15120151_FIRE COMMENTS_1FIRE DEPARTMENT
SANTA CLARA COUNTY
14700 Winchester Blvd., Los Gatos, CA 95032-1818
(408) 378-4010 •(408) 378-9342 (fax) • www.scefd.org
PLAN
REVIEW No. 16 0488
BLDG 15120151
PLAN REVIEW COMMENTS PERMIT No.
Plans and Scove of Review:
'This project shall comply with the following:
1. The 2013 California Building /Fire Codes (CBC/CFC), as adopted by the City of Cupertino.
.The scope of this improvement project includes the following:
:Details for equipment anchorage on all 4 floors. New storage room (2090) added to Room 2071 on
:the 2nd floor. New non -rated shaft on the 4th Floor in Room 4022.
Plans are not approved. Resubmit drawings and provide a response letter addressing comments
on this plan review.
Plan Review Comments:
Comment #1
!NOTE
'Sheets A8.22 & A8.23 (showing proposed "New Storage Room 2090" & "New shaft on the 4th floor"),
,were not included on previous submittals of this project to the Fire Department, and per "Details 5 &
7" on sheet A8.22, and "Details 2 & 7" on sheet A8.23, it is noted that "Snorkels" will be installed in the
building. Please refer to comments #2 & #3 that follow.
Comment #2
Provide information of type of exhaust through the snorkels, and provide material safety data sheets,'
if applicable.
:Comment #3
.Some appliances with snorkels are located on 1st, 3rd & 4th floors (Sheets A8.22 & A8.23).
(Provide on drawings details & layout of proposed exhausts through the building.
Comment #4
;Alter the sprinkler system as needed by new partitions and ceilings. Submit shop drawings (3 sets)
<and a permit application to the Santa Clara County Fire Department for approval before altering the
City PLANS SPECS NEW RMDL AS
CUP ® ❑ ❑ ® ®
OCCUPANCY
BA-3
CONST. TYPE
II-B
ApplicantName DATE
Main Street Cupertino Aggregator 3/1/2016
PAGE
1 OF 2
SEC/FLOOR
4 Story
AREA
126,581 s.f.
LOAD
PROJECT DESCRIPTION
Commercial Construction
PROJECT TYPE OR SYSTEM
Tenant Improvement
NAME OF PROJECT
MAIN STREET CUPERTINO APPLE TI
LOCATION
19339
Stevens Creek Blvd Cupertino
TABULAR FIRE FLOW
REDUCTION FOR FIRE SPRINKLERS
REQUIRED FIRE FLOW ® 20 PSI
BY
Obrien, Gilery &
—
e
as the Santa Clara Countv Central Fire Protection District
Serving Santa Clara County and the communities of Campbell, Cupertino, Los Altos,
Los Altos Hills, Los Gatos, Monte Sereno, and Saratoga
FIRE DEPARTMENT
SANTA CLARA COUNTY
14700 Winchester Blvd., Los Gatos, CA 95032-1818
(408) 378-4010 • (408) 378-9342 (fax) • www.sccfd.org
PLAN
REVIEW No. 16 0488
BLDG 15120151
PLAN REVIEW COMMENTS PERMIT No.
system. Call (408) 378-4010 for more information.
NOTE: The "Building Department Permit Number" that corresponds to this project shall be
provided on sprinkler system shop drawings to be submitted for review.
Comment #5
:If the "Fire Alarm system" is to be altered/modified to accommodate this project, submit fire alarm
system shop drawings (3 sets) and a permit application to the Fire Prevention Division for review
and approval of modifications to the fire alarm system to accommodate this project. Call (408) 378
-4010 for more information.
;NOTE: The "Building Department Permit Number" that corresponds to this project shall be
provided on fire alarm system shop drawings to be submitted for review.
'Comment #6
What follows is a review by the Hazardous Materials Section.
;This installation shall comply with the following:
1. 2013 California Fire Code (CFC), as adopted by the City of Cupertino,
2. Chapter 9.12 of the Cupertino Municipal Code (CMC)
DISAPPROVED: Unable to complete review due to insufficient information submitted. Please
provide additional information which addresses the following items [CFC 105.2.11:
• Previous plans submitted for this scope of work did not include sheets A8.22 and A8.23. These
sheets show that snorkels will be installed in the building. Please describe the purpose of the snorkels
throughout the building.
(Please resubmit plans / specifications which address all of the items above. Following review of
resubmittal, additional conditions may apply.
City PLANS SPECS NEW RMDL AS
CUP N ❑ ❑ N H
OCCUPANCY
B,A-3
CONST. TYPE
II-B
AppllcantName DATE
Main Street Cupertino Aggregator 3/1/2016
PAGE
2 OF 2
SEC/FLOOR
4 Story
AREA
126,581 s.f.
LOAD
PROJECT DESCRIPTION
Commercial Construction
PROJECT TYPE OR SYSTEM
Tenant Improvement
NAME OF PROJECT
MAIN STREET CUPERTINO APPLE TI
LOCATION
19339 Stevens Creek Blvd Cupertino
TABULAR FIRE FLOW
REDUCTION FOR FIRE SPRINKLERS
REQUIRED FIRE FLOW 0 20 PSI
BY
O'brien, Gilery &
—�
as the Santa Clara County Central Fire Protection District
Serving Santa Clara County and the communities of Campbell, Cupertino, Los Altos,
Los Altos Hills, Los Gatos, Monte Serene, and Saratoga