Loading...
15100056CUPERTINO WATER -CONSERVING PLUMBING FIXTURES OWNER CERTIFICATE OF COMPLIANCE COMMUNITY DEVELOPMENT DEPARTMENT • BUILDING DIVISION 10300 TORRE AVENUE • CUPERTINO, CA 95014-3255 F a E-0 IORE ia- 1-1 6 (408) 777-3228 • FAX (408) 777-3333 • building(a.cupertino.org Owner Name ® rf ,J t#iZ J& R,& Zt- Permit No. 0,06 Address 10 t N ffl 6 co 1�; 1Z [ so Y) O �e Ae 4.) ® rf.4 ,e 1. Is your real property a registered historical site? ❑ YYCivil Code Sections 1101.1 through 1101.8 do not apply. Skip the rest of the form and sign bottom of form. LINO Go to Question 2. 2. Does your real property have a licensed plumber certifying that, due to the age or configuration of the property or its plumbing, installation of water -conserving plumbing fixtures is not technically feasible? VYes Civil Code Sections 1101.1 through 1101.8 do not apply. ❑ The licensed plumber's certification has been provided to the Building Division. Skip the rest of the form and sign bottom of form. ❑ No Go to Question 3. 3. Is water service permanently disconnected for your building? �Zo Civil Code Sections 1101.1 through 1101.8 do not apply. Skip the rest of the form and sign bottom of form. JV Go to Question 4. 4. Is your real property built and available for use or occupancy on or before January 1, 1994? ❑ No My real property is built and available for use or occupancy after January 1, 1994. Civil Code Sections 1101.1 through 1101.8 do not apply. Skip the rest of the form and sign bottom of form. Z/yes My real property is built and available for use or occupancy on or before January 1, 1994. Civil Code Sections 1101.1 through 1101.8 apply. Check one of the three following statements and sign bottom of form.. 5. Plose check ONE of the following: i� My property is a single family residential real property. See Civil Code Section 1101.4. On and after January"1, 2014, building alterations or improvements shall require all non-compliant plumbing fixtures to be replaced with water -conserving plumbing fixtures throughout the building. On or before January 1, 2017, all non- compliant plumbing fixtures shall be replaced with water -conserving plumbing fixtures (regardless of whether property undergoes alterations or improvements). ❑ My property is a multifamily residential real property. See Civil Code Section 1101.5. On and after January 1, 2014, specified building alterations or improvements shall require non- compliant plumbing fixtures to be replaced with water -conserving plumbing fixtures. On or before January 1, 2019, all non-compliant plumbing fixtures shall be replaced with water - conserving plumbing fixtures throughout the building (regardless of whether property undergoes alterations or improvements). ❑ My property is a commercial real property. See Civil Code Section 1101.5. On and after January 1, 2014, specified building alterations or irmprovements shall require non- compliant plumbing fixtures to be replaced with water -conserving plumbing fixtures., On or before January 1, 2019, all non-compliant plumbing fixtures shall be replaced with water- conserving plumbing fixtures throughout the building (regardless of whether property undergoes alterations or improvements). I, as the owner or owner's agent of this property, certify under penalty of perjury that non-compliant plumbing fixtures will be replaced prior to date specified above with water -conserving plumbing fixtures in accordance with Civil Code Sections 1101.1 through 110 1.8, the current California Plumbing Code and California Green Building Standards Code, and manufacturer's installation requirements, and that the waA cons ervingsplumbing fixtures comply with the requirements as indicated in the table on the followina nage. I Owner or Owner Agent's Signatur/,��j-- Date A7?�� Upon completing and signing this C frcate, please return it to the Building Division in order to final your bu lding ermit. SB407 2015.doc revised 08/26/15 BUILDING PER -MIT CANNOT BE FINALED AND COMPLETED UNTIL THIS CERTIFICATE HAS BEENSIGNED AND RETURNED:TO THE BUILDING DIVISION 1. If the existing plumbing fixture water usage/flow rate is equal to or lower than trie figure snown, it is not requires to oe upgrauea. SB407 2015.doc revised 08/26/15 Non -Compliant Water -Conserving Plumbing Fixture Plumbing Fixture/ (Fixture Complying with Current Code"Applicable to New Construction) Maximum Water=Usa a/Flow Rate Fixture Type Water Usage 2013 CPC Ch. 4 2013 CPC Ch. 4 2013 CPC Ch. 4 /Flow Rate 2013 CALGreen Div. 4.3 2013 CALGreen Div. 4.3 2013 CALGreen Div. 5.3 Single -Family Multi -Family Commercial Residential Residential Water Closets Exceed 1.6 Single flush toilets: 1.28 gallons/flush (Toilets) Gallons/flush Dual flush toilets: 1.28 gallons/flush effective flush volume (the composite, average flush volume of two reduced flushes and one full flush Urinals Exceed 1.0 0.5 gallons/flush Gallons/flush Showerheads Exceed 2.5 2.0 gallons per minute @ 80 psi. Also certified to the performance criteria"of gallons per minute U.S. EPA WaterSense Specification for Showerheads (A hand-held shower is considered a showerhead.) For multiple showerheads serving one shower, the combined flow rate of all showerheads and/or other shower outlets controlled by a single valve shall not exceed 2.0 gallons per minute @ 80 psi, or the shower shall be designed to allow only one shower outlet to be in operation at a time. ` Faucets — Exceed 2.2 gallons Maximum 1.5 gallons per Within units: 0.5 gallons per minute @ 60 Lavatory per minute minute @ 60 psi; minimum Maximum 1.5 gallons psi Faucets 0.8 gallons per minute @ per minute @ 60 psi; 20 psi minimum 0.8 gallons per minute @ 20 psi In common and public use areas: 0.5 gallons per minute @ 60 psi 1.8 gallons per minute 60 psi Faucets — Exceed 2.2 gallons 1.8 gallons per minute @ 1.8 gallons'.per minute 1.8 gallons per minute @ 60 Kitchen per minute 60 psi @ 60 psi psi Faucets May temporarily increase May temporarily up to 2.2 gallons per increase up to 2.2 minute @ 60 psi, and must gallons per minute @ default to maximum 60 psi, and must 1.8 gallons per minute @ default to maximum 60 psi 1.8 gallons per minute Where faucets meeting @ 60 psi the above are unavailable, Where faucets meeting aerators or other means the above are may be used to achieve unavailable, aerators or reduction. other means may be used to achieve reduction. 1. If the existing plumbing fixture water usage/flow rate is equal to or lower than trie figure snown, it is not requires to oe upgrauea. SB407 2015.doc revised 08/26/15 SMOKE / CARBON MONOXIDE ALARMS OWNER CERTIFICATE OF COMPLIANCE COMMUNITY DEVELOPMENT DEPARTMENT > BUILDING DIVISION 10300 TORRE AVENUE • CUPERTINO, CA 95014-3255 (408) 777-3228 o FAX (408) 777-3333 o building(ckupertino.org s 44 V s `a ti :&l 13 r_.5 #A) Wo Xr si .6lte: 3,QaT&,", M,t.iom-de: t PERMIT CANNOT BE FINALED AND COMPLETED UNTIL THIS CERTIFICATE HAS BEEN L-STET—NE12 AND RETURNED TO THE BUILDING DIVISION PURPOSE This affidavit is a self -certification for the installation of all required Smoke and Carbon Monoxide Alarms for compliance with 2013 CRC Section R314,2013 CBC Sections 420.6 and 907.2.11.2 where no interior access for inspections are required. GENERAL INFORMATION Existing single-family and multi -family dwellings shall be provided with Smoke Alarms and Carbon Monoxide alarms. When the valuation of additions, alterations, or repairs to existing dwelling units exceeds $1000.00, CRC Section R314 and CBC Sections 907.2.11.5 and 420.6 require that Smoke Alarms and/or Carbon Monoxide Alarms be installed in the following locations: AREA SMOKE ALARM CO ALARM Outside of each separate sleeping area in the immediate vicinity of the bedroom(s) X X On every level of a dwelling unit including basements X X Within each sleeping room X Carbon Monoxide alarms are not required in dwellings which do not contain fuel-burnuzg appliances and that do not have an attached garage. Carbon monoxide alarms combined with smoke alarms shall comply with CBC Section 420.6 and shall be approved by the Office of the State Fire Marshal. Power Supply: In dwelling units with no commercial power supply, alarm(s) may be solely battery operated. In existing dwelling units, alarms are permitted to be solely battery operated where repairs or alterations do not result in the removal of wall and ceiling finishes or there is no access by means of attic, basement or crawl space. Refer to CRC Section R314 and CBC Sections 907.2.11.4 and 420.6.2. An electrical permit is required for alarms which must be connected to the building wiring. As owner of the above -referenced property, I hereby certify that the alarm(s) referenced above has/have been installed in accordance with the manufacturer's instructions and in compliance with the California Building and California Residential Codes. The alarms have been tested and are operational, as of the date signed below. 1 have read and agree to comply with the terms and conditions of this statement .Name: / :: nature.................................................................fpate;j0.i% 7 Signature........... sLi.................................... Smoke and CO forni.doc revised 03/18/14