, PVC, and TPO roofing membranes
described in this report comply with, or are suitable
alternatives to what is specified in, those codes listed in
Section 8.0 of this report, subject to the following
conditions:
See Sections 5.1 through 5.8, except revise Section 5.3 to
read as follows:
5.3 Foam plastic insulation must be separated from the
interior of the building by an approved thermal barrier
in accordance with BNBC Section 2603.4.1.5, SBC
Section 2603.5.1.5, and UBC Sections 2602.4 and
2602.5.3, as applicable.
ESR -1463 I Most Widely Accepted and Trusted
Option I
Option 2
4�¢SSIFjFO AssiFle
V� C UL
%1=beane for Roofing Syvans
a. to Extemal Fire Exposwe
Scc UL Direc:aty of Prodnc:s Cerriiicd fm Canada
.and UL Reofn? M=rwli and 5ystems Direc:oxy
60P6
4�SSIFjFO
C UL US
Diembixne for Roofm' Sjvems
at to Extemal Fim Eicpecutc
Scc Ui. Dirc mrry of Products CatiScd for Canada.
wd IJL Roo:"m, Miataials and Systems D -venmy
6OP6
FIGURE 1— INSPECTION AGENCY LABEL
5of10
ESR -1463 1 Most Widely Accepted and Trusted Page 6 of 10
TABLE 1—PRODUCT NAMES
CARLISLE PRODUCT
MULE -HIDE PRODUCT
WEATHERBOND PRODUCT
VERSICO PRODUCT
KELLY CO./
NAME
NAME
NAME
NAME
2001 INC.
PRODUCTNAME
Sure -Seal
Mule -Hide Standard
WeatherBond RBR EPDM
Versigard
EPDM
Membrane
_
Sure -Seal FR
Mule -Hide FR EPDM
WeatherBond RBR FR EPDM
Versigard Nonreinforced
C- EPDM -C
Membrane
EPDM
Sure -Tough Reinforced
Mule -Hide Standard
WeatherBond RBR Standard
Versigard Reinforced
C- EPDM -CR
Reinforced EPDM
Reinforced EPDM Membrane
Sure -Tough FR
Mule -Hide FR Reinforced
VersigardFR Reinforced
C- EPDM -CR Type 1
Reinforced
EPDM
_
Sure -White
Mule -Hide White -on-
WeatherBond RBR White EPDM
Versigard Nonreinforced
EPDM RF -White
Black EPDM
Membrane
EPDM -White
Sure -Weld
Mule -Hide TPO -c
WeatherBond PRO TPO
Versiweld
Reinforced TPO / White
Membrane
TPO
Sure -Weld HS
Mule -Hide TPO -c (FR)
-
Versiweld ES
-
SAT -TPO
Mule -Hide SA -TPO
WeatherBond PRO PAS TPO
Versiweld CIA TPO
-
Sure -Weld EXTRA
Mule -Hide TPO -c Extra
WeatherBond PRO TPO
Versiweld PLUS
Membrane
_
Sure -Weld HS EXTRA
Mule- Hide TPO -c Extra
Versiweld ES PLUS
(FR)
_
_
Sure -Weld FleeceBACK
Mule -Hide TPO -c Fleece
Versiweld VersiFleece
Back
_
_
Sure -Flex
Mule -Hide PVC
WeatherBond PRO PVC
VersiFlex Reinforced
Membrane
PVC Membrane
_
Sure -Flex FRS
Mule -Hide FRS PVC
VersiFlex FRS
Membrane
-
Reinforced PVC
-
Membrane
Sure -Seal 90 -8 -30A
Mule -Hide Bonding
WeatherBond RBR LC -60 Bonding
G200SA Yellow
2001 Inc. Bonding
Bonding Adhesive
Adhesive
Adhesive
Substrate Adhesive
Adhesive
Sure -Seal Aqua Base 120
Mule -Hide Water -Based
Aqua Base 120 Bonding Adhesive
Aqua Base 120 Bonding
Bonding Adhesive
Bonding Adhesive
Adhesive
_
Sure -Weld Bonding
Mule -Hide TPO -c
WeatherBond PRO TPO Bonding
Versiweld Bonding
Adhesive
Bonding Adhesive
Adhesive
Adhesive
_
Sure -Weld Low VOC
Mule -Hide TPO -c Low
Versiweld LOW VOC
Bonding Adhesive
VOC Bonding Adhesive
-
Bonding Adhesive
_
Sure -Flex PVC Bonding
Mule -Hide PVC Bonding
WeatherBond PRO PVC Bonding
VersiFlex PVC Bonding
Adhesive
Adhesive
Adhesive
Adhesive
_
Sure -Flex Low VOC PVC
Mule -Hide Low VOC
VersiFlex Low VOC PVC
Bonding Adhesive
PVC Bonding Adhesive
_
Bonding Adhesive
_
FAST 100 Adhesive
Mule -Hide SP -100
FAST 100 Adhesive
Adhesive
_
_
FAST 100 LV Adhesive
Mule -Hide SP- 100 -LT
FAST 100 LV Adhesive
Adhesive
_
_
ESR -1463 I Most Widely Accepted and Trusted Page 7 of 10
TABLE 2 —FIRE CLASSIFICATION ASSEMBLIES — ADHERED ROOFING SYSTEMS'':
SYSTEM
ROOF
DECK
BARRIER BOARD
INSULATION'
MEMBRANE /MAX. ROOF SLOPE
NO.
CLASS
OR SLIP SHEET
Sure -Weld, Spectro -Weld - '/;:12
Any of the following insulations,
Sure -Seal, Sure - Tough, Sure - White, Sure -
1 -inch min. to 6 -inch max.
Seal FleeceBACK, Sure-Weld HS, SAT -TPO,
1
A
Noncombustible
thickness: Carlisle "SecurShield
",'Polyiso ",
Sure -Weld FleeceBACK, Spectro -Weld
Polyiso HP -H Hunter
FleeceBACK - /2:12
Panels "H- Shield" or
"H- Shield -CG"
Sure -White FleeceBACK, Sure -Flex, Sure -
Flex FRS - 2/.:12
'/r inch -thick fiberboard', 72
Sure -White FleeceBACK-- 2/<:12
inch -thick fiberboard or barrier
board (see Section 3.6) over 5-
Sure -Seal, Sure -Tough - 1:12
2
A
Noncombustible
—
inch max Insulfoam EPS2,' /2-
Sure - White, Sure -Seal FleeceBACK, Sure -
inch- thick fiberboard or barrier
Weld, Spectro-Weld, Sure -Weld HS, SAT -
board (see Section 3.6) over
TPO, Sure -Weld FleeceBACK, Spectro-Weld
System No. 1 insulations
FleeceBACK, Sure -Flex, Sure -Flex FRS -
1 12:12
Sure -White FleeceBACK- 3/.:12
Sure - White, Sure -Seal FleeceBACK - 11/2:12
Noncombustible or
Sure - Tough, Sure -Weld, Spectro-Weld, Sure -
Combustible - min.
'%/
Barrier board
Weld FleeceBACK, Spectro-Weld
3
A
inch -thick
(see Section 3.6)
—
FleeceBACK - 3:12
in.
r plywood or min.
Sure -Weld HS, SAT -TPO -4:12
/,Both -thick
Sure -Seal FR, Sure -Flex, Sure -Flex FRS -
unlimited slope
Any of the following insulations,
Sure- Weld_Spectro -Weld - '/4:12
Combustible - min.
Barrier board
1-inch min.
Sure -Seal, Sure- Tough, Sure - White, Sure -
" /',inch -thick
n
(see Section 3.6) or
to 6 -inch max. thickness:
"SecurShield ",
Seal FleeceBACK, Sure -Weld HIS, SAT -TPO,
4
A
plywood othick in.
plywood or min.
Slip sheet: layers
Slip
Carlisle Polyiso
Polyiso HP ",
Sure -Weld FleeceBACK, Spectro -Weld
FleeceBACK /2:12
Section 3.7)
-H
Hunter Panels "H- Shield" or
-
Sure -White FleeceBACK, Sure -Flex, Sure -
"H- Shield -CG"
Flex FRS - 2/.:12
Combustible - min.
"/',inch
Any of the following insulations,
Sure -Weld, Spectro-Weld, Sure -Weld HS,
5
C
-thick
_
2 -inch min. to 6 -inch max.
SAT -TPO, Sure -Flex. Sure-Flex FRS -
plywood or min.
7/
thickness: Carlisle 'Polyiso HP-
unlimited slope
,inch-thick OSB.
H" or Hunter Panels "H-Shield'
Single layer of minimum 3.0" or
double layer of minimum 1.5"
6
A
Combustible
—
Carlisle -SecurShield Polyiso' or
EPDM, PVC, and TPO Membranes - '/2:12
Hunter Panels
"H- Shield -CG"
Single layer of minimum 1.9"
7
B
Combustible
—
Carlisle " SecurShield Polyiso" or
EPDM, PVC, and TPO Membranes - '/2:12
Hunter Panels
'H- Shield -CG'
For SI: 1 inch = 25.4 mm.
'All foam plastic insulation must be UL- classified foamed plastic for roofing systems, and must be limited to the maximum thickness in
accordance with Section 5.4 of this report or the maximum thickness in accordance with this table, whichever is less.
2See Section 3.10 for adhesive application rate.
2UL Classified EPS may be installed below min. 1- inch -thick Carlisle or Hunter Panels polyisocyanurate insulations (max slopel:12) or below
min.' /rinch -thick Carlisle SecurShield HD or Hunter Panels H- Shield HD (max slope 2:12) on noncombustible decks.
°Cadisle SecurShield HD or Hunter Panels H- Shield HD may replace fiberboard and may be used as a coverboard over any insulation. When
these two boards are used directly below the Sure -Weld membrane, the slope is limited to max. '12:12.
°When these systems are used for reroofing or recovering, installation must be in accordance with Sections 4.2.2 and 5.7 of this report, and
IBC Section 1510, IRC Section R907, BNBC Section 1512, SBC Section 1510 or UBC Appendix to Chapter 15, as applicable.
ESR -1463 I Most Widely Accepted and Trusted Page 8 of 10
TABLE 3 —FIRE CLASSIFICATION ASSEMBLIES — MECHANICALLY FASTENED ROOFING SYSTEMS'
SYSTEM
ROOF
DECK
BARRIER BOARD
INSULATION'
MEMBRANE /MAX. ROOF
NO.
CLASS
OR SLIP SHEET
I
SLOPE
Any of the following insulations, 1 -inch min. to
"SecurShield
Sure - Tough, Sure -Weld,
Spectro-Weld, Sure -Flex, Sure -
1
A
Noncombustible
—
6 -inch max. thickness: Carlisle
",
Flex FRS - '1x:12
Polyiso' or "Polyiso HP -H Hunter Panels 'H-
'H-Shield-CG"
Sure -Weld HIS - 1'/2:12
Shield" or
Sure -Tough FR - 2:12
4rinch -thick fiberboard', ' /2-inch -thick
Sure- Tough, Sure -Weld HS,
fiberboard or barrier board (see Section 3.6)
Sure -Flex, Sure -Flex FRS - 1:12
2
A
Noncombustible
—
over 5 -inch max Insulfoam EPS2,' /,inch -thick
Sure -Weld, Spectro-Weld -
fiberboard or barrier board (see Section 3.6)
1'/x:12
over System No. 1 insulations
Sure -Tough FIR - 3'/2:12
Sure -Weld, Spectro -Weld, Sure -
3
A
Noncombustible
—
To 5 -inch max: Insulfoam SP
Weld HS, Sure -Flex, Sure -Flex
FRS - %:12
Noncombustible or
Sure - Tough, Sure -Weld,
Combustible - min.
Barrier board
Spectro -Weld -3:12
4
A
12rinch -thick
—
Sure -Tough FR - 3'/2:12
plywood or min.
(see Section 3.6)
Sure -Weld HS, Sure -Flex, Sure -
2116- inch -thick OSB.
Flex FRS - unlimited
Combustible - min.
Barrier board
Any of the following insulations, 1 -inch min.
Sure - Tough, Sure -Weld,
,s
(see Section 3.6)
to 6 -inch max. thickness: Carlisle
Spectro-Weld, Sure -Flex, Sure-
,
5
5
A
plywood or min.
or Slip sheet: 2
'SecurShield Polyiso' or'POlyiso HP -H ",
Flex FRS - I2:12
2
/16 -inch -thick OSB.
layers, (see Section
Hunter Panels
"H- "H-
Sure -Weld HS, 1'12:12
3.7)
Shield" or Shield -CG'
Sure -Tough FR - 2:12
Combustible - min.
Sure -Tough - 1:12
15/32- inch -thick
-t
Slip sheet, 2layers
Sure -Tough FR, Sure Weld,
6
A.
plywood min.
(see Section 3.7)
—
Spectro -Weld, Sure -Weld HS,
21,6- inch -thick OSB.
Sure -Flex, Sure -Flex FRS -
1 Ix:12
Combustible - min.
Sure - Tough, Sure -Tough FR,
B
,s /,2- inch -thick
Slip sheet, 1 layer
Sure -Weld, Spectro -Weld,
7
plywood or min.
(see Section 3.7)
—
Sure -Weld HS, Sure -Flex, Sure -
2 /,v inch -thick OSB.
Flex FRS - 02:12
Combustible - min.
Any of the following insulations, 2 -inch min.
,s Izrinch -thick
to 6 -inch max. thickness: Carlisle
"SecurShield "Polyiso
Sure -Weld, Spectro -Weld,
8
C
plywood or min.
—
Polyiso' or
", 'H-Shield"or
Sure -Weld HS, Sure -Flex, Sure-
116- inch -thick OSB.
HP -H Hunter Panels H- Shield
Flex FRS - unlimited
CG"
Single layer of minimum 3 -inch or double
9
A
Combustible
—
layer of minimum 1.5 -inch Carlisle
EPDM, PVC, and TPO
"SecurShield Polyiso' or
Membranes - '22:12
Hunter Panels "H- Shield -CG"
Single layer of minimum 1.9 -inch Carlisle
10
B
Combustible
—
' SecurShield Polyiso' or Hunter Panels "H-
EPDM, PVC, and TPO
Shield -CG" or single layer of an inverted G3
Membranes - '/2:12
cap sheet.
For SI: 1 inch = 25.4 mm.
'All foam plastic insulation must be UL- classified foamed plastic for roofing systems, and must be limited to the maximum thickness in
accordance with Section 5.4 of this report or the maximum thickness in accordance with this table, whichever is less.
2UL Classified EPS may be installed below min. 1- inch -thick Carlisle or Hunter Panels polyisocyanurate insulations (max slopel:12) or below
min. ' /,inch -thick Carlisle SecurShield HD or Hunter Panels H- Shield HD (max slope 2:12) on noncombustible decks.
'Carlisle SecurShield HD or Hunter Panels H- Shield HD may replace fiberboard and may be used as a coverboard over any insulation. When
these two boards are used directly below the Sure -Weld membrane, the slope is limited to , 12:12.
`When these systems are used for reroofing or recovering, installation must be in accordance with Sections 4.2.2 and 5.7 of this report, and
IBC Section 1510, IRC Section R907, BNBC Section 1512, SBC Section 1510 or UBC Appendix to Chapter 15, as applicable.
ESR -1463 1 Most Widely Accepted and Trusted Page 9 of 10
TABLE 4 —WIND RESISTANCE - MECHANICALLY FASTENED ASSEMBLIES°''
SYSTEM
MAXIMUM
DECK'
INSULATION'
MEMBRANE
MEMBRANE
MAXIMUM
MAXIMUM
NO.
ALLOWABLE
FASTENING
FASTENER
FASTENER
WIND UPLIFT
SPACING
ROW
(psf)
(Inches)
SPACING'
Foam plastic
insulation' 2.
1
45
Noncombustible
' /rinch -thick
fiberboard or
Sure -Tough
HP -X Fastener &
Metal Fastening Bar
12
6 it 6 inches
barrier board
(See Sect. 3.6)
2
75
Noncombustible
Same as System No. 1
Sure -Tough
HP -X Fastener &
6
6 It 6 inches
Metal Fastening Bar
3
52
Noncombustible
Same as System No. 1
Sure -Tough
HP Fastener &
Polymer Seam Plate
6
9 ft 6 inches
4
45
Noncombustible
Same as System No. 1
Sure -Tough
Sure -Tile Fastener &
12
9 ft 6 inches
ST Fastening Bar
5
30
Noncombustible
Same as System No. 1
Sure -Tough
HP Fastener &
12
9 it 6 inches
(75 mil)
Polymer Seam Plate
6
60
Noncombustible
Same as System No. 1
Sure -Tough
HP Fastener &
6
9 h 6 inches
(75 mil)
Polymer Seam Plate
Sure -Weld,
HP -X or HP -Xtra
7
45
Noncombustible
Same as System No. 1
Sure -Weld EXTRA, or
Fasteners with Piranha
12
7 It 6 inches
Spectro-Weld
or Piranha Xtr i Plates
Sure -Weld,
HP -Xtra Fasteners with
8
45
Noncombustible
Same as System No. 1
Sure -Weld EXTRA, or
piranha Xtra Plates
12
9 If 6 inches
Spectro -Weld
Sure -Weld,
HP -X or HP -Xtra
9
60
Noncombustible
Same as System No. 1
Sure -Weld EXTRA, or
Fasteners with
Piranha or Piranha Xtra
6
9 it 6 inches
Spectro-Weld
Plates
Sure -Weld,
HP -X or HP -Xtra
10
67
Noncombustible
Same as System No. 1
Sure -Weld EXTRA, or
Fasteners with Piranha
6
7 ft 6 inches
Spectro-Weld
or Piranha Xtra Plates
Sure -Weld,
HP -X or HP -Xtra
11
30
Noncombustible
Same as System No. 1
Sure -Weld EXTRA, or
Fasteners with Piranha
12
11 it 6 inches
Specho -Weld
or Piranha Xtra Plates
Sure -Weld,
HP -X or HP -Xtra
12
60
Noncombustible
Same as System No. 1
Sure -Weld EXTRA, or
Fasteners with Piranha
6
11 ft 6 inches
Spectro-Weld
or Piranha Xtra Plates
13
53
Noncombustible
Same as System No. 1
Sure -Flex
HP -X Fasteners with
6
6 it 4 inches
Piranha Plates
14
83
Noncombustible
Same as System No. 1
Sure -Flex
HP -X Fasteners with
6
2 It 11 inches
Piranha Plates
HP -X or HP -Xtra
15
30
Noncombustible
Same as System No. 1
Sure -Flex
Fasteners with Piranha
18
6 it 4 inches
or Piranha Xtra Plates
HP -X or HP -Xtra
16
45
Noncombustible
Same as System No. 1
Sure -Flex
Fasteners with Piranha
12
6 It 4 inches
or Piranha Xtra Plates
17
53
Noncombustible
Same as System No. 1
Sure -Flex
HP -X Fasteners with
12
2 It 11 inches
Piranha Plates
18
45
Noncombustible
Same as System No. 1
Sure -Weld
HP -X Fasteners with
1 per 5.3 1`12
NIA
OMG RhinoBond Plates
19
60
Noncombustible
Same as System No. 1
Sure -Weld
HP -X Fasteners with
1 per 4 112
NIA
OMG RhinoBond Plates
For SI: 1 inch = 25.4 mm; 1 ft = 0.305 m; 1 psi = 47.88 Pa.
'Foam plastic insulation must be any of the following (1 -inch min. to 6 -inch max. thickness): Carlisle "SecurShield Polyiso ", "Polyiso HP -H"
Hunter Panels "H- Shield" or Hunter Panels "H- Shield- CG ".
'All foam plastic insulation must be UL- classified foamed plastic for roofing systems, and must be limited to the maximum thickness in
accordance with Section 5.4 of this report or the maximum thickness in accordance with this table, whichever is less.
'Steel deck must be minimum No. 22 gage galvanized steel (base -metal thickness 0.030 inch (0.76 mm)]. Concrete must have a minimum
compressive strength (f'.) of 2500 psi. See Section 5.6 of this report.
°For existing metal roofing. the assemblies listed must be installed by fastening through the roofing and into structural members (pudins, angle
iron, beams, etc.) capable of resisting all expected loads. The maximum allowable wind uplift (field) pressures are shown in Column 2.
sUL Classified EPS may be installed below min. 1- inch -thick Carlisle or Hunter Panels polyisocyanurate insulations (max slopel:12) or below
min.' /rinch -thick Carlisle SecurShield HD or Hunter Panels H- Shield HD (max slope 2:12) on noncombustible decks.
6 Carlisle SecurShield HD or Hunter Panels H- Shield HD may replace fiberboard and may be used as a coverboard over any insulation. When
these two boards are used directly below the Sure -Weld membrane, the slope is limited to '/2:12.
ESR -1463 1 Most Widely Accepted and Trusted Page 10 of 10
Table 4 footnotes cont'd
z When these systems are used for reroofing or recovering, installation must be in accordance with Sections 4.2.2 and 5.7 of this report, and
IBC Section 1510, IRC Section R907, BNBC. Section 1512, SBC Section 1510 or UBC Appendix to Chapter 15, as applicable.
3 Fastener row spaces shown are for field of roof only. See Section 4.3 for recognized fascia systems for mechanically fastened roof
assemblies. The maximum allowable load for Carlisle SecurEdge 300 is 234 plf (348 kg /m). The maximum allowable load for Carlisle
SecurEdge 3000 is 200 plf (298 kg/m). Distance between the edge of the roof and the first row of fasteners must be determined accordingly.
TABLE 5 —WIND RESISTANCE – ADHERED ASSEMBLIES'
SYSTEM
ALLOWABLE
DECK'
INSULATION / MIN. THICKNESS'''
INSULATION
MEMBRANE
NO.
WIND UPLIFT
FASTENING
TYPE
(FIELD) (ps1)
RATE
1
46
Combustible or
'/z inch fiberboard' , "/zz inch OSB, or barrier board (See
7
er 2 h 1
EPDM, PVC and TPO
Noncombustible
Section 3.6)
p
Membranes
Combustible or
Carlisle'Polyiso HP -H' or 'SecurShield Polyso': Hunter
"H-Shield' 'H-
z
EPDM, PVC and TPO
2
45
Noncombustible
Panels or Shield -CG' / 1. inch
7 per 3.2 h
Membranes
with'/2-inch Securock coverboard (optional)
Combustible or
Cadisle'Polyiso HP -H' or'SecurShield Polyiso'; Hunter
z
EPDM. PVC and TPO
3
46
Noncombustible
Panels'H- Shield' rock- Shield -CG' / 2.0 inch
1 per a h
Membranes
with ° /e-inch Securock coverboard (optional)
a
68
Combustible or
Carlisle'Polyiso HP -H' or 'SecurShield Polyiso'; Hunter
FAST Adhesive
FleeceBACK Membranes
Noncombustible
Panels'H. Shield' or -H- Shield -CG' / 1.0 inch
Combustible or
Cadisle'Polyiso HP -H' or'SecurShield Polyiso'; Hunter
7
EPDM, PVC and TPO
5
75
Noncombustible
Panels 'H- Shield' rock- Shield -CG' / 2.0 inch
1 per 1.6 h
Membranes
with'/z - inch Securock coverboard (optional)
Combustible or
Cadisle'Polyiso HP -H' or'SecurShield Polyso-; Hunter
7
TPO Membranes;
6
720
Noncombustible
Panels 'H. Shield' or'H. Shield -CG' / 2.0 inch
1 per 1 It
EPDM membranes (vn th
noncombustible deck only)
Combustible or
Carlisle 'Polyiso.HP -H' or'SecurShield Polyso'; Hunter
7
728
Panels 'H-Shield' or'H- Shield / 2.0 inch
1 per 1 h 7
EPDM and TPO Membranes
Noncombustible
-Inch and
With '/2-Inch Securock coverboard (optional)
Combustible or
Carlisle'Polyiso HP -H' or'SecurShield Polyiso -; Hunter
8
135
Panels eld' ro ck -Shield / 2.0 inch
1 per 1 h z
FleeceBACK Membranes
Noncombustible
with �/z -inch Securock coverboard (optional)
'12-inch coverboard
9
141
Combustible or
'/7 inch DensDeck Prime
7 per 1 hz
FleeceBACK Membranes
Noncombustible
For SI: 1 inch = 25.4 mm; 1 ft = 0.305 m; 1 psf = 47.88 Pa
'AII foam plastic insulation must be UL- classified foamed plastic for roofing systems, and must be limited to the maximum thickness in
accordance with Section 5.4 of this report or the maximum thickness in accordance wAth this table, whichever is less.
7Steel deck must be minimum No. 22 gage galvanized steel (base -metal thickness 0.030 inch (0.76 mm)). Concrete must have a minimum
compressive strength (f'.) of 2500 psi. See. Section 5.6 of this report.
3UL Classified EPS may be installed below min. 1- inch -thick Carlisle or Hunter Panels polyisocyanurate insulations (max slope1:12) or below
min. V/ inch -thick Carlisle SecurShield HD or Hunter Panels H- Shield HD (max slope 2:12) on noncombustible decks.
4Carlisle SecurShield HD or Hunter Panels H- Shield HD may replace fiberboard and may be used as a coverboard over any insulation. When
these two boards are used directly below the Sure -Weld membrane, the slope is limited to '/7:12.
'When application is over existing roofs, documentation of the wind - uplift resistance of the composite roof construction must be submitted to
the code official for approval at the time of permit application. For reroofing or recovering, installation must be in accordance with IBC Section
1510, IRC Section R907, BNBC Section 1512, SBC Section 1510 or UBC Appendix to Chapter 15, as applicable.