14120008S,'
CITY OF CUPERTINO BUILDING PERMIT
BUILDING ADDRESS: 20849 GREENLEAF DR
CONTRACTOR: SIMON ZHANG
PERMIT NO: 14120008
OWNER'S NAME: HUANG XIANGDONG AND ZHANG XIAOYI
18488 PROSPECT RD
DATE ISSUED: 05/28/2015
OWNER'S PHONE: 4083327690
SARATOGA, CA 95070
PHONE NO: (408) 887 -0591
fu / LICENSED CONTRACTOR'S DECLARATION
JOB DESCRIPTION: RESIDENTIAL COMMERCIAL ❑
REMOVE (E) ACCESSORY SHED AND CONSTRUCT (N) 1
License Class_ Li #/1,.
STORY 2ND UNIT WITH 1,261 S.F (2 BEDROOMS /1 BATH)
Contractor.
I hereby affirm that I am licensed under to provisions of Chapter 9
(commencing with Section 7000) of Division 3 of the Business & Professions
Code and that my license is in full force and effect.
I hereby affirm under penalty of perjury one of the following two declarations:
I have and will maintain a certificate of consent to self - insure for Worker's
Compensation, as provided for by Section 3700 of the Labor Code, for the
Sq. Ft Floor Area:
Valuation: $230000
performance of the work for which this permit is issued.
I have and will maintain Worker's Compensation Insurance, as provided for by
b'ection 3700 of the Labor Code, for the performance of the work for which this
APN Number: 32609007.20849
Occupancy Type:
permit is issued.
APPLICANT CERTIFICATION
I certify that I have read this application and state that the above information is
PERMIT EXPIRES IF WORK IS NOT STARTED
correct. I agree to comply with all city and county ordinances and state laws relating
WITHIN 180 D R MIT ISSUANCE OR
to building construction, and hereby authorize representatives of this city to enter
upon the above mentioned property for inspection purposes. (We) agree to save
180 D AST C SPECTION.
indemnify and keep harmless the City of Cupertino against liabilities, judgments,
costs, and expenses which may accrue against said City in consequence of the
ate:
granting of this permit. Additionally, the applicant understands and will comply
s
with all non -point source regulations per the Cupertino Municipal Cod Sectio
RE- ROOFS:
9.18.
Signature e k/
All roofs shall be inspected prior to any roofing material being installed. If a roof is
installed without first obtaining an inspection, I agree to remove all new materials for
inspection.
❑ OWNER- BUILDER DECLARATION
Signature of Applicant: Date:
I hereby affirm that I am exempt from the Contractor's License Law for one of
the following two reasons:
ALL ROOF COVERINGS TO BE CLASS "A" OR BETTER
I, as owner of the property, or my employees with wages as their sole compensation,
will do the work, and the structure is not intended or offered for sale (Sec.7044,
Business & Professions Code)
I, as owner of the property, am exclusively contracting with licensed contractors to
HAZARDOUS MATERIALS DISCLOSURE
construct the project (Sec.7044, Business & Professions Code).
I have read the hazardous materials requirements under Chapter 6.95 of the
California Health & Safety Code, Sections 25505, 25533, and 25534. I will
I hereby affirm under penalty of perjury one of the following three
maintain compliance with the Cupertino Municipal Code, Chapter 9.12 and the
declarations:
Health & Safety Code, Section 25532(a) should I store or handle hazardous
I have and will maintain a Certificate of Consent to self - insure for Worker's
material. Additionally, should I use equipment or devices which emit hazardous
Compensation, as provided for by Section 3700 of the Labor Code, for the
air contaminants as defined by the Bay Area Air Quality Management District I
performance of the work for which this permit is issued.
will maintain compliance with the Cupertino Municipal Code, Chapter 9.12 and
I have and will maintain Worker's Compensation Insurance, as provided for by
the Health & Safety Code, Sections 25505, 25533, and 25534.
�u
Section 3700 of the Labor Code, for the performance of the work for which this
Owner or authorized agent: C Date:
permit is issued.
I certify that in the performance of the work for which this permit is issued, I shall
not employ any person in any manner so as to become subject to the Worker's
CONSTRUCTION LENDING AGENCY
Compensation laws of California. If, after making this certificate of exemption, I
become subject to the Worker's Compensation provisions of the Labor Code, I must
I hereby affirm that there is a construction lending agency for the performance of
forthwith comply with such provisions or this permit shall be deemed revoked.
work's for which this permit is issued (Sec. 3097, Civ C.)
Lender's Name
APPLICANT CERTIFICATION
Lender's Address
I certify that I have read this application and state that the above information is
correct. I agree to comply with all city and county ordinances and state laws relating
to building construction, and hereby authorize representatives of this city to enter
upon the above mentioned property for inspection purposes. (We) agree to save
ARCHITECT'S DECLARATION
indemnify and keep harmless the City of Cupertino against liabilities, judgments,
costs, and expenses which may accrue against said City in consequence of the
I understand my plans shall be used as public records.
granting of this permit. Additionally, the applicant understands and will comply
with all non -point source regulations per the Cupertino Municipal Code, Section
Licensed Professional
9.18.
Signature Date
Ve
•
CONSTRUCTION PERMIT APPLICATION
COMMUNITY DEVELOPMENT DEPARTMENT • BUILDING DIVISION ` V
10300 TORRE AVENUE • CUPERTINO, CA 95014 -3255 `
(408) 777 -3228 •FAX (408) 777 -3333 • building a(�cupertino. or q O
NEW CONSTRUCTION ❑ ADDITION ❑ ALTERATION / TI ❑ REVISION / DEFERRED ORIGINAL PERMIT #t
PROJECT ADDRESS Jtq +
APN k
OWNERNAME I PHONE 7- 6
X 'Cly U /V
E -MAIL J �L4(A l
(� �- Mary ,
STREET ADDRESS
CITY, STATE, ZIP IA 7 /' CA FAX
P7
2014
(�
CONTACT NAME
PH%o / _ (� ➢i (Q
E -MAIL
STREET ADDRES
CITY, STATE, ZIP r�
FAX
2
- C
�\ 1-G- H O U
�G�
ARCHITECT ❑ ENGINEER ❑ DEVELOPER ❑ TENANT
❑ OWNER 1:3 OWNER- BUILDER ❑ OWNER AGENT El CONTRACTOR 13 CONTRACTOR AGENT b<_
CONTRACTOR NAME
LICENSE NUMBER
LICENSE TYPE
BUS. LIC k
COMPANY NAME
E -MAIL
FAX
STREET ADDRESS
CITY, STATE, ZIP
PHONE
CHrrECT NGINEER NAME
LICENSE NUMBER
BUS. LIC #
COMPANY NAME
E -MAIL
FAX
STREET ADDRESS
CITY, STATE, ZIP
PHONE
DESCRIPTION OF WORK
- `e
Provo, 4- S Y h
EXISTING USE
PROPOSED USE CONSTR
TYPE
#STORIES
'n
r¢-
Y) �J
V I
USE
TYPE
OCC.
SQ.FT.
VALUATION (S)
EXISTG
AREA % j _
!(J
NEW FLOOR
AREA / I
DEMO
AREA �2 2 /�
/
TOTAL
NET AREA
�(p
�I C
B�
C V v1 0
BATHROOM
REMODEL AREA
KITCHEN
REMODEL AREA
OTHER
REMODEL AREA
ll..
PORCH AREA
DECK AREA
TOTAL DECKIPORCH AREA
GARAGE AREA: DETACH
(,
❑ ATIACH
9DWELLINGUNI'I'S:
ISA SECOND UNrrc�
❑YES
SECOND TORY E] YES
BEING ADDED? ❑NO
ADDITION? ❑NO
PRE - APPLICATION ❑YES IF YES, PROVIDE COPY OF
IS THE BLDG AN ❑YES
TOTALVALUATION:
PLANNING APPLX NO PLANNING APPROVAL LETTER
EICHLER HOME? FIND
By my signature below, I certify to each of the following: I am the property owner or authorized agent to act on the opA owner's behalf. I have read this
application and the information I have provided is correct. I have read the Description of Work and verify it is accur I agree to comply with all applicable local
ordinances and state laws relating to ildi g construction. I autho .ze representatives of Cupertino to enter the above - identified property for inspection purposes.
C 1
Signature of Applicant/Agent: Date: C 2^
SUPPLEMENTAL 0RMAT1CM_REQbfT1SD
PLAN cPrECiT��E ...u_..
Y . RouTUac silr
Q OVER THE COUNTER s'
❑ BUILDING PLAN REVIEW
New SFD or Multifamily dwellings: Apply for demolition permit for
existing building(s). Demolition per is required prior to issuance of building
*
a
permit for new building.
❑ {EXPRESS 4 e
❑ PLANI\II\G PLAN REVIEW e
vp 1 Yu
Commercial Bldgs: Provide a completed Hazardous Materials Disclosure
❑ sTAnnnRD
❑ PvBLICwoRxs '
form if any Hazardous Materials are being used as part of this project.
a3
❑
LARGE w
FZRE DEPT
Copy of Planning Approval Letter or Meeting With Planning prior to
p
❑'
_
submittal of Building Permit application.
IvlArox
sAnITAIiY SEwER:I)ISTRICT:
.'
. ❑ +•ENVIROIVfiIENTALIHEALTFi. ,
BldgApp_2011.doc revised 06121111
"'I,
CITY OF CUPERTINO
10 oiAVIO FFF. FRTIMATOR —BUILDING DIVISION
OCCUPANCY TYPE:
ADDRESS: 208441GREENLEAF DR
DATE: 12/02/2014
REVIEWED BY: MELISSA
PC FEE ID
APN: 326 09 007
BP #:
VALUATION: $230,000
PERMIT TYPE: Building Permit
PLAN CHECK TYPE: New Construction
PRIMARY
USE: SFD or Duplex
2nd Unit? '' Yes 0 No
PENTAMATION 1 R3SFD2ND
PERMIT TYPE:
WORK I
REMOVE E ACCESSORY SHED 336 S.F. CONSTRUCT N 1 STORY 2ND UNIT WITH 1,261 S.F
SCOPE
(2 BEDROOMS /1 BATH)
OCCUPANCY TYPE:
TYPE OF
CONSTR.
FLR AREA
S.
PC FEES
PC FEE ID
BP FEES
BP FEE ID
R -3 (Custom)
II- B,III- B,IV,V -B
1,261
$2,715.89
IR3PLNCK
$1,887.73
IR3INSP
$0.00
PME Plan Check:
$0.00
Permit Fee:
$1,887.73
Suppl. Insp. Fee:O Reg. 0 OT
0.0
1 hrs
$0.00
PME Unit Fee:
$0.00
PME Permit Fee:
$0.00
TOTALS:
1,261
$2,715.89
Construction Tax: 1BCONSTAXR
1 $1,887.73
# new
NOTE: This estimate does not include fees due to other Departments (i.e. Planning, Public Works, Fire, Sanitary Sewer District, Schoot
nictrirt erc ) The.ce fees are hated nn the nreliminary information available and are onlv an estimate. Contact the Dept for adda'l info.
FEE ITEMS (Fee Resolution 11 -053 Ef ' 711113)
t fech, Man "heck
1'1111rrh. Plum C. he('%
Check
mech. P2rutit F e
I'lerxzh. Fevinit " ;,ee:
h7vc. Per)Wf Fce.
Ofhcr ,t loch. Irrsp
!other Pi11;nb /VuP3
Usher Ins"',
i ?e.
P /21n1b. hisp. /.ev.
Elec. InS17. 1`;?O:
NOTE: This estimate does not include fees due to other Departments (i.e. Planning, Public Works, Fire, Sanitary Sewer District, Schoot
nictrirt erc ) The.ce fees are hated nn the nreliminary information available and are onlv an estimate. Contact the Dept for adda'l info.
FEE ITEMS (Fee Resolution 11 -053 Ef ' 711113)
FEE
QTY /FEE
MISC ITEMS
Plan Check Fee:
$2,715.89
Select a Misc Bldg/Structure
or Element of a Building
i
Suppl. PC Fee: 0 Reg. 0 OT
0.0
hrs
$0.00
PME Plan Check:
$0.00
Permit Fee:
$1,887.73
Suppl. Insp. Fee:O Reg. 0 OT
0.0
1 hrs
$0.00
PME Unit Fee:
$0.00
PME Permit Fee:
$0.00
Construction Tax: 1BCONSTAXR
Filunits
# new
$ 667.73
_ 2. irninistr ati t a Fee:
0
0
Work Without Permit? 0 Yes C• No
$0.00
Advanced Planning Fee:
IPLLONGR
$176.54
Select a Non - Residential
Building or Structure
0
0
7i�cr��r'l C7r >r, urrr.arata,'iu,t IE7�>. >:
Strong Motion Fee:
IBSEISMICR
$29.90
Select an Administrative Item
Bldg Stds Commission Fee: IBCBSC
$10.00
SUBTOTALS:
$5,487.791
$0.00 ° TOTAL FEE-T
$5,487.79
Revised: 10/01/2014
Building Department
City Of Cupertino
10300 Torre Avenue
Cupertino, CA 95014 -3255
Telephone: 408 - 777 -3228
C U P E RT I N O Fax: 408 - 777 -3333
CONTRACTOR / SUBCONTRACTOR LIST
JOB ADDRESS: zo 8 ,r�.�
PERMIT # X6)00
OWNER'S NAME: 414 &44 ` IT14
PHONE # 'C
GENERAL CONTRACTOR:
BUSINESS LICENSE #
ADDRESS:
CITY /ZIPCODE: f
*Our municipal code requires all businesses working in the city to have a City of Cupertino business license.
NO BUILDING FINAL OR FINAL OCCUPANCY INSPECTION(S) WILL BE SCHEDULED UNTIL THE
GENERAL CONTRACTOR AND ALL SUBCONTRACTORS HAVE OBTAINED A CITY OF CUPERTINO
BUSINESS LICENSE.
I am not using any subcontractors:
Signature Date
Please check applicable subcontractors and complete the following information:
o/
SUBCONTRACTOR
BUSINESS NAME
BUSINESS LICENSE #
Cabinets & Millwork
Cement Finishing
Electrical
ELEC-J ICAL
Excavation
Fencing
Flooring / Carpeting
Linoleum / Wood
Glass / Glazing
Heating
L' I-i J� � Gvn i CC;,( h C_
Insulation
Landscaping
Lathing
Masonry
Painting / Wallpaper
Paving
Plastering
Plumbing
Roofing
Septic Tank
Sheet Metal
Sheet Rock
Ay' A2L /xic .
-?0oo �?
Tile
Owner / Contractor Signature
Dat
BUILDING ENERGY ANALYSIS REPORT
04
OT
PROJECT:
SINGLE HOUSE 2ND UNIT
20847 GREENLEAF
CUPERTINO, CA 95014
Project Designer:
H.M.C. ASSOCIATES, LLP.
12280 SARATOGA SUNNYVALE RD. #209
SARATOGA, CA 95070
()408)446 -8418
Report Prepared by:
ECEI ' E- PERFECT DESIGN & DEVELOPMENT, INC.
C 2, 2914
BY
Job Number:
P14-7280
Date:
10/8/2014
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC — www.energysoft.com.
User
0
I TABLE OF CONTENTS I
Cover Page
Table of Contents
Form CF -1 R Certificate of Compliance
Form RMS -1 Residential Measures Summary
Form MF -1 R Mandatory Measures Summary
HVAC System Heating and Cooling Loads Summary
Room Load Summary
Room Heating Peak Loads
Room Cooling Peak Loads
EnergyPro 6.3 by EnergySoft Job Number: ID: P14- -7280
User Number: 1919
1
2
3
10
11
14
15
16
17
FENESTRATION
Orientation Area(ft)
I Total Area: 103 Glazinq Percentage: 12.9%
U -Fac SHGC Overhang Sidefins
New /Altered Average U- Factor:
Exterior Shades
0.30
Status
Left (Kq 0.0
0.300
0.21 none
none
Bug Screen
New
Right (E) 8.0
0.300
0.21 none
none
Bug Screen
New
Rear (N) 36.0
0.300
0.21 none
none
Bug Screen
New
Front (S) 59.0
0.300
0.21 none
none
Bug Screen
New
HVAC SYSTEMS
Qty. Heating
Min. Eff
Cooling
Min. Eff
Thermostat
Status
1 Central Furnace
80% AFUE
Split Air Conditioner
14.0 SEER
Setback
New
HVAC DISTRIBUTION
Location Heating
Cooling Duct Location
Duct
R -Value
Status
WHOLE HOUSE Ducted
Ducted Attic
8.0
New
WATER HEATING
Qty. Type
Gallons Min. Eff
Distribution
Status
1 Small Instantaneous Gas
0
0.84
Recirc/Demand Motion
New
[Ene:m�yPro
6.3 6 Ene Soft User Number. 1919
RunCode: 2 0 14 -10- 08 715:24:38
ID: P14 -7280
Page 10 of J7
MANDATORY MEASURES SUMMARY: Residential Page 1 of 3 MF -1 R
Project Name
Date
SINGLE HOUSE 2ND UNIT
1101812014
NOTE: Low -rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF-
1 R -ALT Form) shall supersede the items marked with an asterisk ( *) below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R
Form with plans.
-Building Envelope Measures:
110.6(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§110.6(a)4: Fenestration products (except field - fabricated windows) have a label listing the certified U- Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of 10 -111 (a).
110.7: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
11 0.8 a : Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -2R Form.
§110.8(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §110.8(1) when the
installation of a Cool Roof is specified on the CF -1 R Form.
*§150.0(a): Minimum R -30 R -19 for Additions /Alterations insulation in wood -frame ceiling orequivalent U- factor.
§150.0(b): Loose fill insulation shall conform with manufacturer's installed design labeled R- Value.
*§150.0(c): Minimum R -13 insulation in 2x4 wood -frame wall (R -19 in 2x6) orequivalent U- factor.
*§150.0(d): Minimum R -19 insulation in raised wood -frame floor orequivalent U- factor.
§150.0 ft Air retarding wrap is tested, labeled, and installed according to ASTM E1677-95(2000) when specified on the CF -1 R Form.
150.0 : Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150.0(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3 %; water vapor permeance
rate is no greater than 2.0 permlinch and shall be protected from physical damage and UV light deterioration.
§150.0(q) Fenestration Products. Fenestration separating conditioned space from unconditioned space or outdoors shall meet the
requirements of either Item 1 or 2 below:
1. Fenestration, including skylight products, must have a maximum U- factor of 0.58.
2. The weighted average U- factor of all fenestration, including skylight products, shall not exceed 0.58.
EXCEPTION to Section 150.0(q)1: Up to 10 square feet of fenestration area or 0.5 percent of the Conditioned Floor Area,, whichever is
greater, is exempt from the maximum U- factor requirement.
§150.0(r) Solar Ready Buildings. Shall meet the requirements of Section 110.10 applicable to the building project.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
150.0 a 1A: Masonry or factory-built fire laces have a closable metal or glass door covering the entire opening of the firebox.
§150.0(e)1 B: Masonry or factory-built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a with a readily accessible, operable, and tight-fitting damper and or a combustion -air control device.
§150.0(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the
outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110.0- §110.3: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission.
§110.3(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §11 0.3(c)5.
§110.5: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu /hr are exempt), and pool and
spa heaters.
§150.0(h): Heating and /or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA.
§150.0(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 11 0.2 c .
§150.00)lA: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally
wrapped with insulation having an installed thermal resistance of R -12 or greater.
§150.00)1 B: Unfired storage tanks, such as storage tanks or backup tanks for solar water - heating system, or other indirect hot water
tanks, have R -12 external insulation or R -16 internal insulation where the internal insulation R -value is indicated on the exterior of the
tank.
EnergyPro 6.3 by EnergySoR User Number. 1919 ID: P14 -7280 Page 11 of 17
MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 WAR
Project Name
Date
SINGLE HOUSE 2ND UNIT
101812014
§150.00)2A: All domestic hot water system piping conditions listed below, whether buried or unburied, must be insulated per TABLE
120.3 -A.
i. The first 5 feet (1.5 meters) of hot and cold water pipes from the storage tank.
ii. All piping with a nominal diameter of 3/4 inch (19 millimeter) or larger.
iii. All piping associated with a domestic hot water recirculation system regardless of the pipe diameter.
iv. Piping from the heating source to storage tank or between tanks.
v. Piping buried below grade.
vi. All hot water pipes from the heating source to the kitchen fixtures.
§150.00)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards
Table 120.3 -A.
§150.0(1)3A: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
§150.00)4: Solar water - heating systems and /or collectors are certified by the Solar Rating and Certification Corporation.
§150.0(m)l: All air - distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC
Sections 601, 602, 603, 604, 605 and Standard 6 -5; supply -air and return -air ducts and plenums are insulated to a minimum installed
level of R -6 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct- closure system that
meets the applicable requirements of UL 181, UL 181A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic
or tape is used to seal openings reater than 1/4 inch, the combination of mastic and either mesh or tape shall be used
§150.0(m)l: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross - sectional area
of the ducts.
§150.0(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
unless such tape is used in combination with mastic and draw bands.
150.0(m)7: Exhaust fans stems have back draft or automatic dampers.
§150.0(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150.0(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
§150.0(m)10: Flexible ducts cannot have porous inner cores.
§150.0(n)l: Systems using gas or propane water heaters, whether tank or on- demand, to serve individual dwelling units shall include
all the following components:
A. A 120V electrical receptacle that is within 3 feet from the water heater and accessible to the water heater with no obstructions;
B. A Category III or IV vent, or a Type B vent.with straight pipe between the outside termination and the space where the water
heater is installed;
C. A condensate drain that is no more than 2 inches higher than the base of the installed water heater, and allows natural draining
without pump assist,
D. A gas supply line with a capacity of at least 200,000 Btu /hr.
§150.0(o): All dwelling units shall meet the requirements of ANSI /ASHRAE Standard 62.2 Ventilation and Acceptable Indoor Air Quality
in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation required in
Section 4 of that Standard.
Pool and Spa Heating Systems and Equipment Measures:
§110.4(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on -off switch mounted outside of the heater, a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating or a pilot light.
§110.4(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
and return lines, or built-up connections for future solar heating.
110.4(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover.
§110.4(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
programmed to run only during off-peak electric demand periods.
§150.0(p): Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150.0(p).
Residential Lighting Measures:
§150.0(k)lA: Installed luminaires shall be classified as high - efficacy or low- efficacy for compliance with Section 150.0(k) in accordance
with TABLE 150.0 -A or TABLE 150.0 -B, as applicable.
§150.0(k)IC: The wattage of permanently installed luminaires shall be determined asspecified by 130.0 c .
§150.0(k)ID: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency - 20 kHz.
§150.0(k)l E: Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume
no more than five watts of power per luminaire or exhaust fan as determined in accordance with Section 130.0(c). Night lights shall not
be required to be controlled by vacancy sensors.
EnergyPro 6.3 by EnergySoft User Number. 1919 ID: P14 -7260 Page 12 of 17
MANDATORY MEASURES SUMMARY: Residential (Page 3, of 3 WAR
Project Name
Date
SINGLE HOUSE 2ND UNIT
1101812014
150.0 k 1 F: Lighting integral to exhaust fans in rooms other than kitchens, shall meet the applicable requirements of §150.0(k).
150.0(k)2: All switching devices and controls shall meet the requirements of §1 50.0(k)2.
§150.0(k)3: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts
for dwelling units larger than 2,500 ft2 may be exempt from the 50 percent high efficacy requirement when all
lighting in the kitchen is controlled in accordance with the applicable provisions in Section' 150.0(k)2, and is also
controlled by vacancy sensors or dimmers.
§150.0(k)4: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
illuminated cabinet.
§150.0(k)5: Lighting installed in bathrooms shall meet the following requirements:
A. A minimum of one high efficacy luminaire shall be installed in each bathroom; and
B. All other lighting installed in each bathroom shall be hi 2h efficacy or controlled by vacancy sensors.
§150.0(k)6: Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and
controlled by vacancy sensors.
§150.0(k)7: Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be
high efficacy, or shall be controlled by either dimmers or vacancy sensors.
EXCEPTION 1: Luminaires in closets less than 70 square feet.
EXCEPTION 2: Lighting in detached storage building less than 1000 square feet located on a residential site.
§150.0(k)8: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing /rating laboratory; and have a label that certifies the luminaire is airtight with air
leakage less than 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150.0(k)9A: For single - family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on
the same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements:
L Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of items
ii or iii below; and
ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor; or controlled by a
motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and
automatically reactivates the motion sensor within 6 hours
iii. Controlled by one of the following methods:
a. Photocontrol not having an override or bypass switch that disables the photocontrol; or
b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and
which is programmed to automatically turn the outdoor lighting OFF during daylight hours; or
c. Energy management control system which meets all of the following requirements:
At a minimum provides the functionality of an astronomical time clock in accordance with Section 110.9;
meets the Installation Certification requirements in Section 130.4; meets the requirements for an EMCS in
Section 130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and,
is programmed to automatically turn the outdoor lighting OFF during daylight hours.
§150.0(k)9A: For low -rise multi - family residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and
outdoor lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the
following requirements:
i. Shall comply with Section 150.0(k)9A; or
ii. Shall comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0.
§150.0(k)9: For low -rise residential buildings with four or more dwelling units, outdoor lighting not regulated by Section 150.0(k)9B or
Section 150.0(k)9D shall comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0.
§150.0(k)9D: Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall
comply with the applicable re uirements in Sections 110.9 130.0, 130.2 130.4 140.7 and 141.0.
§150.0(k)10: Internally illuminated address signs shall comply with Section 140.8; OR not contain a screw -base socket, and consume
no more than five watts of power as determined according to §1 30.0(d).
§150.0(k)11: Lighting for residential parking garages for eight or more
vehicles shall comply with the applicable requirements for nonresidential garages in Sections 110.9, 130.0, 130.1,
130.4, 140.6, and 141.0.
§150.0(k)12A. In a low -rise multi - family residential building where the total interior common area in a single building equals 20 percent
or less of the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or
controlled by an occupant sensor.
§150.0(k)12B. In a low -rise multi - family residential building where the total interior common area in a single building equals more than
20 percent of the floor area, permanently installed lighting in that building shall:
i. Comply with the applicable requirements in Sections 110.9, 130.0, 130.1, 140.6, and 141.0; and
ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each
space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and Off from all designed paths of
in ress and egress.
EnergyPro 6.3 by EnergySoft User Number.- 1919 /D: P14 -7280 Page 13 of 17
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name Date
SINGLE HOUSE 2ND UNIT 10/8/2014
System Name Floor Area
WHOLE HOUSE 800
ENGINEERING CHECKS
Number of Svstems
Total C
Output
Cooling S'
Output
Total C
Total C
Total C
Total 0
Air S stern
CFM pc
Airflow
Outside Air (%
Outside Air of
Note: values above
HEATING SYSTEI
28 OF 70 OF
Outside Air
0 cfm
70 OF
at ARI
800 HVAC EQUIPMENT SELECTION
800 CARRIER 24ABB324/58CVA- 070 -12 (2 TON)'
1.00
421.1
0.0% Total Adjusted System Output
0.00 (Adjusted for Peak Design conditions)
:ions TIME OF SYSTEM PEAK
16,4061 5,1761 1 40,8001
16,4061 5,1761 1 40,800
Aug 3 PM Jan 1 AM
70 OF 105 OF
Coo, � - � I __lCE1U-
Supply Fan Heating Coil
105 OF
800 cfm
........... .. _ .........._..... , ,�
ROOM
70 OF
PSYCHROMETICS (Airstream Temperatures at Time of Coolina Peakl
88/68 °F 75/61 OF 75161 OF 55/54 °F
r
Outside Air
0 cfm Supply Fan Cooling Coil 55 / 54 OF
800 cfm
46.0% ROOM
.,
75 / 61 OF 75 / 61 OF
EnergyPro 6.3 by EnergySoft User Number.- 1919 RunCode: 2014- 10 -08T15 :24:38 ID: P14 -7280 Page 14 of 17
SYSTEM LOAD
1
COIL COOLING PEAK
COIL HTG. PEAK
CFM
Sensible
Latent
CFM
Sensible
40,800
Total Room Loads
237
5,042
449
217
8,083
40,800
Return Vented Lighting
0
51.0
Return Air Ducts
197
383
Return Fan
0
0
22,800
Ventilation
F 0
0
0
0
0
22,800
Supply Fan
0
0
1.9
Supply Air Ducts
197
383
28.5
421.1
TOTAL SYSTEM LOAD
1
5,4351
4491
8,849
800 HVAC EQUIPMENT SELECTION
800 CARRIER 24ABB324/58CVA- 070 -12 (2 TON)'
1.00
421.1
0.0% Total Adjusted System Output
0.00 (Adjusted for Peak Design conditions)
:ions TIME OF SYSTEM PEAK
16,4061 5,1761 1 40,8001
16,4061 5,1761 1 40,800
Aug 3 PM Jan 1 AM
70 OF 105 OF
Coo, � - � I __lCE1U-
Supply Fan Heating Coil
105 OF
800 cfm
........... .. _ .........._..... , ,�
ROOM
70 OF
PSYCHROMETICS (Airstream Temperatures at Time of Coolina Peakl
88/68 °F 75/61 OF 75161 OF 55/54 °F
r
Outside Air
0 cfm Supply Fan Cooling Coil 55 / 54 OF
800 cfm
46.0% ROOM
.,
75 / 61 OF 75 / 61 OF
EnergyPro 6.3 by EnergySoft User Number.- 1919 RunCode: 2014- 10 -08T15 :24:38 ID: P14 -7280 Page 14 of 17
ROOM LOAD SUMMARY
Project Name Date
SINGLE HOUSE 2ND UNIT 101812014
System Name Floor Area
WHOLE HOUSE 800
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name I Room Name Mult. CFM I Sensible I Latent CFM I Sensible I Latent CFM Sensible
FLOOR PLAN IFLOORPLAN 1 1 2371 5,0421 449 2371 5,0421 4491 2171 8,083
Total includes ventilation load for zonal
PAGE TOTAL
TOTAL*
237
5,042
449
217
8,083
237
5,042
449
217
8,083
ROOM HEATING PEAK LOADS
Project Name
SINGLE HOUSE 2ND UNIT
Date
101812014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name FLOOR PLAN
Floor Area 800.0 ftz
Indoor Dry Bulb Temperature 70 °F
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 28 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT OF
=
=
=
=
=
=
=
=
=
=
=
=
=
=
42
Btu /hr
R -30 Roof Attic
800.0
0.0310
42
1,042
R -15 Wall
817.0
0.0950
42
3,260
Double Non Metal Clear (6)
103.0
0.3000
42
1,298
R -19 Floor Crawlspace
800.0
0.0370
42
1,243
Items shown with an asterisk ( *) denote conduction
Infiltration:[ 1.00 X 1.077
Schedule Air Sensible
Fraction
through an interior surface
X 800 X
Area
another room
8.00 X 0.257
Height ACH
Page Total
/60] X
AT
6,842
=
1,241
TOTAL HOURLY HEAT LOSS FOR ROOM 8,083
EnergyPro 6.3 by EnergySoR User Number.- 1919 RunCode: 2014- 10- 08T15:24 :38 ID: P14 -7280 Page 16 of 17
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
SINGLE HOUSE 2ND UNIT
1 101812014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name FLOOR PLAN
Outdoor Dry Bulb Temperature
88 OF
Floor Area 800.0 ft2
Outdoor Wet Bulb Temperature
68 OF
Indoor Dry Bulb Temperature 75 OF 1
Outdoor Daily Range:
30 OF
Opaque Surfaces Orientation Area U- Factor CLTD'
Btu /hr
R -30 Roof Attic (N) 800.0 X 0.0310 X
37.0 =
918
R -15 Wall (Kq 188.0 X 0.0950 X
13.0 =
232
R -15 Wall (E) 180.0 X 0.0950 X
13.0 =
222
R -15 Wall (N) 236.0 X 0.0950 X
3.0 =
67
R -15 Wall (S) 213.0 X 0.0950 X
6.0 =
121
R -19 Floor Crawlspace 800.0 X 0.0370 X
4.0 =
118
X X
=
X X
=
X J X
=
Page Total
1,679
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded Unshaded
Fenestration Orientation Area GLF Area
GLF
Btu/hr
WINDOWS (K9 0.0 X 8.3 + 0.0 X
21.1 =
0
WINDOWS (E) 0.0 X 8.3 + 8.0 X
21.1 =
169
WINDOWS (N) 0.0 X 8.3 + 36.0 X
8.3 =
298
WINDOWS (S) 0.0 X 8.3 + 59.0 X
11.5 =
676
X + X
=
X + X
=
X + X
=
X + X
=
X + X
=
Page Total
1,143
Internal Gain
Btu /hr
Occupants 2.4 Occupants X 245 Btuh /occ.
=
588
Equipment 800 Floor Area X 0.50 w/g Q ft
=
1,365
Infiltration: 1.077 X 0.65 X 29.33 X 13 =
267
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
-
5,042
Latent Gain
Btu /hr
Occupants 2 4 Occupants X 155 Btuh /occ.
=
372
Infiltration: 4,830 X 0.65 X 29.33 X 0.00084 =
77
Air Sensible CFM ELA Aye/
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
538
EnerqvPro 6.3 by EnerqvSoff User Number., 1919 RunCode: 2014- 10- 08T15:24 :38 ID: P14 -7280
Pa a 17 of 17