14120118CITY OF CUPERTINO BUILDING PERMIT
BUILDING ADDRESS: 10931 N DE ANZA BLVD
CONTRACTOR: AIRTEKS.COM INC
PERMIT NO: 14120118
OWNER'S NAME: VIDOVICH JOHN T ET AL
2432 ARMSTRONG ST
DATE ISSUED: 12/22/2014
OWNER'S PHONE: 5107190621
LIVERMORE, CA 94551
PHONE NO: (925) 292-0148
❑ LICENSED CONTRACTOR'S DECLARATION
JOB DESCRIPTION: RESIDENTIAL COMMERCIAL ❑
TO CLEAR CODE ENFORCEMENT CASE: REMOVE AND
License Class G 2. Lic. # 5.r
REPLACE 8.5 TON PACKAGE UNIT.
Contractor�iY t�K_ • t _ Date 12-22-Z f
I hereby affirm that I am licensed under the provisions of Chapter 9
(commencing with Section 7000) of Division 3 of the Business & Professions
Code and that my license is in full force and effect.
I hereby affirm under penalty of perjury one of the following two declarations:
I have and will maintain a certificate of consent to self-insure for Worker's
Compensation, as provided for by Section 3700 of the Labor Code, for the
Sq. Ft Floor Area:
Valuation: $12500
performance of the work for which this permit is issued.
I have and will maintain Worker's Compensation Insurance, as provided for by
Section 3700 of the Labor Code, for the performance of the work for which this
APN Number: 32610061 00
Occupancy Type:
permit is issued.
APPLICANT CERTIFICATION
I certify that I have read this application and state that the above information is
PERMIT EXPIRES IF WORK IS NOT STARTED
correct. I agree to comply with all city and county ordinances and state laws relating
WITHIN 180 DAYS OF PERMIT ISSUANCE OR
to building construction, and hereby authorize representatives of this city to enter
upon the above mentioned property for inspection purposes. (We) agree to save
180 DAYS FROM LAST CALLED INSPECTION.
indemnify and keep harmless the City of Cupertino against liabilities, judgments,
costs, and expenses which may accrue against said City in consequence of the
Issued by: �j�%/�/� G� Date:
granting of this permit. Additionally, the applicant understands and will comply
L
with all non-point source r ons per the Cupertino Municipal Code, Section
9 18.
/Z —e e , �
Signature e 6
RE-ROOFS:
All roofs shall be inspected prior to any roofing material being installed. If a roof is
installed without first obtaining an inspection, I agree to remove all new materials for
inspection.
❑OWNER-BUILDER DECLARATION
Signature of Applicant: Date:
I here affirm that I am exempt from the Contractor's License Law for one of
the following two reasons:
ALL ROOF COVERINGS TO BE CLASS "A" OR BETTER
I, as owner of the property, or my employees with wages as their sole compensation,
will do the work, and the structure is not intended or offered for sale (Sec.7044,
Business & Professions Code)
1, as owner of the property, am exclusively contracting with licensed contractors to
HAZARDOUS MATERIALS DISCLOSURE
construct the project (Sec.7044, Business & Professions Code).
I have read the hazardous materials requirements under Chapter 6.95 of the
California Health & Safety Code, Sections 25505, 25533, and 25534. I will
I hereby affirm under penalty of perjury one of the following three
maintain compliance with the Cupertino Municipal Code, Chapter 9.12 and the
declarations:
Health & Safety Code, Section 25532(a) should I store or handle hazardous
I have and will maintain a Certificate of Consent to self-insure for Worker's
material. Additionally, should I use equipment or devices which emit hazardous
Compensation, as provided for by Section 3700 of the Labor Code, for the
air contaminants as defined by the Bay . it Quality Management District I
performance of the work for which this permit is issued.
will maintain compliance with the Cupert' o Municipal Code, Chapter 9.12 and
I have and will maintain Worker's Compensation Insurance, as provided for by
the Health & Safety Code, Secjions 25 , 25533, a 534.
Section 3700 of the Labor Code, for the performance of the work for which this
12—,??—
Owner or authorized age t: tip- Date:
permit is issued.
I certify that in the performance of the work for which this permit is issued, I shall
not employ any person in any manner so as to become subject to the Worker's
CON RUCTION LENDING AGENCY
Compensation laws of California. If, after making this certificate of exemption, I
become subject to the Worker's Compensation provisions of the Labor Code, I must
I hereby affirm that there is a construction lending agency for the performance of
forthwith comply with such provisions or this permit shall be deemed revoked.
work's for which this permit is issued (Sec. 3097, Civ C.)
Lender's Name
APPLICANT CERTIFICATION
Lender's Address—
I certify that I have read this application and state that the above information is
correct. I agree to comply with all city and county ordinances and state laws relating
to building construction, and hereby authorize representatives of this city to enter
upon the above mentioned property for inspection purposes. (We) agree to save
ARCHITECT'S DECLARATION
indemnify and keep harmless the City of Cupertino against liabilities, judgments,
costs, and expenses which may accrue against said City in consequence of the
I understand my plans shall be used as public records.
granting of this permit. Additionally, the applicant understands and will comply
with all non-point source regulations per the Cupertino Municipal Code, Section
Licensed Professional
9 18.
Signature Date
CUPERTINO
11_10d -011e
GENERAL PERMIT APPLICATION MEP
COMMUNITY DEVELOPMENT DEPARTMENT • BUILDING DIVISION
10300 TORRE AVENUE • CUPERTINO, CA 95014-3255 MISC
(408) 777-3228 • FAX (408) 777-3333 • building(cDcupertino.org
ICAL ❑ELECTRICAL ❑MISCELLANEOUS
FLUMbINU CHAN
PROJECT ADDRESS / /
APN #
OWNERNAME � , J� /I C PHONE j /c?- Q � E-MAIL
CITY, yCTDATE�ZIPz G FAX
STREET ADDRESS_'�^ `�� �%N�OrfG3 G
U J
CONTACT NAME PHONE E-MAIL
STREET ADDRESS
CITY, STATE, ZIP
FAX
❑ OWNER ❑ OWNER -BUILDER ❑ OWNER AGENT ONTRACTOR ❑ CONTRACTOR AGENT ❑ ARCHITECT ❑ ENGINEER ❑ DEVELOPER ❑ TENANT
CONTRACTOR NAME LICENSE NUMBER LICENSE TYPE
fes. L—z
BUS. LIC #
1 95
COMPANY NAME E-MAIL_ a1, v ¢
FAX
S�ETADDRESS
CITY, SSE, ZIP
I
P
cl'_3Zr
ARCHITECT/ENGINEER NAME
LICENSE NUMBER
BUS. LIC #
COMPANY NAME
E-MAIL
FAX
STREET ADDRESS
CITY, STATE, ZIP
PHONE
USE OF ❑ SFD or DUPLEX ❑ MULTI-FAMH.Y
PROJECT IN WB.DLAND ElYES
7PROJICT IN ❑ YES
IS THE BLDG AN ❑YES
BUILDING: MMERCIAL
(:O
URBAN INTERFACE AREA NO.
LO OD ZONE NO
EICHLER HOME? >LNO
y
DESCRIPTION OF WORK
^\
RECEIVED EY,
TOTAL VALUATION:
By my signature below, Ipertify to each of the following: I am the property owner or authorized agent to act on the property owner's behalf. I have read this
application and the in ation I have provided is correct. I have read the Description of Work and verify it is accurate. I agree to comply with all applicable local
ordinances and stato4aws relating to buildin ction. a esentatives of Cupertino to enter the above -identified property for inspection purposes.
Date: 2 -2 ` l
Signature of Applicant/Agent:
SUPP MENTAL INFORMATION REQUIRED
OFFICE USE ONLY
W
OYER -THE -COUNTER
i>F
EXPRESS
- STANDARD
-
U
�1
LARGE
i
p MAJOR
MEPMiscApp_2011.doc revised 06/21/11
CITY OF CUPERTINO
WAW 'Ur IV V Q rTX4 A Tnu - III TILLING DIVISION
1' iJJJ ••wJ a
FEE ID
a .••» -•
QTY/FEE
ADDRESS: 10931 N De Anza Blvd
UNITS
DATE: 12/22/2014
REVIEWED BY: SEan
Other Appliance/Equip
FBP#-:
VALUATION: $12,500
APN:
#
$72
�''�'�' 1:'i='" h?
*PERMIT TYPE: Mechanical Permit
11"wirh, hksp, Fee
PLAN CHECK TYPE: Alteration /Addition /Repair
PRIMARY
SFD or Duplex
PENTAMATION 1 RMAP1
PERMIT TYPE: i
USE:
PME Unit Fee:
$72.00
WORK
To Clear Code Enforcement Case: Remove and replace 8.5 ton package unit.
(,'o wr..,.wtion dLia:
SCOPE
Administrative Fee: IADMIN
APPLIANCE / EQUIP TYPE
FEE ID
a .••» -•
QTY/FEE
QTY
UNITS
BP FEES
I'hurth_ 1 Ic7:a Ciaecis
Other Appliance/Equip
113APPLOT
1
#
$72
�''�'�' 1:'i='" h?
11"wirh, hksp, Fee
PME Unit Fee:
$72.00
PME Permit Fee:
$48.00
(,'o wr..,.wtion dLia:
Administrative Fee: IADMIN
$45.00
Work Without Permit? (E) Yes 0 No
$120.00
TOTALS:
Travel Documentation Fee: ITRAVDOC
$72.00
StronV Motion Fee: IBSEISMICR
NOTE: This estimate does not includejees due to other Departments (Le. rianmrcg, ruuuc rrEll na, A 11c, u.w��•y �•-�• - •�-•-- _._
_. _ ___ _„___:__ __.:�� r. ... ,:r r r� ..,,d gra nnhi an o.ctimatn_ Contact the Dept for addn 7 info.
District, etc.. [hese fees are based on cne /GIN 111-1
FEE ITEMS (Tee Resolution 11-053 Eff. 7/1/13)
b,[ v, noucw.c uvu..w
FEE
a .••» -•
QTY/FEE
___________
MISC ITEMS
.0 $0.00
Mech. Plan Check 0hrs
I'hurth_ 1 Ic7:a Ciaecis
S":tf y)l
Mech. Permit Fee: IMPERMIT
Fter Mech. Insp. 0.0 hrs $48.00
01h,". -r 111vMb Irrs �
�''�'�' 1:'i='" h?
11"wirh, hksp, Fee
NOTE: This estimate does not includejees due to other Departments (Le. rianmrcg, ruuuc rrEll na, A 11c, u.w��•y �•-�• - •�-•-- _._
_. _ ___ _„___:__ __.:�� r. ... ,:r r r� ..,,d gra nnhi an o.ctimatn_ Contact the Dept for addn 7 info.
District, etc.. [hese fees are based on cne /GIN 111-1
FEE ITEMS (Tee Resolution 11-053 Eff. 7/1/13)
b,[ v, noucw.c uvu..w
FEE
a .••» -•
QTY/FEE
___________
MISC ITEMS
S":tf y)l
PME Plan Check:
$0.00
PME Unit Fee:
$72.00
PME Permit Fee:
$48.00
(,'o wr..,.wtion dLia:
Administrative Fee: IADMIN
$45.00
Work Without Permit? (E) Yes 0 No
$120.00
Travel Documentation Fee: ITRAVDOC
$48.00
StronV Motion Fee: IBSEISMICR
$1.63
Select an Administrative Item
Bldg Stds Commission Fee: IBCBSC
$1.00
`�
$335.63
TOTAL FEE.•
$0.00$335.63
Revised: 10/0V2014
r
Installation
Table 1. Maximum unit & comer weights (lbs) and center of gravity dimensions (in.) - cooling models
Maximum Model Center of Gravity
Unit Weights(a) Corner Weights(b) (in.)
Ton Model No. Shipping Net A S C D Length Width
3 TSC036E/THCO36E 555 481 157 122 95 107 31 19
4
TSC048E
586
511
167
129
101
114
31
19
5
TSCO60E
636
561
183
142
111
125
31
19
6
TSC072F
762
667
218
186
131
132
44
21
71/2
TSCO90F
781
686
222
195
136
134
44
21
71/2
TSC092F
940
797
249
235
163
149
46
21
81/2
TSC102F
999
856
264
239
177
175
45
22
10
TSC120F
1058
960
320
218
233
189
40
24
3
THC037E
614
544
163
144
111
125
33
19
4
THC048E/THCO47E
787
692
220
178
132
163
40
23
4
THC048F
737
642
208
177
128
130
44
22
5
THC060E/THC067E
841
746
241
193
139
173
39
22
5
THC060F
774
679
219
189
135
137
43
21
6
THC072F
883
740
228
219
155
138
47
21
71/2
THC092E
1445
1228
347
330
269
283
49
28
71/2
THC092F
1026
928
315
209
224
180
40
24
81/2
THC102E
1472
1_12.55
359
335
271
290
48
28
10
THC120E
1462
1245
353
332
271
288
48
28
(a) Weights are approximate.
(b) Corner weights are given for information only.
Figure 15. Rigging and center of gravity
�CLEVIS
Table 2. Factory installed options (fiops)/accessory net weights (Ibs)(a),(b)
TSC036E-060E
THC047E-067E
THC036E/
THC048E/F-
TSC072F-102F
THC092F,
THCO92E-
THC037E
060E/F
THC072F
TSC120F
120E
Net Weight
Net Weight
Net Weight
Net Weight
Net Weight
Accessory 3-5 Ton
4-5 Ton
6-81/2 Ton
71/2.-10 Ton
71/2-10 Ton
Barometric Relief 7
10
10
10
10
Belt Drive Option (3 phase only) 31
31
—
—
—
Coil Guards 12
20
20
20
30
continued on next page
20 RT-SVX22J-EN
.Inhncnn r.nntrols Unitary Products
5186;64Nf-E-1210
Table 9: ZS -06 thru -12 Physical Data
Models
Component
ZS -06
ZS -07
ZS -08
ZS -10
ZS -12
Nominal Tonnage
6.51
7.5
8.5
10
12.5
ARI COOLING PERFORMANCE
Gross Capacity @ ARI A point (Mbh)
81000
90000
104000
126000
156000
ARI net capacity (Mbh)
78000
88000
101000
120000
150000
EER
11.2
11.2
11.2
11.2
11.2
IEER
13
12.1
12.5
12.5
12.7
IPLV
12.9
12.1
12.5
12.6
13.06
Nominal CFM
2600
2500
3000
4000
4100
System power (KW)
6.95
7.87
8.60
10.70
13.40
Refrigerant type
R -410A
R-41 OA
R-41 OA
R-41 OA
R-41 OA
Refrigerant charge (Ib -oz)
System 1
4-12
4-12
4-14
6-8
7-8
System 2
4-10
4-10
5-0
6-8
7-8
ARI HEATING PERFORMANCE
Heating model
12 18
12 18
12 18
18 24
18 24
Heat input (K Btu)
120 180
120 180
120 180
180 240
180 240
Heat output (K Btu)
96 144
96 144
96 144
144 192
144 192
- -
- -
- -
AFUE %
-
-
Steady state efficiency (%)
80 80
80 80
80 80
80 80
80 80
No. burners
4 6
21 21
4 6
21 21
4 6
21 21
6 8
21 21
6 8
21 21
No. stages
Temperature Rise Range (°F)
20-50 35-65
15-45 1 30-60
10-40 25-55
20-50 35-65
10-40 25-55
Gas Limit Setting (°F)
165 165
165 165
215 195
195 160
195 160
Gas piping connection (in.)
3/4 3/4
3/4 1 3/4
3/4 3/4
3/4 3/4
3/4 3/4
DIMENSIONS (inches)
89
89
89
89
119-1/2
Length
59
59
59
59
59
Width
42
42
50-3/4
50-3/4
50-3/4
Height
OPERATING WT. (lbs.)
860
880
1020
1060
1253
COMPRESSORS
Type
Recip
Recip
Recip
Recip
Scroll
2.
2
2
2
2
Quantity
Unit Capacity -Steps(./.)
50/100
50/100
50/100
50/100
50/100
CONDENSER COIL DATA
Face area (Sq. Ft.)
18.5
18.5
18.5
29.0
29.0
Rows
1
1
1
1
1
23
23
23
23
23
Fins per inch
.71/18
.71/18
1/25
Tube diameter (in.)/mm
.71/18
.71/18
2 -pass
2 -pass
2 -pass
2 -pass
2 -pass
Circuitry Type
Microchannel
Microchannel
Microchannel
Microchannel
Microchannel
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
10.6
10.6
13.2
13.2
13.2
3
3
3
4
3
Rows
15
15
15
15
15
Fins per inch
0.375
0.375
0.375
0.375
0.375
Tube diameter
Intertwined
Intertwined
Intertwined
Intertwined
Intertwined
Circuitry Type
TXV
TXV
TXV
TXV
TXV
Refriaerant control
.Inhncnn r.nntrols Unitary Products
Plot Plan with unit locations
Front
Goodyear 8773
10931 North De Anza Raod
Cupertino, CA
Back
RECEIVED
NOV 2 2 2014
BY
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING DIVISION - CUPERTINO
APPROVED
This set of plans and specifications N1UST be kept at the
job site during construction. It is unlawful to make any
changes or alterations on same, or to deviate
therefrom, without approval from the Building Official.
The Stamping of this plan and specifications SHALL NOT
be held to permit or to be an approval of the violation
Bany provisions of any Cit Ordinance or State Law.
DAT—E�- �T�
PERMIT #
P
�� PANS
flA air
DAVEs�G SEPT.
Change existing 8.5 -Tan package unit: with new 8.5 -ton unit (like for like)
Note:
(1) Hook up existing high voltage electrical
(2) Hook up existing gas
(3) Hook up existing low voltage wiring
(4) Reconnect existing duct smoke detector.
i
(5) Hook up existing condensate piping
New Coleman ZS-8N12ATAAA6A (6) 4750 CFM
208/230/60/3 Gas Package unit. i (7) 2100 square feet
N Weight 1020 pounds '0 (8) Factory Economizer
m ,ham
H
Goodyear 8773
10931 North De Anza Raod
Cupertino, CA
o f h i a ur �HuruKNIH
REQUIRED ACCEPTANCE TESTS
MECHANICAL COMPLIANCE FORMS & WORKSHEETS (indicate if worksheet is included)
For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, refer to the 2013 Nonresidential Manual Note: The Enforcement Agency may
require all forms to be incorporated onto the building plans. Forms NRCC-MCH-04-E and NRCC-MECH-05-E are alternative forms to NRCC-MCH-01-E, NRCC-MCH-02-E and NRCC-
MCH-03-E for projects using only single zone packaged HVAC systems.
YES NO Form
X NRCC-MCH-04-E (1 of 2)
X NRCC-MCH-04-E (2 of 2)
X NRCC-MCH-05-E (1 of 2)
X NRCC-MCH-05-E (2 of 2)
Title
Certificate of Compliance. Required on plans when used.
Mechanical Acceptance Tests. Required on plans when used.
HVAC Prescriptive Requirements. It is required on plans when used.
Mechanical SWH Equipment Summary is required for all submittals with service water heating, pools or spas. It is
required on plans where applicable.
CA Building Energy Efficiency Standards - 2Q13 Nonresidential Compliance
June 2014
STATE OF CALIFORNIA
REQUIRED ACCEPTANCE TESTS
CEC-NRCC-MCH-04-E Revised 06/14
CERTIFICATE OF COMPLIANCE
Required Acceptance Tests
Project Name:
Q—J ve.A b r ? -j j C2 i Date Preparedi
CALIFORNIA ENERGY COMMISSION
N RCC -MCH -04-E
(Page 2 of 3)
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to check the
applicable boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the equipment
description and the number of systems. The NA number designates the Section in the Appendix of the Nonresidential Reference Appendices Manual that describes the test.
Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately.
Enforcement Agency:
Systems Acceptance. Before occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a building or space is operated
for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance.
Systems Acceptance. Before occupancy permit is granted. All newly installed HVAC equipment must be tested using the Acceptance Requirements..
The NRCC-MCH-04-E form is not considered a completed form and is not to be accepted by the building department unless the correct boxes are checked. The equipment
requiring testing, person performing the test (Example: HVAC installer, TAB contractor, controls contractor, PE in charge of project) and what Acceptance test must be
conducted. The following checked -off forms are required for ALL newly installed and replaced equipment. In addition a Certificate of Acceptance forms shall be submitted to
the building department that certifies plans, specifications, installation certificates, and operating and maintenance information meet the requirements of Section 10-103(b)
and Title 24 Part 6. The building inspector must receive the properly filled out and signed forms before the building can receive final occupancy.
Test Description
Equipment
Requiring
Testing or
Verification
# of
units
MCH -02-A
Outdoor
Air
MCH -03-A
Single Zone
Unitary
MCH -04-A
Air
Distribution
Ducts
MCH -05-A
Economizer
Controls
MCH -06-A
Demand
Control
Ventilation
(DCV)
MCH -07-A
Supply
Fan VAV
MCH -11-A
Automatic
Demand
Shed
Control
MCH -12-A
FDD for
Packaged
DX Units
MCH -14-A
Distribute
d Energy
Storage
DX AC
MCH -18-A
Energy
Managem
ent
Control
Test Performed By:
Systems
System
ZS -8N12
1
X
X
X
CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014
REQUIRED ACCEPTANCE TESTS
CEC-NRCC-MCH-04-E Revised 46/14
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-MCH-04-E
Required Acceptance Tests (Page 3 of 3}
Project Name: Goodyear 877310931 NORTH DE ANZA BLVD Cupertino, CA Date Prepared:
11/15/2014
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Jerry Bohland Documentation Author Signature: f /
Company: Airteks.com, Inc. Signature Date: f
11/17/2024
Address: 2432 Arnstrong Street CEA/ HERS Certification Identifi tion (if applicable):
City/state/Zip: Livermore, CA 94551 Phone:
925-292-0148
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible
designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance
conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
5. 1 will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement
agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the ocu the builder provides to the
building owner at occupancy.
Responsible Designer Name: ,ferry Bohland Responsible Designer Signature:
Company : Airteks.com, Inc.
Address: 2432 Arnstrong Street
Livermore, CA 94551
CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance
Date Signed: 11/17/2014
License: 930172
Phone: 925-292-0148
.lune 2014
STATE OF CALIFORNIA
REQUIREMENTS FOR PACKAGED SINGLE ZONE UNiTS
CEC-NRCC-MCH-05-E (Revised 06/14)
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-05-E
Requirements for Packaged Single -Zone Units (Page 1 of 2)
Project Name: Goodyear 8773 10931 NORTH DE ANZA BLVD Cupertino, CA Date Prepared: 11/15/2014
Equipment Tag(s)l
MANDATORY MEASURES
Heating Equipment Efficiency4
Cooling Equipment Efficiency4
Thermostats5
Furnace Standby Loss Contro16
Law Leakage AHU
Ventilation?
Demand Control Ventilation$
Occupant Sensor Ventilation Control$
Shutoff and Reset Controls9
Outdoor Air and Exhaust Damper Control
Automatic Demand Shed Controls
Economizer FDD
Duct Insulation
PRESCRIPTIVE MEASURES
Equipment is sized in conformance with
140.4(a&b)
Economizer
Electric Resistance Heatingi0
Duct Leakage Sealing and Testing."
T-24 Sections
Requirement3
As Scheduled3
Requirement3
As Scheduled3
Requirement3
As Scheduled3
110.1 or 110.2(a)
80%
80%
110.1 or 110.2(a)
11.2 EER
11.2 EER
110.2(b), 110.2(c)
Setback
setback
110.2(d)
N/A
N/A
110.2(f)
N/A
N/A
120.1(b)
N/A
N/A
120.1(c)4
N/A
N/A
120.1(c)5, 120.2(e)3
N/A
N/A
120.2(e)
N/A
N/A
120.2(f)
N/A
N/A
120.2(h)
N/A
N/A
120.2(i)
Yes
Yes
120.4
N/A
N/A
140.4(a & b)
140.4(e)
140.4(8)
140.401
Notes:
1. Provide equipment tags (e.g. ACI orAC1 to 101. Multiple units of the same make and model with the same application and accessories can be grouped together.
2. Enter the following information as appropriate: Unit Manufacturer; Unit Model Number (including all accessories); Description of the unit (e.g. gas -pack or heat pump; rated heating capacity
(enter "N/A" if no heating); and, rated cooling capacity (enter "N/A° if no cooling). For unit capacities include the units (e.g. kBtuh or tons).
8. For each requirement, enter the minimum requirement from the Standard In the left column (under "Standard Requirement"). In the right column (under "As Scheduled") enter the value for
the units as specified.
4. Where there is more than one requirement (e.g. full and part load efficiency) enter both with the appropriate labels (e.g. COP and /EER).
5. In the left column identify the thermostatic requirements from the standard (e.g. programmable setback thermostat or heatpump with electric heat), . In the right column indicate the
capabilities of the thermostat as scheduled.
6. If the unit has a furnace which is rated at >=225,000 Btuh of capacity, indicate the rated standby loss and ignition source (e.g. IID). If there is no furnace or the unit is rated for <225,000 Btuh
indicate "N/A".
Z In the left column, enter both the required ventilation value from Table 120.1A and for the number of occupants times 15 cfm/person. In the right column enter the actual minimum
ventilation as scheduled. If the space is naturally ventilated enter "N/A" in the left column and "the space is naturally ventilated" in the right column.
8. If the space is required to have either DCV or Occupant Sensor Ventilation Control indicate "required" in the left column (otherwise indicate "N/A" in the left column). If either DCV or Occupant
Sensor Ventilation Control is provided indicate "provided" in the right column (otherwise indicate "N/A" in the right column)
9. In the left column indicate the required time controls from the standard. In the right column identify the device that provides this functionality (e.g. EMCS or programmable timeclock).
10. Enter N/A if there is no electric heating. If the system has electric heating indicate which exception to 140.4(8) applies.
11. If duct leakage sealing and testing is required, a MCH -04-A form must be submitted.
CA Building Energy Efficiency Standards - 2013 Nonresidential Comptiance June 2014
QI^I=vrruirvrttvih p q
REQUIREMENTS FOR PACKAGE® SINGLE ZONE UNITS
U=U-NKX-1V1GH-05-E Revised 06/14 CALIFORNIA ENERGY COMMISSION ' .W'
CERTIFICATE OF COMPLIANCE NRCC-MCH-05-E
Requirements for Packaged Single -Zone Units (Page 2 of 2)
Project Name: Goodyear 877310931 NORTH DE ANZA BLVD Cupertino, CA Date Prepared: 11/15/2014
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Jerry Bohland
Documentation Author Signature
Company: Airteks.com, Inc.
Signature Date:
11/17/2014
Address: 2432 Armstrong Street
CEA/ HERS Certification Iden ifcation (if applicable):
City/state/Zip: Livermore, CA 94551
Phone: 925-292-0148
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible
designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance
conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information other documents,
provided on applicable compliance
worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
5. 1 will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement
agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be incl ed wit the documentation the builder provides to the
building owner at occupancy.
Responsible Designer Name: Jerry Bohland
Responsible Designer Signature:
Company:
Airteks.com, Inc.
Date Signed:
11/17/2014
Address: 2432 Armstrong Street
License: 930172
City/State/Zip:
Livermore, CA 94551
Phone:
92S-292-0148
CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance
June 2014
41
STATE OF CALIFORNIA
REQUIR8D ACC STS
CEC-NRCC-MQH-04-E (ReVis r� ma"
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OFC PLIANCE
Required Accepta ce Tests
NRCC-MCH-04-E
(Page 1 of 3)
Project Name: G odyear 877310931 NORTH DE ANZA BLVD upertino, CA Date Prepared:
11/15/2014
MECHANICAL
CE FORMS &
(indicate if worksheet Is included)
For detailed instructio on the use o Isand all Energy Efficiency Standards compliance forms, refer to the 2013 Nonresidential Manual Note: The Enforcement Agency may
require- all forms to be incor ed onto the building plans. Forms NRCC-MCH-04-E and NRCC-MECH-05-E are alternative forms to NRCC-MCH-01-E, NRCC-MCH-02-E and NRCC-
MCH-03-E for projects using only single zone packaged HVAC systems.
YES NO Form
X NRCC-MCH-04-E (1 of 2)
X NRCC-MCH-04-E (2 of 2)
X NRCC-MCH-05-E (1 of 2)
X NRCC-MCH-05-E (2 of 2)
Title
Certificate of Compliance.'Required on plans when used.
Mechanical Acceptance Tests. Required on plans when used.
HVAC Prescriptive Requirements. It is required on plans when used.
Mechanical SWH Equipment Summary is required for all submittals with service water heating, pools or spas. It is
required on plans where applicable.
CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance
June 2014
STATE OF CALIFORNIA
REQUIRED ACCEPTANCE TESTS
CEC-NRCC-M6,H-04-E Revised 06/14
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
NRCC-MCH-04-E
Required Acceptance Tests (Page 2 of 3)
Project Name: r�^4
v V C�� 6 % I `�, 1 i �.� �•� �.�J �r� Date Prepared:
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance te'ts for mechanical systems. The designer is required to check the
applicable boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the equipment
description and the number of systems. The NA number designates the Section in the Appendix of the Nonresidential Reference Appendices Manual that describes the test.
Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately.
Enforcement Agency:
Systems Acceptance. Before occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a building or space is operated
for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance.
Systems Acceptance. Before occupancy permit is granted. All newly installed HVAC equipment must be tested using the Acceptance Requirements..
The NRCC-MCH-04-E form is not considered a completed form and is not to be accepted by the building department unless the correct boxes are checked. The equipment
requiring testing, person performing the test (Example: HVAC installer, TAB contractor, controls contractor, PE in charge of project) and what Acceptance test must be
conducted. The following checked -off forms are required for ALL newly installed and replaced equipment. In addition a Certificate of Acceptance forms shall be submitted to
the building department that certifies plans, specifications, installation certificates, and operating and maintenance information meet the requirements of Section 10-103(b)
and Title 24 Part 6. The building inspector must receive the properly filled out and signed forms before the building can receive final occupancy.
Test Description MCH -02-A MCH -03-A MCH -04-A MCH -05-A MCH -06-A MCH -07-A MCH -11-A MCH -12-A MCH -14-A MCH -18-A Test Performed By:
Equipment # of Outdoor Single Zone Air Economizer Demand Supply Automatic FDD for Distribute Energy
Requiring units Air Unitary Distribution Controls Control Fan VAV Demand Packaged d Energy Managem
Testing or Ducts Ventilation Shed ADX Units Storage ent
Verification (DCV) Control DX AC Control
Systems System
ZS -8N 12 1 X X X
CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014
REQUIRED ACCEPTANCE TESTS
Ute-NKUL;-Mu1i-04-t Kevised 05114 CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-04-E
Required Acceptance Tests (Page 3 of 3)
Project Name: Goodyear 877310931 NORTH DE ANZA BLVD Cupertino, CA Date Prepared:.
11/15/2014
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Jerry Bohland
Documentation Author Signature:
Company: Airteks.com, Inc.
'
Signature Date:
11/17/201
Address: 2432 Arnstrong Street
CEA/ HERS Certification Identifi tion (if applicable):
City/state/zip: Livermore, CA 94551
Phone: 925-292-0148
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible
designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance
conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
5. 1 will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement
agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the docu the builder provides to the
building owner at occupancy.
Responsible Designer Name: Jerry Bohland Responsible Designer Signature:
company: Airteks.com, Inc. Date Signed: 11/17/2014
Address: 2432 Arnstrong Street
License: 930172
Phone: 925-292-0148
City/state/zip: Livermore, CA 94551
CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014
0
STATE OF CALIFORNIA
REQUIREMENTS FOR PACKAGED SINGLE ZONE UNITS 1+ ,
GLG-NKGG-MGhi-Ub-t Kevisea Ub/74 CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-MCH-05-E .
Requirements for Packaged Single -Zone Units (Page 1 of 2)
Project Name: Goodyear 8773 10931 NORTH DE ANZA BLVD Cupertino, CA Date Prepared: 11/15/2014
Equipment Tag(s)'
MANDATORY MEASURES T-24 Sections Requirement3 As Scheduled3 Requirement3 As ScheduledRequirement3 As ScheduledHeating Equipment Efficiency4 110.1 or 110.2(a) 80 80%
Cooling Equipment Efficiency4 110.1 or 110.2(a) 11.2 EER 11.2 EER
ThermostatS5 110.2(b), 110.2(c) Setback Setback
Furnace Standby Loss Contro16 110.2(d) N/A N/A
Low Leakage AHU 110.2(f) N/A N/A
Ventilation? 120.1(b) N/A N/A
Demand Control Ventilation$ 120.1(c)4 N/A N/A
Occupant Sensor Ventilation Controls 120.1(c)5, 120.2(e)3 N/A N/A
Shutoff and ,Reset Controls 120.2(e) N/A N/A
Outdoor Air and Exhaust Damper Control 120.2(f) N/A N/A
Automatic Demand Shed Controls 120.2(h) N/A N/A
Economizer FDD 120.2(i) Yes Yes
Duct Insulation 120.4 N/A N/A
PRESCRIPTIVE MEASURES
Equipment is sized in conformance with 140.4(a & b)
140.4(a&b)
Economizer 140.4(e)
Electric Resistance Heating10 140.4(8)
Duct Leakage Sealing and Testing." 140.4(1)
Notes:
1. Provide equipment togs (e.g. AC1 orAC1 to 10). Multiple units of the same make and model with the same application and accessories can be grouped together.
2. Enter the following information as appropriate: Unit Manufacturer; Unit Model Number (including all accessories); Description of the unit (e.g. gas -pack or heat pump; rated heating capacity
(enter "N/A" if no heating); and, rated cooling capacity (enter "N/A" if no cooling). For unit capacities include the units (e.g. kBtuh or tons).
3. For each requirement, enter the minimum requirement from the Standard In the left column (under "Standard Requirement"). In the right column (under "As Scheduled") enter the value for
the units as specified.
4. Where there is more than one requirement (e.g. full and part load efficiency) enter both with the appropriate labels (e.g. COP and LEER).
5. In the left column identify the thermostatic requirements from the standard (e.g. programmable setback thermostat or heatpump with electric heat), . In the right column indicate the
capabilities of the thermostat as scheduled.
6. if the unit has a furnace which is rated at>=225,000 Btuh of capacity, indicate the rated standby loss and ignition source (e.g. IID). If there is no furnace or the unit is rated for <225,000 Btuh
indicate "N/A".
7. In the left column, enter both the required ventilation value from Table 120.1A and for the number of occupants times 15 cfm/person. In the right column enter the actual minimum
ventilation as scheduled. If the space is naturally ventilated enter "N/A" in the left column and "the space is naturally ventilated" in the right column.
8. If the space is required to have either DCV or Occupant Sensor Ventilation Control indicate "required" in the left column (otherwise indicate "N/A" in the left column). If either DCV or Occupant
Sensor Ventilation Control is provided indicate "provided" in the right column (otherwise indicate "N/A" in the right column)
9. In the left column indicate the required time controls from the standard. In the right column identify the device that provides this functionality (e.g. EMCS or programmable timeclock).
10. Enter N/A if there is no electric heating. If the system has electric heating indicate which exception to 140.4(g) applies.
11. If duct leakage sealing and testing is required, a MCH -04 -A form must be submitted.
CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014
o i m i r- yr �.nurvrtt%ire
REQUIREMENTS FOR PACKAGED SINGLE ZONE UNITS
GH -05-E
CERTIFICATE OF COMPLIANCE NRCC-MCH-05-E
Requirements for. Packaged Single -Zone Units
(Page 2 of 2)
Project Name: Goodyear 877310931 NORTH DE ANZA BLVD Cupertino, CA Date Prepared: 11/15/2014
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: ferry Bohland
Documentation Author Signature:
-/r
Company: Airteks.com, Inc.
Signature Date: f
11/17/2014
Address: 2432 Armstrong Street
CEA/ HERS Certification Iden fication (if applicable):
City/State/Zip: Livermore, CA 94551
Phone: 925-292-0148
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible
designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance
conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information on other compliance documents,
provided applicable
worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
S. i will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement
agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be incl ed wit the documentation the builder provides to the
building owner at occupancy.
Responsible Designer Name: Jerry Bohland
Responsible Designer Signature:"
Company:
Airteks.com, Inc.
Date Signed:
11/17/2014
Address: 2432 Armstrong Street
License: 930172
City/State/Zip:
Livermore, CA 94551
Phone:
925-292-0148
CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014