16010048 CITY OF CUPERTINO BUILDING PERMIT
BUILDING ADDRESS: 888 CANDLEWOOD DR CONTRACTOR:AMERICAN SOLAR PERMIT NO:16010048
DIRECT
OWNER'S NAME: LU CHIEN-PING AND LEE CHARLENE S 11766 WILSHIRE BLVD STE 500 DATE ISSUED:01/07/2016
OWNER'S PHONE: 4088987209 LOS ANGELES,CA 90025 PHONE NO:(424)214-6700
JOB DESCRIPTION:RESIDENTIALCOMMERCIAL LICENSED CONTRACTOR'S DECLARATION 0 0
INSTALL(N)ROOFTOP MOUNTED SOLAR PV-22 PANELS
License Class 4' Lie.# Y( 7 GJ (5.94 KW); UPGRADE(E)PANEL TO(N)200 AMP PANEL
s /
Contractoa /l if�J�/C
I hereby affirm that I am licensed under the provisions of Chapter 9
(commencing with Section 7000)of Division 3 of the Business&Professions
Code and that my license is in full force and effect.
I hereby affirm under penalty of perjury one of the following two declarations:
I have and will maintain a certificate of consent to self-insure for Worker's
Compensation,as provided for by Section 3700 of the Labor Code,for the
performance of the work for which this permit is issued. Sq.Ft Floor Area: Valuation:$15000
ave •and will •maintain Worker's Compensation Insurance,as provided for by
Section 3700 of the Labor Code,for the performance of the work for which this APN Number:36919025.00 Occupancy Type:
permit is issued.
APPLICANT CERTIFICATION
I certify that I have read this application and state that the above information is PERMIT EXPIRES IF WORK IS NOT STARTED
correct.I agree to comply with all city and county ordinances and state laws relating WITHIN 180 DAYS OF PERMIT ISSUANCE OR
to building construction,and hereby authorize representatives of this city to enter
upon the above mentioned property for inspection purposes. (We)agree to save 180 D YS FROM LAST CALLED INSP C -ION.
indemnify and keep harmless the City of Cupertino against liabilities,judgments, 0
{6
costs,and expenses which may accrue against said City in consequence of the i
granting of this permit. Additionally,the applicant understands and will comply Issued by: Date:
with all non-point source regulations per the Cupertino Municipal Code,Section
9.18.
pd RE-ROOFS:
Signature / e` Date / '74 6, All roofs shall be inspected prior to any roofing material being installed.If a roof is
installed without first obtaining an inspection,I agree to remove all new materials for
inspection.
0 OWNER-BUILDER DECLARATION
Signature of Applicant: Date:
I hereby affirm that I am exempt from the Contractor's License Law for one of
the following two reasons: ALL ROOF COVERINGS TO BE CLASS"A"OR BETTER
I,as owner of the property,or my employees with wages as their sole compensation,
will do the work,and the structure is not intended or offered for sale(Sec.7044,
Business&Professions Code)
I,as owner of the property,am exclusively contracting with licensed contractors to HAZARDOUS MATERIALS DISCLOSURE
construct the project(Sec.7044,Business&Professions Code). I have read the hazardous materials requirements under Chapter 6.95 of the
California Health&Safety Code,Sections 25505,25533,and 25534. I will
I hereby affirm under penalty of perjury one of the following three maintain compliance with the Cupertino Municipal Code,Chapter 9.12 and the
declarations: Health&Safety Code,Section 25532(a)should I store or handle hazardous
I have and will maintain a Certificate of Consent to self-insure for Worker's material. Additionally,should I use equipment or devices which emit hazardous
Compensation,as provided for by Section 3700 of the Labor Code,for the air contaminants as defined by the Bay Area Air Quality Management District I
performance of the work for which this permit is issued. will maintain compliance with the Cupertino unicipal Code,Chapter 9.12 and
I have and will maintain Worker's Compensation Insurance,as provided for by the Health&Safety Code,Sectio 25505, 4.
Section 3700 of the Labor Code,for the performance of the work for which this //‘ f
Owner or authorized ager'�r )ti > 1/� '• e: ` ��1
permit is issued.
I certify that in the performance of the work for which this permit is issued,I shall
not employ any person in any manner so as to become subject to the Worker's CONSTRUCTION LENDING AGENCY
Compensation laws of California. If,after making this certificate of exemption,I •
become subject to the Worker's Compensation provisions of the Labor Code,I must I hereby affirm that there is a construction lending agency for the performance of
forthwith comply with such provisions or this permit shall be deemed revoked. work's for which this permit is issued(Sec.3097,Civ C.)
Lender's Name
APPLICANT CERTIFICATION Lender's Address
I certify that I have read this application and state that the above information is
correct.I agree to comply with all city and county ordinances and state laws relating
to building construction,and hereby authorize representatives of this city to enter
upon the above mentioned property for inspection purposes.(We)agree to save ARCHITECT'S DECLARATION
indemnify and keep harmless the City of Cupertino against liabilities,judgments,
costs,and expenses which may accrue against said City in consequence of the I understand my plans shall be used as public records.
granting of this permit.Additionally,the applicant understands and will comply
with all non-point source regulations per the Cupertino Municipal Code,Section Licensed Professional
9.18.
Signature Date
•
--- ALTERNATIVE ENERGY PERMIT APPLICATION
COMMUNITY DEVELOPMENT DEPARTMENT•BUILDING DIVISION A.
S;: : 10300 TORRE AVENUE•CUPERTINO, CA 95014-3255
CUPERTINO (408)777-3228 {c�
FAX(408)X77-3333•buildinqcuoertino.orq ) 46
PROJECT ADDRESS 9 jbol
APN Riq 005
OWNER NAME o (P. I '1 11 1,C '--^"\. ' Le-e PHONE P� o� E-MAIL
STREET ADDRESS Lf �4. f 000ei` (r. C,FY, STATEpi- l G1 - / J 0 O V ( P ..
CONTACT NAME e � /� ^ PHONE NiA s m
4,5
�,)c�c c(VC�;in G�+2 `i j a 3/0-CO -4(611 ht v c eirti5 �,7c � �
STREET ADDRESS CITY,STATE,ZIP F. ,-
-
//
A Ole f Ai, J aCo
❑ OWNER 0 OWNER-BUILDER 0 OWNEERAGENT 'KCOITYRACTOR 0 CONTRACTOR AGENT 0 ARCILTECT 0 ENGINEER 0 DEVELOPER 0 TENANT
CONTRWTOR NAME a •
LICENSE NUI/BE LICENSE TYPE BUS.LIC"
("14A/PP i3OC /1 g da- b ire I v/6107 ( c,- 4/6 I
COMPANY NAME I E-MAIL FAX
LSP
STREET ADDRRjESS / i• ! /Q f CITY,S ATE,ZIP /� PHONE
ARCHITECT/ENGINEER NAME LICENSE NUMBER �/ BUS.LIC m
COMPANY NAME E-MAIL FAX
STREET ADDRESS CITY,STATE,ZIP PHONE
USE OF 0<ED or Duplex 0 Multi-Family PROJECT IN WILDLAND PROJECT IN
STRUCTURE: 0 Commercial URBAN INTERFACE AREA ❑ Yes 0 No FLOOD ZONE 0 Yes 0 No
•
/ CWATERHEATING 0 OTHER:
i' `OLAR PANELS 0 ELECTRIC VEHICLE CHARGING STATION 0 SOLAR
FOR SOLAR PANELS: NUMBER OF PANELS/UNITS:5 eif KILOWATTS(COMMERCIAL ONLY): TOTAL VALUATION/Lc-00o
DESCRIPTION OF WORK44115! fY// C/(.C54/ ,e,o r /i',�014—mf eI �(,P- a r/7 fj :5'--0! 7 !` Id
S 2- 44419 ,GLSa t rte+ cer e.ff el--P t Grv,L.e.
cEIigD .
� : sem
t 1 � a ,ems .
By my signature below,I certify to each of the following: I am th. .perry owner or authorized agent to act on the property owner's behalf. I have read this
application and the information I have provided is correct. I -• read the Description of Work and verify it is accurate. I agree to comply with all applicable local
ordinances and state laws relating to bu' tructio•. authorize representatives of Cupertino to enter the above-identified pro•erty for inspection purposes.
Signature of Applicant/Agent: ;_ Date:
S PPLEMENTAL INFORMATION REQUIRED r10E nr.qE O+ZY
W
- OTTR"'rrr7 COUI TER ,n,-
- --YXPRES , ` -- — £,
gS2A,`DARD�Ewa f
PI/App 2011.doc revised 03/16/11
1 SMOKE / CARBON MONOXIDE ALARMS
IL E
OWNER CERTIFICATE OF COMPLIANCE 7 -�,
COMMUNITY DEVELOPMENT DEPARTMENT•BUILDING DIVISION
CUPERTINO 10300 TORRE AVENUE•CUPERTINO, CA 95014-3255
(408)777-3228• FAX(408)777-3333•buildinq(a�cupertino.orq
(AMPLE- � _ Permit No. /6a/CO 48
Address _CJeto i,0003) '11z( #of Alarms Smoke: Carbon Monoxide:
PERMIT CANNOT BE FINALED AND COMPLETED UNTIL THIS CERTIFICATE
HAS BEEN,SIGNED AND RETURNED TO THE BUILDING DIVISION
PURPOSE
This affidavit is a self-certification for the installation of all required Smoke and Carbon Monoxide Alarms for
compliance with 2013 CRC Section R314,2013 CBC Sections 420.6 and 907.2.11.2 where no interior access for
inspections are required.
GENERAL INFORMATION
Existing single-family and multi-family dwellings shall be provided with Smoke Alarms and Carbon
Monoxide alarms. When the valuation of additions, alterations, or repairs to existing dwelling units exceeds
$1000.00, CRC Section R314 and CBC Sections 907.2.11.5 and 420.6 require that Smoke Alarms and/or Carbon
Monoxide Alarms be installed in the following locations:
AREA SMOKE ALARM CO ALARM
Outside of each separate sleeping area in the immediate vicinity of the X X
bedroom(s)
On every level of a dwelling unit including basements X X
Within each sleeping room X
Carbon Monoxide alarms are not required in dwellings which do not contain fuel-burning appliances and that
do not have an attached garage. Carbon monoxide alarms combined with smoke alarms shall comply with
CBC Section 420.6 and shall be approved by the Office of the State Fire Marshal.
Power Supply: In dwelling units with no commercial power supply, alarm(s)may be solely battery operated.
In existing dwelling units, alarms are permitted to be solely battery operated where repairs or alterations do
not result in the removal of wall and ceiling finishes or there is no access by means of attic,basement or crawl
space. Refer to CRC Section R314 and CBC Sections 907.2.11.4 and 420.6,2.An electrical permit is required for
alarms which must be connected to the building wiring.
As owner of the above-referenced property, I hereby certify that the alarm(s) referenced above has/have been
installed in accordance with the manufacturer's instructions and in compliance with the California Building
and CaliforniarCalifornia Residential Codes. The alarms have been tested and are operational, as of the date signed
below.
1 have read and agree to comply w' the terms pd conditio s of this statement
Ow er(or Owngr Agent's)Name: /
—rt A --- f -'-
(� 2N 111 L( Signature (17441(
Contractor Name: QQ r
1/ Air
yL/P.J/CELL! goal. A/ect Signature `We/.a.Okla .4 Lic.#......(...7A57.!C7 e Date: . .
Smoke and CO form.doc revised 03/18/14
\k�, i/, WATER-CONSERVING PLUMBING FIXTURES
FILE
OWNER CERTIFICATE OF COMPLIANCE
r,\ COMMUNITY DEVELOPMENT DEPARTMENT•BUILDING DIVISION
CUPERTINO 10300 TORRE AVENUE•CUPERTINO,CA 95014-3255
(408)7- 3228•F (408)777-3333• buildinqa.cupertino.orq
Owner Name TY‘ ) c( Permit No, /COMO g
Address - r Cpi '2wtoci P} . a ? z7Ji0r (3 c 3p-
1.
1. Is your real property a registered historical site? l
❑ Yes Civil Code Sections 1101.1 through 1101.8 do not apply. Skip the rest of the form and sign bottom of form.
,t No Go to Question 2.
2. Does your real property have a licensed plumber certifying that, due to the age or configuration of the property or its
plumbing,installation of water-conserving plumbing fixtures is not technically feasible?
❑ Yes Civil Code Sections 1101.1 through 1101.8 do not apply.
❑ The licensed plumber's certification has been provided to the Building Division.
Skip the rest of the form and sign bottom of form.
j4 No Go to Question 3.
3. Is water service permanently disconnected for your building?
LI Yes Civil Code Sections 1101.1 through 1101.8 do not apply. Skip the rest of the form and sign bottom of form.
No Go to Question 4.
4. Is your real property built and available for use or occupancy on or before January 1, 1994?
❑ No My real property is built and available for use or occupancy after January 1, 1994.
Civil Code Sections 1101.1 through 1101.8 do not apply. Skip the rest of the form and sign bottom of form.
Ck Yes My real property is built and available for use or occupancy on or before January 1, 1994.
Civil Code Sections 1101.1 through 1101.8 apply. Check one of the three following statements and sign
bottom of form..
5. Please check ONE of the following:
My property is a single-family residential real property. See Civil Code Section 1101.4.
On and after January 1, 2014, building alterations or improvements shall require all non-compliant plumbing fixtures
to be replaced with water-conserving plumbing fixtures throughout the building.On or before January 1,2017,all non-
compliant plumbing fixtures shall be replaced with water-conserving plumbing fixtures (regardless of whether
property undergoes alterations or improvements).
❑ My property is a multifamily residential real property. See Civil Code Section 1101.5.
On and after January 1,2014,specified building alterations or improvements shall require non-compliant
plumbing fixtures to be replaced with water-conserving plumbing fixtures.
On or before January 1,2019,all non-compliant plumbing fixtures shall be replaced with water-
conserving plumbing fixtures throughout the building(regardless of whether property undergoes alterations or
improvements).
❑ My property is a commercial real property. See Civil Code Section 1101.5.
On and after January 1, 2014,specified building alterations or improvements shall require non-compliant
plumbing fixtures to be replaced with water-conserving plumbing fixtures.
On or before January 1, 2019, all non-compliant plumbing fixtures shall be replaced with water- conserving
plumbing fixtures throughout the building(regardless of whether property undergoes alterations or improvements).
I,as the owner or owner's agent of this property,certify under penalty of perjury that non-compliant plumbing fixtures will be
replaced prior to date specified above with water-conserving plumbing fixtures in accordance with Civil Code Sections 1101.1
through 1101.8,the current California Plumbing Code and California Green Building Standards Code,and manufacturer's
installation requirements,and that the water-conservin lumbing fixtures comply with the requirements as indicated in the
table on the following page.
Owner or Owner Agent's Signature: ( Date: dud /( --, 6
Upon completing and signing this Certificate,please return it o th uilding Division in order to final your built ng permit.
SB407 2015.doc revised 08/26/15
CITY OF CUPERTINO 1601004g
FEE ESTIMATOR-BUILDING DIVISION
ADDRESS: 888 Candelwood Dr DATE: 01/07/2016 REVIEWED BY: PAUL
• APN: 369 19 025 BP#: • *VALUATION: $15,000
*PERMIT TYPE: Building Permit PLAN CHECK TYPE: Addition
PRIMARY PENTAMATION
SFD or Duplex SOLAR-RES
USE: PERMIT TYPE:
WORK Install (N) rooftop mounted solar PV- 22 Panels(5.94 KW); Upgrade(E) panel to (N) 200 Amp Panel
SCOPE
1
AitchNan€.hez:* L..]; P; ; / ; /(..,eck [ [ Elec.Plan Check ! 0.01 hrs $0.00
J •.Pee: Plumb,, ` m t Fee: Elec.Permit Fee: 1EPERMIT
;t.,,. !;;,. n O bei .'t;£ Jew n _ Other Elec.Insp. F.c.71 hrs $48.00
:l.
tech bap
t,cc Plumb Imp , v. f £c. Insp 1'ee
NOTE:This estimate does not include fees due to other Departments(i.e.Planning,Public Works,Fire,Sanitary Sewer District,School
District,etc.). These fees are based on the preliminary information available and are only an estimate Contact the Dept for addn'1 info.
FEE ITEMS (Fee Resolution 11-053 Fff. 7/1/13) FEE QTY/FEE MISC ITEMS
Plan Check Fee: $0.00 1 # Alternative Energy System
Suppl.PC Fee: c Reg. 0 OT 0.0 hrs $0.00 $236.00 1PHOTOVRES Photovoltaic System A
PME Plan Check: $0.00 200 amps Electrical
Permit Fee: $0.00 $48.00 1BELEC200 Services
Suppl.Insp.Fee:0 Reg. 0 OT 0.0 hrs $0.00
PME Unit Fee: $0.00
PMEPermit Fee: $48.00
..snsiructioe Lay.
Administrative Fee: 1ADMIN $45.00
Work Without Permit? 0 Yes ® No $0.00
Advanced Planning Fee: $0.00 Select a Non-Residential 0
Building or Structure 0
Travel Documentation Fee: 1TRAVDOC $48.00
Strong Motion Fee: 1BSEISMICR $1.95 Select an Administrative Item
Bldg Stds Commission Fee: IBCBSC $1.00
SUBT(}TA .S $143.95 $284.00 :4 TOTAL NSE I $427.95
Revise • 01/01/201
SHEET INDEX PROJECT DESCRIPTION:
PROJECT DEVELOPER
PV-1 SITE PLAN &VICINITY MAP
PV-2 ROOF PLAN &MODULES 22x270W ROOF MOUNTED SOLAR �
PV-3 MOUNTING DETAIL& P.O.0 DETAILCPAfyIUNITY DF�•'F PHOTOVOLTAIC MODULES CS American
PV-4 ELECTRIC LINE DIAGRAM '_COPi"� 'JT r' pr'�RT1�IENT SYSTEM SIZE: 5.94 kW DC STC PROJECT SITE Solar Direct
PV-5 WIRING CALCULATIONS B�II-alt�� DIVISION - CUP`r�TINO \ 11766 WILSHIRE BLVD.,
PV-6 PLACARDS APPROVED EQUIPMENT SUMMARY SUITE Soo
PV-8 EQUIPMENT SPECIFICATION This set of Plan./
speCrflcatier,s �,t�ST be kept at the 22 SUNEDISION : SE F270 KzD-3y A c I/ „ PH:(855)765-2755
PV-7 EQUIPMENT SPECIFICATIONLOS ANGELES,CA 90025
01 SOLAREDGE: SE6000A-US(240V)INVERTER + FX:(424)214-6750
job Site during c:;rStrUction It is uinla.tiful to make any
PV-9 EQUIPMENT SPECIFICATION :hangest of alterations on same or to deviate EXISTING 100A ELECTRICAL SERVICE PANEL .M- wEe:nttp://www.americansola direct.com
PV-10 EQUIPMENT SPECIFICATION TO BE UPGRADED TO 200A `
PV-11 EQUIPMENT SPECIFICATION therefrom, WIU, ut approval from the Building Official. _���,-� REVISIONS
The StamI -air ` DESCRIPTION DATE REV
PV-12 EQUIPMENT SPECIFICATION P► of thi;plan anc}specifications SHALL NOT
PV-13 EQUIPMENT SPECIFICATION be held to pmi.t•or b be an approval of the violation I
,•-K
•• '” " • City Correction 4.16
PV-14 EQUIPMENT SPECIFICATION ' '1/4 ,
PV-15 EQUIPMENT SPECIFICATION 6Y any ell L.,
, { nX e °r �Ce or State Latin, PLAT PLANS ECKED Br, `�
PV-16 GROUNDING DETAIL .�-
PV-17 ROOF FLASHING PATE Y, ' ' y ft 4•% THIS DRAWING IS PROPERTY OF
�ER.IVIT # �� r DATE i
1�` -. ,N, AMERICAN SOLAR DIRECT INC.THIS
+1 � r DRAWING IS USED IN CONFIDENTIAL AND IS
„f' ONLY TO BE USED IN CONDUCTION
PLANNING DEPT - . -. WITH WORK DESIGNATED BY
S►. AMERICAN SOLAR DIRECT INC.NO
PA" E
CUPERTINO - ' � 11r "• DISCLOSEDSC F TD OTHERS TISHO T
TO OTHERS WITHOUT
r "' *' THE PRIOR WRITTEN PERMISSION
-41, , OF AMERICAN SOLAR DIRECT INC.
`T — 96-6 SIDE PROPERTY LINE ' " ) 'r 4 �-� ''' .* I "�
(11) SUNEDISION : (E)CHIMNEY .- , i J, CONTRACTOR INFORMATION
�� - C-10 LICENCE HOLDER
SE F270 KzD-3y w - MAURICIO RODRIGUEZ
ROOF#1 l AP(E) �� J s �� MRODRIGUEZ@AMERICANSOIARDIRECT.COM
„ 114-0 VIII
(626) 435-9221
WIt— Signature-Maurice Rod guez
1-STORY LICENSE C10/C46IC39#941069
/ HOUSE ATIO I a HOUSE PHOTO
L� SCALE: NTSa.
1111, 1111OFFICE CIIp,.
1111111
IO
w
O
I--
liii I PROJECT SITE J
0 11 I W E_
a (E) rn O
U
a. EXISTING GARAGE `J;,,`f''1'. :: .. 6.i+__+, . T 1----.
.. ' ' W ti O
DRIVEWAY (3)SUNEDISION : 1 �•'' : tai ).,la.' :-rtJ ,i,_; - -J w p d�
W I I Ell 11 I 1.. E F27 KzD- E' y vow t. . Q U O Q a) O 07)
0 1111 S 0 3y _ �,- I�rn�nTerylSchoal o= W O U
Di �' — 211-6" 11 1111,11, I ROOF#4 7.;...„- a "►*. R► r u oU Oo M(E) PATIO ` �•r. i f .�' i 1:1`-.1• a� WJ
Z S (2)SUNEDISION . ,� • ,� . l • '' ' ;i .` ..7 O J Q'p W _;— Z
b
Mlm• MEM
r .4,« 8S3 7neltznIelmso:Drj..•. .% + ± C� Z W Z v Z
Q CO — — SEF270KzD 3 , . c^ . .� ' Z(6)SUNEDISION : — •� �� y -'• . ,ROOF#3 _. d U D 02 J QSE F270 KzD 3y 96'-6" ROPERTY `r� , - .; z ao U QU SIDE P2
ROOF#2LINE c� (N)MAI !:, ® u� °o
C;� �� PANEL • �� `"''a.----� 0 r r, .� = co W
` .4 Hyde Middle Schnr'.a --=ted
f .i ! r g.Rt.
6uiiding Department ���9et Rd, -`I .r ;". u ! eli '�'rk _ �, _, U
qc:
11.
.. . ' I V ED 'g r AA;; rr� -r. ~�` F " :,•.P:�� + r. !r SHEET NAME
pm U 7 20 6 Or h r �_4.,. �' ,r
C nrd F8 nl5 i
�' .� z'.;'a. S 1 pping.CenLer ��.;� - : . . SITE PLAN &
JAN O7 2016 COMPLIANCE jr`1. I rr" -"�' = ,, VICINITY MAP
GOVERNING CODES R``vilzwED FOR CODE a - r • :,.
CALIFORNIA ELECTRIC CODE, 2013 EDITION (CEC) B 3 9tai(U �' • t_ I f yf• • , ',I _ �' ill* �.}–-'. , • SHEET SIZE
CALIFORNIA RESIDENTIAL CODE, 2013(CRC)
Revie.:ed BY
ANSI B
CALIFORNIA PLUMBING CODE, 2013(CPC) 11" X 17"
CALIFORNIA BUILDING CODE, 2013 EDITION (CBC) VICINITY MAP
CALIFORNIA MECHANICAL CODE, 2013(CMC) SHEET NUMBER
- ARTICLE 690, NEC 2011 CODE BOOK 1 SITE PLAN WITH ROOF PLAN SCALE: NTS
TITLE 24 RESIDENCE ENERGY EFFICIENCY STANDARDS PV-1CAL-FIRE PHOTOVOLTAIC INSTALLATION GUIDELINES PV-1 SCALE: 1/16"=1'-0"
•
MODULE TYPE, DIMENSIONS & WEIGHT PROJECT DEVELOPER
MODULE TYPE=SUN EDISON-SE F270 KzD-3y ///����j�i
MODULE WEIGHT=42.54 LBS /
u 4/` American
MODULE DIMENSIONS=65.3"x 39"=17.67 SF
UNIT WEIGHT OF ARRAY=2.98 PSF Solar Direct
11766 WILSHIRE BLVD.,
ROOF DESCRIPTION SUITE500
Q ROO TYPE-CONCRETE FLAT TILE ROOF LOS ANGELES,CA 90025
(E)CHIMNEY ROO TILT(#1,#2,#3)-20° PH: 765-2755
FX:(855)24 211 -6750
j;(' o aillIl �, RO• AZIMUTH(#1,#2) 180°
1
r- i, ROO. AZIMUTH(#4)-90° WEB:MtpJ/www.emeriw�rsolardired.com
RAE ERS(#1)-2X12 @ 16"O.0 REVISIONS
11 RAF ' RS(#2) 2X8 @ 24"O.0 DESCRIPTION DATE REV
RAF ERS(#3)-2X8 16"O.0 Cit Correction
@ Y 1.4.16 Q
® X11111111/' 121 TOT L ROOF AREA=3165.0
k1111111 b
395.'./3165.0= 12%OF ROOF
AUL -� Q FAC. AREA COVERED BY ARRAY
THIS DRAWING IS PROPERTY OF
AMERICAN SOLAR DIRECT INC.THIS
I 0 M 1lillibk ›-
DRAWING IS CONFIDENTIAL AND IS
BILL OF MATERIAL ONLY TO BE USED IN CONJUCTION
IWITH WORK DESIGNATED BY
A
I� SZ
AMERICAN SOLAR U DISCLOSED TO OTHERS
INC.NO
ART OF THIS DOCUMENT IS TO BE
2'-6" 21-6" A1 O'-On - 6'-8" „ WITHOUT
7'-0"
6'-0" Ai Q
A'EA COVERED(SQ. FT.) 395.56 THE PRIOR WRITTEN PERMISSION
OF AMERICAN SOLAR DIRECT INC.
O M -;,'''V 1 ' ' 36^F SET BACKlip411 ,n_'__ in A G. LOAD PER CONNECTION POINT(LBS) 27.57 CONTRACTOR INFORMATION��►��,, ► ,, ' ,11, C-10 LICENCE HOLDER
fO �� � . „MR� = W IGHT PER SQ. FT.OF SOLAR ARRAY(PSF) 2.93 MAURICIO RODRIGUEZ
__ •�.. .��....� �' 11111\.• ■�■.��_ _I
o - „ `�11' I p ��TAL WEIGHT OF MODULES 921.58 MRODRIGUEZEAMERICANSOLARDIRECT.COM
iit'I'I
►-' ') ' �1� 626 435-9221
__I1TAL WEIGHT OF OPTIMIZERS 46.2� __' '' Signature-Maurido Rodriguez
1 •' 'iiiii i LICENSE C10/C46/C39#941069
�a��.� �� � om mii>-" T-- i I 01 , �I�r��.�'� •TAL WEIGHT OF RACKING COMPONENTS 236.27
lit
TOTAL SYSTEM WEIGHT(LBS) 1157.85
z ►'� � m = TATAL RAIL LENGT 0.87
,- --, PERTlN6
����� Man � \ �� w I # •F 10'SNAP N RAS, ''",;1
p ����i� � �I'° w i tYr�.;,l, �'�ilding Depa►tme�t
PROJECT NAME
® LL 1 # •F13'SNAP NRAI ' !' 62" 7
LL V—
® I . ..t, °,I . .i I r r
T')TAL RAIL LENGTH[_=:, 175.83 W
Lu
lLJ 12'-4" FOR CODE COf�PLIANC= J LLi
3'-O" I •r1 � ' # b F SNAP N RACK
1F !Or
—.Z _ i1 ---- 20'-1" 16'-11" 1�■1i�1f 36"FIRE SET BACK op TrITAL#OF END-CLAMPS �� w °' NQ O o111111 ,.���� 1.x �.; n Reviewed By: � a4 z 0 0 CNJ 0 .�
d M 36"FIRE SET BACK , ' �'� 0' '!.!� ch T TAL#OF MID-CLAMPS 28 N_J rn ,• E p
N r ' �� ' ;'r ' a TOTAL#OF STANDOFF ASSEMBLIES 42 t� U rn or-cap -•-••-- , gillialligait47'
111 -I = Zco Q 11\1 IN o w o
wW 1111\111 �— I- o o� o � � cr'
11111111 oFESS/o a ",W
ill �- o
v � 1111111 � � e� ti 39.4"), J �o wiz
O =
11w ���ii :r ► ', _r �O �G TR(/D q� �U Z Zv I , o k Z Qao ain � U � 2JQ
tro 1� 1111111 N0.C70784 m - ao U EXP.06/30/2017 m - w co
111 ,� o w
(N)SNAP N RACK ®DC ACD I (N)200AMP MAIN (>q CIV II etri
U
( 100 RAIL(TYP.) SERVICE PANEL TF OF CAI�FO
HANWHA-Q CELL: (N)JUNCTION 12'-9�� 3/4" EMT CONDUIT SHEET NAME
BOX TYP. RUN 01/06/2016 4SUNEDISION ROOF PLAN &
s-P AK :L G3- 70 r _
(ROO #1,#2, •3) DISCONNECT • SE F270 KzD-3y MODULES
SNAP N RACK (N) INTEGRATED LEGEND VENT,ATTIC FAN
ATTACHMENT DC DISCONNECT O ❑ SHEET SIZE
(ROOF#1,#2,#3) ■ -JUNCTION BOX (ROOF OBSTRUCTION)
(N)SOLAREDGE: INV -INVERTER 0 -ROOF ATTACHMENT
ANSI B
SE6000A-US (240V) -TRUSSES 11" X 17"
DC 1 -INTEGRATED DC DISCONNECT ____ _CONDUIT
MSP -MAIN SERVICE PANEL SHEET NUMBER
1 ROOF PLAN & MODULES ® -CHIMNEY PV-2
ACD -AC DISCONNECT
PV-2 SCALE:3/32"=1'-0"
(E) FRAMING _ PROJECT DEVELOPER
MEMBERS GENERAL NOTES h
1 �!__ — SOLAR PANEL - (Nc American
iSECURING CLIPS 1. SOLAR PHOTOVOLTAIC SYSTEM TO BE INSTALLED ON RESIDENTIAL STRUCTURE. I Solar Direct
PV MODULE 2. DESIGN COMPLIES WITH THE 2013 EDITION OF THE CRC,AND 2011 NEC,AND ALL LOCAL ORDINANCES AND POLICIES. 11766 WILSHIRE BLVD.,
3. THIS PROJECT HAS BEEN DESIGNED IN COMPLIANCE WITH THE CBC SECTION 1609 TO WITHSTAND A MINIMUM 110 MPH WIND LOAD. SUITE 500
LOS ANGELES,CA 90025
r! - POINT OF CONNECTION 4. THIS SYSTEM WILL NOT BE INTERCONNECTED UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND THE UTILITY IS OBTAINED. PH:(855)765-2755
AT(E)ROOF FRAMING 5. THIS SYSTEM ISA UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES. FX:(424)214-6750
MEMBERS @ 6'-0"MAX. 6. IF THE EXISTING MAIN SERVICE PANEL DOES NOT HAVE A VERIFIABLE GROUNDING ELECTRODE,IT IS THE CONTRACTORS RESPONSIBILITY TO
INSTALL SUPPLEMENTAL COPPER GROUNDING ELECTRODE. WEB:http:/Iwww.americarrsolardirect.com
6 IMIII•I AKII 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED ON THE MODULE AND THE MANUFACTURERS REVISIONS
INSTALLATIONS INSTRUCTIONS. DESCRIPTION DATE REV
24"MAX
8. REFER TO SHEET E.3 FOR SIGNAGE"CAUTION:SOLAR CIRCUIT"STICKER TO BE INSTALLED EVERY 5 FEET AND 90 DEGREE BENDS OF CONDUIT. City Correction I A.I6 Q
RACKING SYSTEM 9. ALL CONDUIT TO RUN ON THE EXTERIOR OF THE HOUSE(NO CONDUIT TO BE INSTALLED IN ATTIC SPACE).
10. SOLAR PANELS SHALL BE INSTALLED WITH NO PORTION MORE THAN 18 INCHES ABOVE THE ROOF IMMEDIATELY BELOW. •
11. THE ROOF MOUNTED PHOTOVOLTAIC SYSTEM SHALL HAVE THE SAME OR BETTER LISTED FIRE-RESISTANCE RATING THAN THE BUILDING ROOF-
PORTRAIT PANEL COVERING MATERIAL. THIS DRAWING IS PROPERTY OF
AMERICAN SOLAR DIRECT INC.THIS
12. REMOVAL OF A DWP-INTERACTIVE INVERTER OR THE EQUIPMENT SHALL NOT DISCONNECT THE BONDING CONNECTION BETWEEN THE DRAWING IS CONFIDENTIAL AND IS
GROUNDING ELECTRODE CONDUCTOR AND THE PHOTOVOLTAIC SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTOR. ONLY TO BE USED IN CONDUCTION
WITH WORK DESIGNATED BY
1 POINT OF CONNECTION DETAIL 13. ALL FIELD INSTALLED JUNCTION,PULL AND OUTLET BOXES LOCATED BEHINDS MODULE OR PANEL SHALL BE ACCESSIBLE DIRECTLY OR BY AMERICAN SOLAR DIRECT INC.NO
PART OF THIS DOCUMENT IS TO BE
DISPLACEMENT OF MODULES(S)OR PANEL(S)SECURED BY REMOVABLE FASTENERS. DISCLOSED TO OTHERS WITHOUT
THE PRIOR WRITTEN PERMISSION
PV-3 SCALE: NTS 5/16"x 2.75"S.S. BOLT&5/16" 14. ONE-AND TWO-FAMILY DWELLINGS,LIVE PARTS IN PV SOURCE CIRCUITS AND PV OUTPUT CIRCUITS OVER 150 VOLTS TO GROUND SHALL NOT OF AMERICAN SOLAR DIRECT INC.
BE ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS WHILE ENERGIZED. CONTRACTOR SPLIT LOCK WASHER INFORMATION
15. NO PIPING,DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL BE PERMITTED TO BE LOCATED WITHIN THE DEDICATED SPACE C-10 LICENCE HOLDER
,�� ABOVE THE ELECTRICAL EQUIPMENT. MAURICIO RODRIGUEZ
PV MODULE 16. "CAUTION:SOLAR ELECTRIC SYSTEM CONNECTED"LABEL SHALL BE LOCATED ON MAIN SERVICE PANEL. MRODRIGUEZ@AMERICANSOLARDIRECT.COM
(626) 435-9221
SNAP N RACK END CLAMP SNAP N RACK LICENSEC10/C46/C3 Rodriguez
69
-- SERIES 100 RAIL — Signature-Mauricio Rodriguez
- SNAP N RACK STAND MOUNTING SYSTEM SPECIFICATIONS
OFF CLAMP \147-4.--„, SNAP N RACK CHANNEL NUT MANUFACTURER: CUPERTIN� '5/16"X 2e S.S. BOLT&5/16" SNAP N RACK PV MOUNTING SOLUTIONS \a�.a i f, artrrtent
S.S. SPLIT WASHER 775 FIERO LN,SUITE 200,SAN LUIS OBISPO,CA 93401 Building Dep PROJECT NAME
i �t (877)732-2860 f
SNAP N RACK RUBBER _' EMAIL:tech@snapnrack.com E- ,AN 0 7 2016` W
RAIN COLLAR INSTALLS `;,k ice.=' 1 W
TOP OF FLASHING ' SERIES 100 RESIDENTIAL MOUNTING SOLUTION • J
r� W E
FLASHING AO MATERIALS: REVIEWED FOR CODE COMPLIANCE Wo
6000 SERIES ALUM. �{ 9�uyLN z Ct O O N
SNAP N RACK STANDOFF STAINLESS STEEL,GALVANIZED STEEL Reviewed By: ti W a 0) 6 E
SHAFT STD(VARIOUS SIZES) co< 0 < rn O
CALLS+CERTIFICATIONS: MO= Z 0 U
ASCE 7-10 WIND SPEEDS FROM 110 MPH TO 190 FOR B AND C EXPOSURE CAT. N U W O M
tAl
(E)CONCRETE FLAT TILE ROOF ASCE 7-10 SEISMIC DESIGN CATEGORY E o°i OW> Z_ P
` r- -- ASCE 7-10 SNOW LOADS UP TO 120 PSF GROUND SNOW LOAD I C./)LLI
I 0 Ir `.O
,��'♦' BUILDING WITH MEAN ROOF HEIGHTS UP TO 60 FOOT TILT ANGLES/ROOF PITCHES FROM d W J
111111.111:
���' 0 DEGREES TO 60 DEGREES. O zwzUZ
WZ
j ': GROUNDING U cL =O J Q
'� / UL LISTED SNAP N RACK GROUND LUG,BONDING CLAMP&CHANNEL NUT, I co 0 0- Q
STAR WASHER W QD G
' THE ROOF MOUNTED PHOTOVOLTAIC SYSTEM IS UL 1703/2703 TESTED FOR SYSTEM FIRE = CO W
(E)SUBSTRATE RATING CLASS A WITH TYPE 1 MODULES(SNAP N RACK UL FILE E359313) 0
•
SEAL PENETRATION AND $ MODULES SHALL BE INSTALLED WITH A MINIMUM 7 INCH CLEARANCE FROM ROOF SURFACE
UNDER BASE WITH ROOF SEALANT. � TO PANEL. L-
5/16"x3/4"S.S LAG SCREW V SHEET NAME
WITH FLAT WASHER 2.5" 5/16"x 1"S.S. BOLT&5/16" S.S.
EoFES
MOUNTING &
MINIMUM EMBEDMENT SPLIT WASHER INSTALLED o � POC DETAIL
FROM BACKSIDE OF STANDOFFti(E) FRAMING BASE PRIOR TO INSTALLATION G' SHEET SIZE •
MEMBERS o N0.C70784 m
ce. EXP.06/30/2017 ANSI B
* i * Ir rI
11 X17
(Tqt CIV 1k_ ��\P
2 ROOF SECTION (SIDE ENLARGED VIEW) 6.0E CAvFo SHEET NUMBER
_
PV-3 SCALE: NTS 01/06/2016 PV-3
PROJECT DEVELOPER
SOLAR ARRAY(5.94kW-DC STC)
(11)MODULES CONNECTED IN SERIES STRING.
(11)MODULES STRINGS ON ROOF#1 ,��American
(11)MODULES CONNECTED IN SERIES STRING. L—! Solar Direct
11766 WILSHIRE BLVD.,
(6)MODULES STRINGS ON ROOF#2
500
(2)MODULES STRINGS ON ROOF#3 ELS
LOS ANGELES,
C
90025
(3)MODULES STRINGS ON ROOF#4 5
PH:(8555)7 765--22 6 755
FX:(424)214-6750
WEB:http://mrw.amencansolardirect.com
REVISIONS
(2)#10 AWG USE-2/PV WIRE+Red (2)#10 AWG THWN-2+Red TO UTILITY GRID DESCRIPTION DATE REV
(2)#10 AWG USE-2/PV WIRE-Black (2)#10 AWG THWN-2-Black— / SolarEdge SE6000A-US Inverter 97.5%CEC
EGC#6 BARE CU IN FREE AIR I,/ Efficiency @ 240 Vac 6000 Wac continuous Li L2 N City Correction I.4.16 A
SUNEDISON EGC#8 THWN-2 =
3/4"EMT Maximum Output Current 25 Amp.Ground fault
SE F270 KzD-3y protection provided per NEC article 690.35
III
1 Y' DC AC 0 BI-DIRECTIONAL THIS DRAWING IS PROPERTY OF
vo o UTILITY METER AMERICAN SOLAR DIRECT INC.THIS
Ie 7 1-PHASE,240V DRAWING IS CONFIDENTIAL AND IS
ONLY TO BE USED IN CONJUCTION
o 0 0 10 11 I I, 11 4 �� WITH WORK DESIGNATED BY
1 AMERICAN SOLAR DIRECT INC.NO
+ + + I I (N)MAIN SERVICE PANEL, PART OF THIS DOCUMENT IS TO BE
L-1+ --r�r — -r�r —r�r+ r r+ AC DISCONNECT: DISCLOSED TO OTHERS WITHOUT
L_ — I I 1-PH,3-W, THE PRIOR WRITTEN PERMISSION
r r r r r r r r r r 240V,60AMP NON-FUSED OF AMERICAN SOLAR DIRECT INC.
u u u I I l 200A RATED,240V,2P
LSI Pil El NEMA 3R,UL LISTED CONTRACTOR INFORMATION
0 0 0 = _ C-10MA LICENCE HOLDER
+ + + + + c o (N)MAIN BREAKER TO MAURICIO RODRIGUEZ
-- I HOUSE 240V,200\2P MRODRIGUEZ@AMERICANSOtARDIRECT.COM
U o o L1 n 6,-:-A
SUNEDISON I _ (626) 435-9221
SE F270 KzD-3y I L2 —�o I o
gnature-Magid°Rodriguez
LCI ENSE C10/C46/C39#941069
ri-i-i
1r\\,...7.—�r —J JUNCTION BOX
G
dr
600 V,NEMA3NULLISTED G _o 0 0 10 11
_ _ + + _I GEC I PROJECT NAME
L I+ — i�i — i�1 1�1 — 1 i
.. u u ■• GROUND W
- 0 0 0 = = J
r -- -- - --
-- , E
-- (3)#8 AWG THWN-2 'g`°"" � CUPERTINO
(1)#8 AWG THWN-2GND ` > d' U
U 3/4"EMT . Building Department IY O zN — N
SolarEdge Power Optimizer P300 Rated .+` . v W
in ; c O
DC Input Power-300 watts L1�16 N..ct w O O
Maximum Input Voltage-48 Vdc cfl< 0 O < O y,
MPPTRange-8 to 48 Vdc MO ZO U ^ � O
Maximum Input Current-10 Adc REVIEWED FOR CODE COMPLIANCE o U > O o Cr)
Maximum Output Current-15 Adc String ..,r CD (n W Z O
Limitations-8 to 25 Optimizers, Reviewed By: T /a0d= W J O
5250 watts STC per string maximum 0 J a a rY W - Z
INTERCONNECTION Z < LLI 0 J a.
120%RULE-NEC 690.64,705.12(D)(2) a 0 D _ - Q
UTILITY FEED+SOLAR BACKFEED W cc 0 a
200.0 A+31.25 A=231.25A — 00 W
BUSS RATING x 120% 0
200.0 A x 120%=240A
I
SHEET NAME
SERVICE INFO ELECTRICAL LINE
UTILITY COMPANY: PG&E DIAGRAM
MAIN SERVICE VOLTAGE: 240V SHEET SIZE
MAIN PANEL BRAND: ANSI B
MAIN SERVICE PANEL: 200A
MAIN CIRCUIT BREAKER RATING: 200A 11" )X 17"
1 ELECTRICAL LINE DIAGRAM MAIN SERVICE LOCATION: EAST
SERVICE FEED SOURCE: OVERHEAD SHEET NUMBER
PV-4 SCALE: NTS J PV-4
SOLAR MODULE SPECIFICATIONS DC CONDUCTOR AMPACITY CALCULATIONS: AC CONDUCTOR AMPACITY CALCULATIONS: PROJECT DEVELOPER
MANUFACTURER SUNEDISON ARRAY TO JUNCTION BOX: No.OF INVERTER 1
American
MODEL# SE F270 KZD-3Y -EXPECTED WIRE TEMP(In Celsius) 39 EXPECTED WIRE TEMP(In Celsius) 39° Solar Direct
PMAX 270.00 W TEMP.CORRECTION PER TABLE 310.15(B)(2)(a) p 91 TEMP.CORRECTION PER TABLE 310.15(B)(2)(a) 0.91 11766 WILSHIRE BLVD.,
VMP 30.2 V NO.OF CURRENT CARRYING CONDUCTORS 3 SUITE 500
NO.OF CURRENT CARRYING CONDUCTORS 4LOS ANGELES,CA 90025
IMP 8.94 A CONDUIT FILL CORRECTION PER NEC 310.15(B)(3)(a) 0.80 CONDUIT FILL CORRECTION PER NEC 310.15(B)(3)(a) 1 PH:(855)765-2755
VOC 37.8 V CIRCUIT CONDUCTOR SIZE 8 AWG FX:(424)214-6750
CIRCUIT CONDUCTOR SIZE 10 AWG
ISC 9.30 A -
CIRCUIT CONDUCTOR AMPACITY 40A CIRCUIT CONDUCTOR AMPACITY 55A WEB:httpl/www.americansolardirect.com
PTC 246.6W REVISIONS
MODULE DIMENSION 65.3"L x 39"W x 1.18"D(In Inch) - DESCRIPTION DATE REV
MAXIMUM CONTINUOUS INPUT CURRENT OF OPTIMIZER(ISC) 1OA City Correction 1.4.16 A
REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B)
25A
CIRCUIT CONDUCTOR AMPACITY MAX INVERTER OUTPUT CURRENT
INVERTER#1 SPECIFICATIONS 1.25 X 1.25 X OPTIMIZER(ISC) 15.625A AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.15(6)(16)
THIS DRAWING IS PROPERTY OF
AMERICAN SOLAR DIRECT INC.THIS
MANUFACTURER SOLAREDGE SOLAR DRAWING IS CONFIDENTIAL AND IS
31.25A ONLY TO BE USED IN CONJUCTION
• 1.25 X MAX INVERTER OUTPUT CURRENT WITH WORK DESIGNATED BY
MODEL# SE6000A-US
DC CONDUCTOR AMPACITY CALCULATIONS: AMERICAN SOLAR DIRECT INC.NO
______ _ PART OF THIS DOCUMENT IS TO BE
NOMINAL AC POWER 6.0KW DISCLOSED TO OTHERS WITHOUT
• FROM JUNCTION BOX TO INVERTER: THE PRIOR WRITTEN PERMISSION
NOMINAL OUTPUT VOLTAGE 240 VAC OF AMERICAN SOLAR DIRECT INC.
AMBIENT TEMPERATURE ADJUSTMENT FOR EXPOSED CONDUIT POWER OPTIMIZER(OPTIMIZER P300-2NM4ARS) CONTRACTOR INFORMATION
NOMINAL OUTPUT CURRENT 25 A PER NEC 310.15(B)(2)(c) +22° MAXIMUM INPUT POWER 300W C-10 LICENCE HOLDER
EXPECTED WIRE TEMP(In Celsius) 39°+22°=61°
MINIMUM INPUT VOLTAGE 8 VDC MAURICIO RODRIGUEZ
MRODRIGUEZ5AMERICANSOLARDIRECT.COM
TEMP.CORRECTION PER TABLE 310.15(B)(2)(a) 0.65 MAXIMUM INPUT VOLTAGE 48 VDC (626) 435-9221
DC PHOTOVOLTAIC POWER SOURCE TO BE INSTALLED MAXIMUM MODULE ISC 10 ADC
AT INVERTER#1 PER NEC 690.53&690.54
NO. CURRENT CARRYING CONDUCTORS 4Signature-Mauricio Rodriguez
CONDUIT FILL CORRECTION PER NEC 310.15(B)(3)(a) 0.80 MAXIMUM OUTPUT CURRENT 15 ADC LICENSE C10/C46/C39#941069
OPERATING CURRENT S1 &S2 8.49 A
- CIRCUIT CONDUCTOR SIZE 10 AWG
OPERATING VOLTAGE 350 V
CIRCUIT CONDUCTOR AMPACITY 40A 9
SHORT CIRCUIT CURRENT 10 A
MAXIMUM SYSTEM VOLTAGE 500 V t f U r" I�TIN
I j l F O PROJECT NAME
MAXIMUM CONTINUOUS INPUT CURRENT OF OPTIMIZER(ISC) 10A "' Building Department
OPTIMIZER(ISC)X No.OF STRING �`" `W
�,
CIRCUIT CONDUCTOR AMPACITY 15.625A / T-```` JAN 07
2016 J W
W > 0) OV
1.25 X 1.25 X OPTIMIZER(ISC) �
REVIEWED FOR CODE COMPLIANCE z o c�o - N
w t] Ln N-- co CPI
Reviewed By: T ' N 0) CO E a_
o= z0O � � �
8U W O 8o � M
o°6cwz � o . .
O
Q_J OCL L z
C Z W Z oz
z Qa.. OJw
E. U D 2 Q
oo U a
co
ELECTRICAL NOTES Lu coW
1.)ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL,AND LABELED FOR ITS APPLICATION. U
2.)ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90 DEGREE C WET ENVIRONMENT.
3.)WIRING,CONDUIT,AND RACEWAYS MOUNTED ON ROOFTOPS SHALL BE ROUTED DIRECTLY TO,AND LOCATED AS CLOSE AS
POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY. SHEET NAME
4.)WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26. WIRING
5.) DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, CALCULATIONS
SUPPORTS, FITTINGS AND ACESSORIES TO FULFILL APPLICABLE CODES AND STANDARDS.
6.)WHERE SIZES OF JUNCTION BOXES, RACEWAYS,AND CONDUITS ARE NOT SPECIFIED,THE CONTRACTOR SHALL SIZE THEM SHEET SIZE I
ACCORDINGLY. ANSI B
7.)ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE.
8.)MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE SUPPORT RAIL, PER THE 11" X 17" _
GROUNDING CLIP MANUFACTURER'S INSTRUCTION. -
9.) MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER EGC VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG. SHEET NUMBER
10.)THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE PV-5
TO BE INSTALLED ON THE FACE OF THE PROJECT DEVELOPER
DISCONNECTION MEANS; TO BE INSTALLED
AT ALL AC AND DC DISCONNECTS ® MARKING SHOULD BE PLACED ON ALL INTERIOR
AND EXTERIOR PV CONDUIT, RACEWAYS, C8> SERVICE METER PANEL PER
C CI American
RESPECTIVELY PER NEC 2008 90.14(C)(2) ENCLOSURES,AND CABLE ASSEMBLIES, EVERY NEC 2008 705.10
Solar Direct
10 FEET,AT TURNS AND ABOVE AND/OR BELOW 11766 WILSHIRE BLVD.,
SOLAR AC DISCONNECT PENETRATIONS AND ALL PV COMBINER AND CAUTION: SUITE 500
JUNCTION BOXES. LOS ANGELES,CA 90025
POWER TO THIS BUILDING IS ALSO SUPPLIED PH:(855)765-2755
-- FROM THE FOLLOWING SOURCES WITH FX:(424)214-6750
SOLAR DC DISCONNECT CAUTION: SOLAR CIRCUIT DISCONNECTS LOCATED AS SHOWN WEB:http://www.amedwnsolardirect.com
REVISIONS
SOLAR ARRAY 1 L DESCRIPTION DATE REV
nDISCONNECTING MEANS MAY BE ENERGIZED IN \ City Correction I.4.IC
THE OPEN POSITION;TO BE INSTALLED AT 0 TO BE LOCATED AT MAIN SERVICE
DISCONNECTING MEANS PANEL: AC DISCONNECT
PER NEC 2008 690.17 DC DISCONNECT THIS DRAWING IS PROPERTY OF
WARNING WARNING: MULTIPLE POWER SOURCES INVERTER AMERICAN SOL DIRECT
INC.
DRAWING IS
ELECTRIC SHOCK HAZARD. UTILITY POWER @ 240/120VAC, 200AMPS ^ ONLY TO BE USED IN CONDUCTION
WITH WORK DESIGNATED BY
DO NOT TOUCH TERMINALS. PV POWER @ 240VAC, 31.25AMPS AMERICAN SOLAR DIRECT INC.NO
PART OF THIS DOCUMENT IS TO BE
TERMINALS ON BOTH THE LINE DISCLOSEDTHIS OTHERS VV1THOUT
AND LOAD SIDE MAY BE WARNING: /\/ OFEA,MRERICANSOLANRDIRECTIINc
ENERGIZED IN THE OPEN PV DISCONNECT
( t CONTRACTOR INFORMATION
POSITION. BACK FED BREAKER C-10 LICENCE HOLDER
DO NOT RELOCATE MAURICIO RODRIGUEZ
0
PHOTOVOLTAIC POWER SOURCE SHALL BE n MRODRIGUEZQAMERICANSO ARDIRECT.COM
LABELED WITH THE FOLLOWING WARNING AT EACH I I
JUNCTION BOX, COMBINER BOX, DISCONNECT,AND (626) 435-9221
DEVICE WHERE ENERGIZED, UNGROUNDED METER AND Signature-Mancoio Rodriguez
LICENSE C10/C46/C39#941069
CIRCUITS MAY BE EXPOSED DURING SERVICE PER MAIN SERVICE
NEC690.35(F)
SYSTEM BREAKDOWN: 9
WARNING MAIN PANEL AMPERAGE 200A
ELECTRIC SHOCK HAZARD. MAIN BREAKER AMPERAGE 200A
THE DC CONDUCTORS OF THIS PV BREAKER AMPERAGE 40A PROJECT NAME
MAXIMUM AMPS OPERATING 31.25A
PHOTOVOLTAIC SYSTEM ARE TOTAL PV AMPERAGE 31.25A w
UNGROUNDED AND MAY BE w
ENERGIZED NOMINAL OPERATING VOLTAGE 240V
OPTIMIZER OPERATING VOLTAGE 350V
NOMINAL OUTPUT CURRENT C P ERT I N O w > p OU
:&t.:4-011; z I O N _ Lf)
C 4> DIRECT-CURRENT PHOTOVOLTAIC " Building Department w a r` N
POWER SOURCE TO BE INSTALLED AT „ . f l ti J W p 0)
0)
INVERTER PER NEC 690.53&690.54 ',,,,,--,- :.., ` 2016 co
< U Q °) o 4737)
INVERTER#1 JAN N O w O U - M
DC DISCONNECT RATINGS: REVIEWED FOR CODE COMPLIANC:o°o Enw _Z _o
OPERATING CURRENT 16.97 A U J z w z ° Z
Reviewed By: Tow/at/J.1'0A+ z w Z o Z
OPERATING VOLTAGE 350 V Z < 0_JQ
0HORT CIRCUIT CURRENT 10 A MARKING CONTENT AND FORMAT
• RED BACKGROUND w co 0oo a 2
MAXIMUM SYSTEM VOLTAGE 500 V • WHITE LETTERING = °O w
• MINIMUM 3/8"LETTER HEIGHT 0
•UNGROUNDED PV SYSTAEM ALL CAPITAL LETTERS
• ARIAL OR SIMILAR FONT, NON-BOLD
• REFLECTIVE WEATHER RESISTANT SHEET NAME 1
INVERTER OUTPUT CONNECTION TO BE MATERIAL SUITABLE FOR THE PLACARDS
INSTALLED AT MAIN SERVICE PANEL ENVIRONMENT(DURABLE ADHESIVE
PER NEC 2008 690.64(B)(7) MATERIALS MUST MEET THIS ,
REQUIREMENT) SHEET SIZE
• TO BE ATTACHED USING POP-RIVETS ANSI B
WARNING
INVERTER OUTPUT CONNECTION 11" X 1711
DO NOT RELOCATE THIS
OVERCURRENT DEVICE SHEET NUMBER
PV-6
I PROJECT DEVELOPER
cfAmerican
Solar Direct
S I LVA N T I S" F-SERIES : 11766 WILSHIRE SUITE SOOBLVD.,
IIIIIIIIIIIIIIII.7MMI"lillIllillIlliIllIlIllPVSunEdison•SunEdisonxPH:(855)765-2755
FX:(424)214-6750
60-Cell High Wattage Modules SILVANTIS F-SERIES: 255W TO 275 W .: ;. CUPERTINO WEB:hap,Iwww.an fcensolerdrecLcom
yy pt,,] �{ ❑�
PHYSICAL PARAMETERS F-S SI MO100tEIBRNli' �<T� pI lR
ticl'I REVISIONS
"_mEdlson is a recognized authority on silicon technology,'
s DESCRIPTION DATE REV
rnanufacturinprocesses developed through more than 5+r r Module D4nensions 11.858 nun x 990 mm x 50 mm
p v �� ' Module Weight 19-3 kg City Correction 1.4.16 Q
''xperience. With our vertically-integrated business model.Suri Celt-Type_ Continuous Cz ICCzl monocrystanme a1 -
divers best-in-class solar modules by continuously leveragin. - • Number Bo �
FrameMateriel Black Anodiced Aluminum REVIEWED FOR CO�1 CGIDIN<DLIANCE
awtechnologyandmanufacturingtechniquesthat p,:ix+rnrze Tempered ARC Glass Thickness 3.2 mm .,1t
"" ' '' • • - - - THIS DRAWING IS PROPERTY OF
efficiency minimize cost and extend product lifetime.'!' I I TEMPERATURE COEFFICIENTS AND PARAMETERS' : t AMERICAN SOLAR DIRECT INC.THIS
Citic module factories are ISO 9001 and 1501403 DRAWING IS CONFIDENTIAL AND IS
-y;11[l ( ��r air
'-�{� • Nominal Operating Cell Temperature INOCTI 45C i 2C � `�'a PLACES � ONLY TO BE USED IN CONDUCTION
ertified.Our products undergo rir^rry'i ,In a r-' I Temperature Coefficient of Pmax -0.45'WC `»,k. -- WITH WORK DESIGNATED BY
--- - AMERICAN SOLAR DIRECT INC.NO
sure the highest possible l�Uaii? • • Temperature Coefficient of Voc -044 we // PART OF THIS DOCUMENT IS TO BE
Temperature Coefficient of Ise I .0:06%X / DISCLOSED TO OTHERS WITHOUT
C THE PRIOR VVRITTEN PERMISSION
OF
Limiting Reverse Current 9.20A Ancon+see rrr-- CONTRA[OR INFORMATION
ature
to
..e s • -
Operating
- - Yl7piaEtAen.
ERICAN SOLAR DIRECT INC.
Maxum System Voltage • 1000 V IUL 85 IECI �'"
- - - .- $- * a Maximum Series Fuse Rating 15 A _s - ! G10 LICENCE HOLDER
Pmax Production Tolerance I 0 W to+5 W t� MAURICIO RODRIGUEZ
r • Junction Box Rating 1 IP67 _ _
lEC 61730 Appbcatton I Oa85-A �1 I MRODRIGUEZ@AMERICANSOLARDIRECT.COM
• Module Flre Performance I Type 2
,` I Module Fire Resistance Rating626 435-9221
Class-[ T-
* . Packaging 5pecdications 20 modules per palletSignature-Meurido Rodriguez
•;,,e,
• v -•,• • .4 520 modules per40'high-cube c nta #9
ner �'� L �.L LICENSE C10/C46/C3941069
Wind and Snow Front Load Up to 5.400 Pe ____a eeraa•
Wind Back Load l 2.400 Pa _
carnets
Reduction of STC efficiency from 1000 W/ntr <4% Module Dimensions
to 200 Win?(Relative) A-990139.01 9-1.658165.31 C-5012.01 D-3011 181 9
STC ELECTRICAL CHARACTERISTICS' Mounting Hole Spacing
SILVANTIS ADVANTAGE E-950[37,4] F-994139.11
F255!F260 F266 F270f F275 F255 F260 I F265 F270 •F275
I Cable Length
11 • 16.8%module efficiency with positive power tolerance (e.g.F2xxCsD3y1' CzD CzD CzD CzD I CzD KzD KzD KzD IC=D KzD •L• 1.000I'61.21
PROJECT NAME
• [ Power Pmax(W) 255 260 2fi5 270 • 275 55 201 265 270 275 Junction Box Dimension*
• Tariff free:not subject to U.S.countervailingor antidumping tariffs Vt>p Ctruxt Rated Voltage 37.5 1015 s60.0 k 2551399 eor x more23x T01
m W
PID-free:compatible with transformerless and multi-MPPT inverters
37.6 37 7 37 8 37,9 37 5 37 6 37 7 37.8 `37:9
p g 'L-Other options available upon request,please contact your local LU
• sales representative for information J
Higher return on investment with more watts-per-module Short-Circuit Current 9 25 9,30 9.35 9.40 . 945 ' 9 15 9.20 9.25 9.30 935 • WE
Isc(Al
• Utilitygrade manufacturing:ISO 14001,ISO 9001 and 100%EL inspection ocienc (Poi). 15.5 I
15B 1 364 16 16.8 15.5 15.8 16.1 16.4_16.8 IV CURVES AT MULTIPLE IRRADIANCES 125 C) W - 0 •
Maximum
30 3 1 29.9 30.0 30.1 30.2 30.3 lb --_ z (X O cV = CV
Voltage Vmmpp M 1 - w 0 Lf) N-
QUALITY & SAFETY ROBUST& AESTHETIC DESIGN Maximum Power Point' 853 8.67 8.81 8.94 908 ' 853 8.67 9.80 8.94 8:08 a CV__1 0) c0 E 0)
_ppW i._.__. -rio4wM N. UQ 0 O
Current h71
• Industry leading PID test conditions: • Black anodized corrosion resistant aluminum framemove. Q
a 96 hours.85 C.85%relative humidity.-1kV a White back sheet:SE-F2xxCzD-3y NOCT ELECTRICAL CHARACTERISTICS, 3 . --- _ = Z 0 (�
a Black back sheet:SE-F2kxKzD3y Model M F255 F260 F265 F270 F275 F255 F260 F265 F270 F275 t CV U co
• IEC certified by TOY SUD: `s , _ _ -A00 W. Ott - Z O
(e. F?xxCzD_3yt` CzD Cz0 CzD CzD CzD KzD Kz0 KzD KzD KzD 0.
a 61730 to ensure electncal safety • Low glare anti-reflective coated[ARC)tempered & - - -- -' - �„ i C/)W - O
Rated Maximum 185 7 189A 193.0 196,6``200,31 184.1 187 i 191 3 19,19 198.5J
Los,,-,_., a 61215 long-term operation in a variety of glass Power Pmax(WI I ! I --____ - __ Q- w H -
Climates including snow loading up to 5400 Pa • Reliabilitytested beyond international standards Open-Circuit Voltage 34 7 ' 34 8 34 8 34 9 r 34.9 346 317 34 7 34 8 34 8 '" \ 0 w
and hall testing Voc M ,-. e CD Q w z -- Z
a 61701 Level 1 salt mist corrosion resistant for SUNEDISON WARRANTY Shri
ort-Circuit Current 7.52 7.55 1758 7.G 764 1 7.32 7.35 7.38 7.11 7.44 n r 1, 2r n 30 is w Z < a- 0 J
IscVole••Mit D _ - Q
marine regions • 25-year limited warranty for materials and -_. - Q
- Maximum Power Point' 27.4 � 27.5 27.5 • 27.6 27.6 27 4 � 27.4 27.5 27 5 27.8 z' OO (� �
a 62716 ammonia testing for agricultural workmanship for residential applications Voltage Vmpp(V) IV CURVES AT MULTIPLE TEMPERATURES 11000 Wlmr) w CO
environments Maximum Power Point 6.78 6.90 7 02 7 14 7 76 6 73 6 115 6 97 7 09 7.21 - CO W
• 25 year linear power warranty at STC_ Current Impp(A) » _
• Manufactured to AOL 0.4 Level II quality a Year 1:<3.5%of rated power --
and tested up to 3x beyond IEC standards a After Year 1:5 0.7%rated power degradation Listed specifications are subject to change without prior notice. r U
per year 'Thmperedore coefhcrons may vary b',, -.10% - -
• CSA listed to UL 1703 for 1.000 V systems 'All elecaical day at standard taNcon ddons r'b70. 1000 W,nrZ AM 1.5,25 C electrical cheracterst5cs may
in the US and Canada „1... raryby^596 and power measurement tolerance by`3% a
Pmax i or iMioon Tolerance.fPl1tory�shasrired mot/We performance is warranted ra meet or exceed the -a r SHEET NAME
• MCS certified by BABT for the UK 7 -•rr
r^ SunEdison'a Linear Wor.enry Palow Nang byo wto+5w _nc EQUIPMENT
'y indicates connector type -34=Bizhnk 5405,-38-A'nphennl Helms li4
0 C� _r I ''' z rr:dreates manufacturing location:M-Malayan.X-Mexico SPECIFICATION
i- NDCTe ectncal cotraClar ctiCS measured under normal operating cot draons of cells:870 Wine 20 C -
I 1 Er C�US V I '- AM S wind!revs • -- -- -.
• • r u ,• a c r •w SHEET SIZE
1:
0 •c For more information about SunEdison's Silvantis modules,please visit
I r trvwwsunedison coin ANSI B
1:1 ,.:Y.;.,..,-..4:. +i�..1••a•. °" ' . . . ' . . 520.4 SuriEdisor. :s S'ingartore Pte_Ltd.;A SunElilion Camparry.All rights reser ed.StieEdeen and the Suetdiaen logo
stfnr can li r 1 2 3 • • 5 • • 10 11 1: 1] W 1r a Ir 1a rs as:1 a A za a ore 0724elsrod Vali,: 4--or uedemieks of Suntdloon Products Singsaore Pia Ltd ondbr Its.affiliates in the united States and rr n
r
sunedison.com t"'aei""'°"�•' [bridle other Lel/ethos All other iiedemarkt mentioned to this documera ere the property of Brett r pootive owners LIM-galea t F_Fn0_Vega 45_05 50mm_v11 12 2014 1 1 X 1 7
SHEET NUMBER
PV-7
PROJECT DEVELOPER
fr
1__.1 American
r--- - CUPERTINO-, Solar Direct'
11766 WILSHIRE BLVD.,
v.) solar - Single Phase Inverter for Nor h II department GELES,C
. , • LOS ANGELES,SUITE 0 90025
SE3000A-US -US/SE5000A-U
�;...,4.!i;f, s/
PH:(855)765-2755
solar - • • o� " 171 FX:(424)214-6750
SE7600A-US/SE10000A-US/SE11400A-US;° ., , JAN 2016
W II I � COMPLIANCE WEB:httP//www.amarica rola direct.com
SE3000A-US SE3800A-US SESOOOA-US SE6000A-US SE76og,EurviiF p{�QO¢ IIREVISIONS
OUTPUT CC((�C VV tt �T��tom-tri- "� •`^(
SolarEdge Single Phase Inverters CC Nominal AC Power Output 3000 3800 5000 6000 7600 9 By114 /c ykiA•vt" CDESCity orrrecON tlon DATE REV
208V
For North America W 5400@2DSV 10800240V a.ls
Max AC Power Output 3300 4150 5450 @240V 6000 8350 10995050�L240V 12000 VA
AC Output Voltage Min:Nom:Max m
SE3000A-US/ SE3800A-US/ SE5000A-US/ SE6000A-US/ 183-208-229 Vac
AC Output Voltage Min:Nom:Max."' THIS DRAWING IS PROPERTY OF
SE7600A US/ SE10000A-US/ SE11400A US 211-240-264 Vac DRAWING IS CONFIDENTIAL AND IS
AC Frequency Min: •I •/ ./ ,/ INom.-Max."' 59.3-60-60.5 lJith HI country sesI ,/ AMERICAN SOLAR DIRECT INC.THIS
ting 57-60-60.5) Hz ONLY TO BE USED IN CONDUCTION
5: III II 24 @ 208V I 32 I 48 @ 208V WITH WORK DESIGNATED BY
-- -_ Max.Continuous Output Current 12.5 16 25 47.5 A AMERICAN SOLAR DIRECT INC.NO
21 240V 42 240V PART OF THIS DOCUMENT IS TO BE
,. .. GFDI Threshold 1 A DISCLOSED TO OTHERS WITHOUT
THE PRIOR WRITTEN PERMISSION
'- Utility Monitoring,(standing Protection,Country Configurable Thresholds Yes Ya OF AMERICAN SOLAR DIRECT INC.
INPUT CONTRACTOR INFORMATION
�pve rte,• Maximum DC Power(STC) 4050 I 5100 I 6750 8100 I 10250 I 13500 I 15350 W
Transformer-less,Ungrounded Yes C-10 LICENCE HOLDER
•i2CJ, adasi .. Max Input Voltage 500 Vdc MAURICIO RODRIGUEZ
66111\a•7
Nom.DC Input Voltage 325 @ 208V/350 6 240V Vdc MRODRIGUEZ@AMERICANSOLARDIRECT.COM
•,e �.• ( 116.5@208V I I 33@208V I (626) 435-9221
UeA Max Input CurrenN" 9.5 13 18 23 34.5 Adc
15.5e 240V 30.5e 240V
Max Input Short Orcuit Current 45 Adc Signature-Mauricio Rodriguez
9 ` Reverse-Polarity Protection Yes LICENSE C10/C46/C39#941069
Ground-Fault Isolation Detection 600koSensitivill
Maximum Inverter Efficiency 97.7 98.2 98.3 98.3 98 98 98 %
CEC Weighted Efficiency 97.5 98 97.5 @ 208V 97 5 97.5 97 @ 208V 975 % C)(11/11
' 98 dal 240V 97.5 @ 240V
Nighttime Power Consumption <2.5 <4 W
ADDITIONAL FEATURES
Supported Communication Interfaces R5485,RS232,Ethernet,ZigBee(optional) PROJECT NAME
.7.'"" Revenue Grade Data,ANSI C12.1 Optionalm
0 IP . Rapid Shutdown-NEC 2014 690.12 Functionality enabled when SolarEdge rapid shutdown kit is installed"' w
W. illiTm'n .
STANDARD COMPLIANCE J
Safety UL1741,UL1699B,UL1998,CSA 22.2 W E
Grid Connection Standards IEEE1547 > O O
ra► Emissions FCC part15 class B W r- O _ u
t INSTALLATION SPECIFICATIONS w Q C N- .0 CV
AC output conduit size/AWG range 3/4"minimum/16-6 AWG 3/4"minimum/8-3 AWG N J COO
0 ' . . DC input conduit sae #of strip a) E Q7
p / strings/ 3/4"minimum/1-2 strings/ III O
3/4"minimum/1-2 strings/16-6 AWG Q U O Q O
AWG range 14-6 AWG CO 0,
Dimensions with Safety Switch 30.5 x 12.5 x 10.5/ in/ O= z Q U ( 1 C0
30.5x12.5x7.2/775x315x184 NU W CO v co
(HxWx0) 775x315x260 mm Q O _
Weight with Safety Switch 51.2/23.2 I 54.7/24.7 88.4/40.1 lb/k¢ O CD 0 -w Z O •
0 a Natural a w J H 1--
• -, . , , convection 0-I W'0 CY W -- Z
Cooling Natural Convection and internal Fans(user replaceable) 0 z W Z 0 Z
fan(user Z Q IZ O J d
The best choice for SolarEdge enabled systems replaceable) a U = Q
Noise <25 <50 dBA CO U W Q
Integrated arc fault protection(Type 1)for NEC 2011 690.11 compliance Min.-Max.Operating Temperature
-13 to+140/-25 to+60(-40 to+60 version available"') •F/'C W
Superior efficiency(98%) Range - 00 W
Protection Rating NEMA 3R U
• Small,lightweight and easy to install on provided bracket "For other regional settings please contact SoarEELe support.
'`'A higher currert source may be used;the inverter will limit Its input current to the values stated.
• Built-in module-level monitoring 's'Revenue grade Inverter P/N:SEnaxA-U5000NNR2(for 7600N inverter:SE7600A-U5002NNR2).
"'Rapid shutdown kit P/N:5E1000-R5D-51.
Internet connection through Ethernet or Wireless "'-40 version P/N:SEAxroA-U5000NNU4(for 7600W inverter.5E7600A-U5002NNU4). -
• Outdoor and indoor installation " SHEET NAME
Fixed voltage inverter,DC/AC conversion only EQUIPMENT
• Pre-assembled Safety Switch for faster installation SPECIFICATION,
- Optional-revenue grade data,ANSI C12.1 ODI
[-MI
Ro ll S SHEET SIZE
USA-GERMANY-ITALY-FRANCE-JAPAN-CHINA-AUSTRALIA-THE NETHERLANDS-ISRAEL www.solaredge.us ANSI B
11" X17"
SHEET NUMBER
PV-8
PEDRepTaIrtrent
" :4 BuildingCUPROJECT DEVELOPER
• H.: IAN 0 1 2016
ci American
•
Solar Direct
FOR CODE COMPLIANCE 11766 WILSHIRE BLVD.,
SUITE 500
Er LOS ANGELES,CA 90025
PH:(855)765-2755
solar iharite LLI solar -. . • z SolarEdge Power Optigw. ED FX:(424)214-6750
NIModule Add-On for North America YVES:httpAwm.amencansolardirect.com '
reviewed By: TP(.4/01334.044/ REVISIONS
P300 / P350 / P400 / P405
DESCRIPTION DATE REV
SolarEdge Power OptimizerA'
lir 2
,.. ...... P300 P350 P400 P405
City Correction
(for 60-cell modules) (for 72-cell modules) (for 96-cell modules) (fat thin fim modules)
INPUT
Module Add-On For North America ._,.. I-- Rated Input DC PowerN 300 350 400 405 W
THIS DRAWING IS PROPERTY OF
......_- . .,
AMERICAN SOLAR DIRECT INC.THIS
i CL Absolute Maximum Input Voltage 48 60 80 125 Vdc DRAWING IS CONFIDENTIAL AND IS
P300 / P350 / P400 I P405 i ...
, (Voc at lowest temperature) ONLY TO BE USED IN CONJUCTION
WITH VVORK DESIGNATED BY
/ C) MPPT Operating Range 8-48 8-60 8-80 12.5-105 Vdc AMERICAN SOLAR DIRECT INC.NO
/
PART OF THIS DOCUMENT IS TO BE'
. Maximum Short Circuit Current(Isc) 10 Mc
DISCLOSED TO OTHERS WITHOUT
' .
,- Maximum DC Input Current CC 12.5 Adc THE PRIOR WRITTEN PERMISSION
OF AMERICAN SOLAR DIRECT INC.
„ Maximum Efficiency 99.5 %
' -- = LII Weighted Efficiency 98.8 % CONTRACTOR INFORMATION
-
0
f Overvoltage Category II C-1LICENCE HOLDER
1... ' MAURICIO RODRIGUEZ
OUTPUT DURING OPERATION(POWER OPTIMIZER CONNECTED TO OPERATING INVERTER)
MRODRIGUEZ@AMERICANSOLARDIRECT.COM
Maximum Output Current 15 Adc
. Maximum Output Voltage 60 I 85 Vdc (626) 435-9221
P OUTPUT DURING STANDBY(POWER OPTIMIZER DISCONNECTED FROM INVERTER OR INVERTER OFF) Signature-Maurido Rodriguez
I , Safety Output Voltage per Power Optimizer 1 Vdc LICENSE C10/C46/C39#941069
. O
-, STANDARD COMPLIANCE fT/1 -1
.. • CL.• .
. .?Qv,.,.. ,
4,
EMC FCC Part15 Class B.IEC61000-6-2,IEC61000-6-3
.
Safety IEC62109-1(class II safety),UL1741
-
.
/ :.., vi 3 fliffit .7 i , s RoHS Yes
s '4„ 11 I ,
/ .. i 1.4 °‘ _I . INSTALLATION SPECIFICATIONS PROJECT NAME
,, ifo, - • , A...A.-P Maximum Allowed System Voltage 1000 Vdc
/' i ' 7 /
,, ,. - Dimensions(W x Lx H) 141 x212 x 40.5/5.55x 834 x1.59 mm/in LLJ
"
.., .,. / Weight(including cables) 950/2.1 gr/lb W
_1
, / f _ Input Connector MC4/Amphenol/Tyco I MC4 _
, , C/5 L.L1 E
Output Wire Type/Connector Double Insulated;Amphenol > v. cp o
.
.
,,''' .1]
,
; Output Wire Length 05/3.0 I 1.2/3.9 m/ft 0
.
• CNI
'' Operating Temperature Range -40-+85/-40-+185 *C tF LLJ 0 LO N- CO
0
C•I_I CD E
.,...- ., Protection Rating IP65/NEMA4 1`.-W L-ll 0 6 0)
'
Relative Humidity 0-100 % CD< 0 0 < 00
CY)
CD= Z
or Roted ETC power of the module.Module of up to 4.5%power tolerancelow
aled. 0
/
z z.1.- o cis
• PV SYSTEM DESIGN USING 9 c75 LU
SINGLE PHASE THREE PHASE 208V THREE PHASE 480V 0_ 11_1_1 H . . N— zr A SOLAREDGE INVERTER121 0—j 12 0 CY 1-1-I -c
Minimum String Length
8 10 18 Z
(Power Optimizers)
0 DI — <
, §PV power optimization at the module-level Maximum String Length(Power Optimizers) 25 25 50 Z CO C.) a-
LIJ ,,,C0
... Up to 25%more energy Maximum Power per String 5250 6000 12750 W I
.., Superior efficiency(99,5%) Parallel Strings of Different Lengths
Yes 0
or Orientations
Mitigates all types at module mismatch losses,from manufacturing tolerance to partial shading
oi it's not allowed to mix P405 with F340/P350/P4,30/P600/P700 In we strirg.
. Flexible system design for maximum space uti lint on SHEET NAME
..• Fast installation with a single bolt EQUIPMENT
.
.• Next generation maintenance with module-level monitoring SPECIFICATION
.. Module-level voltage shutdown for installer and firefighter safety
SHEET SIZE
ANSI B
USA - GERMANY - ITALY - FRANCE - JAPAN - CHINA - ISRAEL - AUSTRALIA www.soleredge.us 11" X 17"
SHEET NUMBER
PV-9