B-2017-0383CITY OF CUPERTINO BUILDING PERMIT
BUILDING ADDRESS: CONTRACTOR: PERMIT NO: B-2017-0383
10123 HILLCREST RD CUPERTINO, CA 95014-1049 (326 16 057) SUNRUN
SERVICES INC
SAN LUIS OBISPO, CA
93401
OWNER'S NAME: WOOLFOLK JOHN W III AND KAY G TRUSTEE I I DATE ISSUED: 03/08/2017
I OWNER'S PHONE: 408-835-9892 I I PHONE NO: (415) 580-6900
LICENSED CONTRACTOR'S DECLARATION
License Class C-46 Lic. #750184
Contractor SUNRUN INSTALLATION SERVICES INC Date 06/30/2018
I hereby affirm that I am licensed under the provisions of Chapter 9 (commencing
with Section 7000) of Division 3 of the Business & Professions Code and that my
license is in full force and effect.
hereby affirm under penalty of perjury one of the following two declarations:
1. I have and will maintain a certificate of consent to self -insure for Worker's
Compensation, as provided for by Section 3700 of the Labor Code, for the
performance of the work for which this permit is issued.
2.` I have and will maintain Worker's Compensation Insurance, as provided for by
Section 3700 of the Labor Code, for the performance of the work for which this
permit is issued.
APPLICANT CERTIFICATION
I certify that I have read this application and state that the above
information is correct. I agree to comply with all city and county ordinances
and state laws relating to building construction, and hereby authorize
representatives of this city to enter upon the above mentioned property for
inspection purposes. (We) agree to save indemnify and keep harmless the
City of Cupertino against liabilities, judgments, costs, and expenses which
may accrue against said City in consequence of the granting of this permit.
Additionally, the applicant understands and will comply with all non -point
source regulatigng per th)jio'e�ino Municipal Code, Section 9.18.
Date 3/8/2017
I hereby affirm that Lafn exempt from the Contractor's License Law for one of the
following two reasons:
1. I, as owner of the property, or my employees with wages as their sole
compensation, will do the work, and the structure is not intended or offered for
sale (Sec.7044, Business & Professions Code)
2. I, as owner of the property, am exclusively contracting with licensed
contractors to construct the project (Sec.7044, Business & Professions Code).
hereby affirm under penalty of perjury one of the following three declarations:
1. I have and will maintain a Certificate of Consent to self -insure for Worker's
Compensation, as provided for by Section 3700 of the Labor Code, for the
performance of the work for which this permit is issued.
2. I have and will maintain Worker's Compensation Insurance, as provided for by
Section 3700 of the Labor Code; for the performance of the work for which this
permit is issued.
3. I certify that in the performance of the work for which this permit is issued, I
shall not employ any person in any manner so as to become subject to the
Worker's Compensation laws of California. If, after making this certificate of
exemption, I become subject to the Worker's Compensation provisions ofthe
Labor Code, I must forthwith comply with such provisions or this permit shall
be deemed revoked..
APPLICANT CERTIFICATION
I certify that I have read this application and state that the above information is
correct. I agree to comply with all city and county ordinances and state laws
relating to building construction, and hereby authorize representatives of this city
to enter upon the above mentioned property for inspection purposes. (We) agree
to save indemnify and keep harmless the City of Cupertino against liabilities,
judgments, costs, and expenses which may accrue against said City in
consequence of the granting of this permit. Additionally, the applicant understands
and will comply with all non -point source regulations per the Cupertino Municipal
Code, Section 9.18.
Signature Date 3/8/2017
BUILDING PERMIT INFO:
BLDG X ELECT —PLUMB
MECH X RESIDENTIAL _ COMMERCIAL
JOB DESCRIPTION:
(N) 34 -PANEL ROOF MOUNTED PV SYSTEM (9.0 KW); (l) MAIN
BREAKER (100 AMP)
Sq. Ft Floor Area: J Valuation: $18090.00
"N Number: Occupancy Type:
326 16 057
PERMIT EXPIRES IF WORK IS NOT STARTED
WITHIN 180 DAYS OF PERMIT ISSUANCE OR
180 DAYS FROM LAST CALLED INSPECTION.
by: Abby
RE -ROOFS:
All roofs shall be inspected prior to any roofing material being installed. If a roof is
installed without first obtaining an inspection, I agree to remove all new materials for
inspection.
Signature of Applicant:
Date:/83 /2017
ALL ROOF COVERINGS TO BE CLASS "A" OR BETTER
HAZARDOUS MATERIALS DISCLOSURE
I have read the hazardous materials requirements under Chapter 6.95 of the
California Health & Safety Code, Sections 25505, 25533, and 25534. I will
maintain compliance with the Cupertino Municipal Code, Chapter 9.12 and the
Health & Safety Code, Section 25532(a) should I store or handle hazardous
material. Additionally, should I use equipment or devices which emit hazardous
air contaminants as defined by the Bay Area Air Quality Management District I
will maintain compliance with the Cupertin 'cipal Code, Chapter 9.12 and
the Health & Safety Code, ec ' 25 5, 25533, and 25534.
Owner or authorized agent:
Date: 3/8/2017
CON IRA CTI LE ING AGENCY
1 hereby affirm that there is a consipiet6n lending agency for the performance
of work's for which this permit is issued (Sec. 3097, Civ C.)
Lender's Name
Lender's Address
ARCHITECT'S DECLARATION
understand my plans shall be used as public records.
Licensed
)-�-w ig - n� 3
ALTERNATIVE ENERGY PERMIT APPLICATION
COMMUNITY DEVELOPMENT DEPARTMENT • BUILDING DIVISION
10300 TORRE AVENUE • CUPERTINO, CA 95014-3255
(408) 777-3228 • FAX (408) 777-3333 • buildinq(a)-cupertino.org
PROJECT ADDRESS 10123 Hillcrest Road
APN# 32616057
OWNER NAME John Woolfolk
PHONE (4708) 835-9892
E-MAIL woolfolk@comcast.net
STREET ADDRESS 10123 Hillcrest Road
CITY, STATE, ZIP Cupertino, CA 95014
FAX
CONTACT NAME
Vance Jason
PHONE
(408) 506-3693
E-MAIL
vance.jason@sunrunhome.co
STREET ADDRESS SAME AS CONTRACTOR
CITY, STATE, ZIP
FAX
❑ OWNER ❑ OWNER -BUILDER ❑ OWNER AGENT
CONTRACTOR ❑ CONTRACTOR AGENT ❑ ARCHITECT ❑ ENGINEER ❑ DEVELOPER ❑ TENANT
CONTRACTOR NAME S u n ru n
TLICENSENUM13ER 750184
LICENSE TYPE C-46
BUS. LIC # 27932
COMPANY NAME
Sunrun
E-MAIL
FAX
(408) 894-9294
STREET ADDRESS 575 Dado St
CITY, STATE, ZIP San Jose, CA 95131
PHONE (408) 747-2487
ARCHITECT/ENGINEERNAME
LICENSE NUMBER
BUS. LIC #
COMPANY NAME
E-MAIL
FAX -
STREET ADDRESS
CITY, STATE, ZIP
PHONE
�,/
LV'
USE OF SFD Or Duplex ❑ Multi -Family
PROJECT IN WILDLAND
PROJECT IN
STRUCTURE: El Commercial
1/
URBAN INTERFACE AREA Eli� Yes NO
FLOOD ZONE ❑ Yes ❑ NO
SOLAR PANELS
❑ ELECTRIC VEHICLE CHARGING STATION
TO SOLAR WATER HEATING
❑ OTHER:
FOR SOLAR PANELS: NUMBER OF PANELS/UNITS: 34
KILOWATTS (COMMERCIAL ONLY):
TOTAL VALUATION: $ 18090.00
DESCRIPTION OF WORK 9.0 kW PV (34) MODULE SOLAR ROOFTOP INSTALLATION, NEW 100A MAIN BREAKER
RECEIVED BY:
QA
By my signature below, I certify to each of thy following:
I am the property owner or authorized agent to act on the property owner's behalf. I have read this
application and the information III ,prov' ed is c
have read the Description of Work and verify itis accurate. I agree to comply with all applicable local
ordinances and state laws relating t ui ng co do
I authorize representatives of Cupertino to enter the above-identifedprope for inspection purposes.
Date: /c
Signature of Applicant/Agent:
PPLE NT INFORMATION REQUIRED
OFFICE USE ONLY
❑ OYER -THE -COUNTER
❑ EXPRESS -
u
x
❑ STANDARD
77
/L
LARGE
W
❑ MAJOR
PVApp 2011. doe revised 03/16/11
CUpERTINO
SMOKE 1 CARSON MONOXIDE ALARMS
OWNER CERTIFICATE OF COMPLIANCE
COMMUNITY DEVELOPMENT DEPARTMENT • BUILDING DIVISION
10300 TORRE AVENUE o CUPERTINO, CA 95014-3255
(408) 777-3228 a FAX (408) 777-3333 • building(c)cupertino.org
PERMT CANNOT BE FINALED UNTIL THIS CERTIFICATE HAS BEEN
COMPLETED, 5LQjL). AND UTURMD TO THE BUILDING DIVISION
PURPOSE
Thisaffidavit is a self -certification for the installation of all required Smoke and Carbon Monoxide Alarms for
compliance with 2016 CRC Section R314, R315, 2016 CBC Sections 420.6 and 907.2.11.2 where no interior access
for inspections are required.
GENERAL INFORMATION
Existing single-family and multi -family dwellings shall be provided with Smoke Alarms and Carbon
Monoxide alarms. When the valuation of additions, alterations, or repairs to existing dwelling units exceeds
$1000.00, CRC Section R314, R315, and CBC Sections 907.2.11.5 and 420.6 require that Smoke Alarms and/or
Carbon Monoxide Alarms be installed in the following locations:
AREA
SMOKE ALARM
CO ALARM '
Outside of each separate sleeph-ig area in the immediate vicinity of the
X
X
bedroom(s)- (Smoke alarms shall not be located within 3 feet of bathroom door)
Signature...................................................................... Lic.#........................................ Date:...................
Or: every level of a dwelling unit including basements and habitable attics
X
X
_
Within eachsleeper room
X
Carbon Monoxide alarms are not required in dwellings which do not contain fuel -burning appliances and that
do not have an attached garage. Carbon monoxide alarms combined with smoke alarms shall comply tivi"rh
CBC Section 420.6 and shall be approved by the Office of the State Fire Marshal.
Power Supply: In dwelling units with no commercial power supply, alarm(s) may be solely battery operated.
In existing dwelling units, alarms are permitted to be solely battery operated where repairs or alterations do
not result in the .removal of wall and ceiling finishes or there is no access by means of attic, basement or crawl
space. Refer to CRC Section R314 and CBC Sections 907.2.11.4 and 420.6.2. An electrical permit is required for
alarms which must be connected to the building wiring.
As owner of the above -referenced property, I hereby certify that the alarm(s) referenced above has/have been
installed in accordance with the manufacturer's instructions and in compliance with the California Building
and California Residential Codes. The alarms specified below have been tested and are operational, as of the
date signed below.
t
Address: ! (f Z3 Y/ /h Permit No. -&-- -- Z6'l - a3 Y3
Specify Number of Alarms: # Smoke Alarms: # Carbon Monoxide Detectors: 1 L
s
l have read and agree to comply with the terms and conditions of this statement
Owner (or Owner Agent's) Name:
o�14
Si natur ................... Date:.%!.
Contr ctor Name:
Signature...................................................................... Lic.#........................................ Date:...................
Smoke and COform.doe revised 01/10/2017
CUPERTINt3
WATER -CONSERVING PLUMBING FIXTURES
OWNER CERTIFICATE OF COMPLIANCE
COMMUNITY DEVELOPMENT DEPARTMENT , BUILDING DIVISION
10300 TORRE AVENUE • CUPERTINO, CA 95014-3255
(408) 777-3228 • FAX (408) 777-3333 • build Ing(a.cupertino.org
Owner Name 41 ev ki, tel_ i A,' CC.-> Wa I k Am" Permit No. L' /7 -" 03 �3
Address 10 1 Z 3 � j''` j r• ,�. � t l�9
1. Is your real property a registered historical site? .
❑ Yes Civil Code Sections 1101.1 through 1101.8 do not apply. Skip the rest of the form and sign bottom of form.
C"No Go to Question 2.
Does your real property have a licensed plumber certifyingthat, due to the age or configuration of the property or its
plumbing, installation of water -conserving plumbing fixtures is not technically feasible?
❑ Yes Civil Code Sections 1101.1 through 1101.8 do not apply.
❑ The licensed plumber's certification has been provided to the Building Division.
Skip the rest of the form and sign bottom of form.
V No Go to Question 3.
3. Is water service permanently disconnected for your building?
❑ Xes Civil Code Sections 1101.1 through 1101.8 do not apply. Skip the rest of the form and sign bottom of form.
No Go to Question 4.
4. Is your real property built and available for use or occupancy on or before January 1, 1994?
❑ No My real property is built and available for use or occupancy after January 1, 1994.
Civil Code Sections 1101:.1. through 1101.8 do not apply. Skip the rest of the form and sign bottom of form.
[(Yes My real property is built and available for use or occupancy on or before January 1, 1994.
Civil Code Sections 1101.1 through 1101.8 apply. Check one of the three following statements and sign
bottom of form..
Plgjase check ONE of the following:
My property is a single family residential real property. See Civil Code Section 1101.4.
On and. after January 1, 2014, building alterations or improvements shall require all non-compliant plumbing fixtures
to be replaced with water -conserving plumbing fixtures throughout the building. On or before January 1, 2017, all non-
compliant plumbing fixtures shall be replaced with water -conserving plumbing fixtures (regardless of whether
property undergoes alterations or improvements).
❑ My property is a multii mnily residential real property. See Civil Code Section 1101.5.
On and after January 1, 2014, specified building alterations or improvements shall require non- compliant
plumbing fixtures to be replaced with water -conserving plumbing fixtures.
On or before January 1, 2019, all non-compliant plumbing fixtures shall be replaced with water -
conserving plumbing fixtures throughout.the building (regardless of whether property undergoes alterations or
improvements).
❑ My property is a commercial real property. See Civil Code Section 1101.5.
On and after January 1, 2014, specified building alterations or improvements shall require non- compliant
plumbing fixtures to be replaced with water -conserving plumbing fixtures.
On or before January 1, 2019, all non-compliant plumbing fixtures shall be replaced with water- conserving
plumbing fixtures throughout the building (regardless of whether property undergoes alterations or improvements).
I, as the owner or owner's agent of this property, certify under penalty of perjury that non-compliant plumbing fixtures will be
replaced prior to date specified above with water -conserving plumbing fixtures. in accordance with Civil Code Sections 1101.1,
through 1101.8, the current California Plumbing Code and California Green Building Standards Code, and manufacturer's
installation requirements, and that the water -conserving plumbing fixtures comply with the requirements as indicated in the
table on the following page.
Owner or Owner Agent's Signature Date: 1
Upon completing and sigmng tans c:ertrtrcate, please return it to the burudmg lirvrsron in oraer to nnai your nursing permit.
SB407 2015.doc revised 08/26/15
1. If the existing plumbing fixture water usage/flotu rate is equal to or lower than the figure shown, it is not required to be upgraded.
SE407 2015.doc revised 08/26/15
Non -Compliant
Water -Conserving Plumbing Fixture
Plumbing Fixture
(Fixture Complying with Current Code Applicable to New Construction)
Fixture Type
Maximum Water Usage/Flow Rate
2013 CPC Ch. 4
2013 CPC Ch. 4
2013 CPC Ch. 4
Water Usage
/Flow Rate
2013 CALGreen D,v. 4.3
2013 CALGreen Div. 4.3
2013 CALGreen Div. 5.3
Single -Family
Multi -Family
Commercial
Residential
Residential
Water Closets
Exceed 1.6
Single flush toilets: 1.28 gallons/flush
(Toil ets)
Gallons/flush
Dual flush toilets: 1.28 gallons/flush effective flush volume (the composite,
average flush volume of two reduced flushes and one full flush
Urinals
Exceed 1.0
Gallons/flush
0.5 gallons/flush
Showerheads
Exceed 2.5
2.0 gallons per minute @ 80 psi. Also certified to the performance criteria of -
gallons per minute
U.S. EPA WaterSense Specification for Showerheads
(A hand-held shower is considered a showerhead.)
For multiple showerheads serving one shower, the combined flow rate of all
showerheads and/or other shower outlets controlled by a single valve shall not -
exceed 2.0 gallons per minute @ 80 psi, or the shower shall be designed to
allow only one shower outlet to be in operation at a time.
Faucets —
Exceed 2.2 gallons
Maximum 1.5 gallons per
Within units:
0.5 gallons per minute @ 60
Lavatory
per minute
minute @ 60 psi; minimum
Maximum 1.5 gallons
psi
Faucets
0.8 gallons per minute @
per minute @ 60 psi;
20 psi
minimum 0.8 gallons
per minute @ 20 psi
In common and public
use areas: 0.5 gallons
per minute @ 60 psi
1.8 gallons per minute
60 psi
Faucets —
Exceed 2.2 gallons
1.8 gallons per minute @
1.8 gallons per minute
1.8 _gallons per minute @ 60
Kitchen
per minute
60 psi
@ 60 psi
psi
Faucets
May temporarily increase
May temporarily
up to 2.2 gallons per
increase up to 2.2
minute @ 60 psi, and must
gallons per minute @
default to maximum
60 psi, and must
1.8 gallons per minute @
default to maximum
60 psi
1.8 gallons per minute
Where faucets meeting
@ 60 psi
the above are unavailable,
Where faucets meeting
aerators or other means
the above are
may be used to achieve
unavailable, aerators or
reduction.
other means may be
used to achieve
reduction.
1. If the existing plumbing fixture water usage/flotu rate is equal to or lower than the figure shown, it is not required to be upgraded.
SE407 2015.doc revised 08/26/15
SCOPE OF WORK
• SYSTEM SIZE: 901 OW DC, 7600W AC
• MODULES: (34) CANADIAN SOLAR: CS6P-265P
• INVERTER(S):
(1) SOLAREDGE TECHNOLOGIES: SE 760OA-US (240V)
• RACKING: SNAPNRACK SERIES 100 UL; FLASHED L FOOT
SEE PEN D01.
• MAIN BREAKER DERATE: REPLACE EXISTING MAIN
BREAKER WITH NEW 100 AMP MAIN BREAKER.
VICINITY MAP
a F
C Q
rP
ror
107 z8 N3licrest itoaa
Sunny View Bay Area
Retirement Community
'Sunny View West G
7" 11 p.- rri F:d
'elt, Yi
nes LLP
Sie��ns U1tr-k L1vd
4
GENERAL NOTES
• ALL WORK SHALL COMPLY WITH 2016 CEC, 2016 CBC, 2016 CRC, MUNICIPAL
CODE, AND ALL MANUFACTURERS' LISTINGS AND INSTALLATION
INSTRUCTIONS.
• PHOTOVOLTAIC SYSTEM WILL COMPLY WITH 2016 CEC.
• ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH 2016 CEC.
• PHOTOVOLTAIC SYSTEM IS UNGROUNDED. NO CONDUCTORS ARE SOLIDLY
GROUNDED IN THE INVERTER. SYSTEM COMPLIES WITH 690.35.
• MODULES CONFORM TO AND ARE LISTED UNDER UL 1703.
• INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741.
• RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.
• CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(G).
• ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT.
• 9.23 AMPS MODULE SHORT CIRCUIT CURRENT.
14.42 AMPS DERATED SHORT CIRCUIT CURRENT (690.8 (a) & 690.8 (b))
CUPERTINO
Building Department
REVIEWED FOR CODE COMPLIANCE
Reviewed By: Kim Dunbar
n-- 03/08/17
LEGEND AND ABBREVIATIONS
SE SERVICE ENTRANCE
MP MAIN PANEL
SP SUB -PANEL
LC PV LOAD CENTER
SM SUNRUN METER
PM DEDICATED PV METER
INVERTER(S) WITH
INV INTEGRATED DC
DISCONNECT AND AFCI
91E]ACDISCONNECT(S)
DC DISCONNECT(S)
9
B COMBINER BOX
CB
F_ —1 INTERIOR EQUIPMENT
LE a SHOWN AS DASHED
SOLAR MODULES
RAIL
STANDOFFS &
FOOTINGS
CHIMNEY
ATTIC VENT
FLUSH ATTIC VENT
0 PVC PIPE VENT
® METAL PIPE VENT
® T -VENT
SATELLITE DISH
PV -1.0
1z
FIRE SETBACKS
SITE PLAN
PV -3.0
LAYOUT
This s
GENERAL NOTES
• ALL WORK SHALL COMPLY WITH 2016 CEC, 2016 CBC, 2016 CRC, MUNICIPAL
CODE, AND ALL MANUFACTURERS' LISTINGS AND INSTALLATION
INSTRUCTIONS.
• PHOTOVOLTAIC SYSTEM WILL COMPLY WITH 2016 CEC.
• ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH 2016 CEC.
• PHOTOVOLTAIC SYSTEM IS UNGROUNDED. NO CONDUCTORS ARE SOLIDLY
GROUNDED IN THE INVERTER. SYSTEM COMPLIES WITH 690.35.
• MODULES CONFORM TO AND ARE LISTED UNDER UL 1703.
• INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741.
• RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.
• CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(G).
• ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT.
• 9.23 AMPS MODULE SHORT CIRCUIT CURRENT.
14.42 AMPS DERATED SHORT CIRCUIT CURRENT (690.8 (a) & 690.8 (b))
CUPERTINO
Building Department
REVIEWED FOR CODE COMPLIANCE
Reviewed By: Kim Dunbar
n-- 03/08/17
LEGEND AND ABBREVIATIONS
SE SERVICE ENTRANCE
MP MAIN PANEL
SP SUB -PANEL
LC PV LOAD CENTER
SM SUNRUN METER
PM DEDICATED PV METER
INVERTER(S) WITH
INV INTEGRATED DC
DISCONNECT AND AFCI
91E]ACDISCONNECT(S)
DC DISCONNECT(S)
9
B COMBINER BOX
CB
F_ —1 INTERIOR EQUIPMENT
LE a SHOWN AS DASHED
SOLAR MODULES
RAIL
STANDOFFS &
FOOTINGS
CHIMNEY
ATTIC VENT
FLUSH ATTIC VENT
0 PVC PIPE VENT
® METAL PIPE VENT
® T -VENT
A AMPERE BY
AC ALTERNATING CURRENT DATE
AFCI ARC FAULT CIRCUIT INTERRUPTER
AZIM AZIMUTH PERMIT
COMP COMPOSITION
DC DIRECTCURRENT
(E) EXISTING
EXT EXTERIOR
FIRM FRAMING
INT INTERIOR
LBW LOAD BEARING WALL
MAG MAGNETIC
MSP MAIN SERVICE PANEL
(N) NEW
NTS NOT TO SCALE
OC ON CENTER
PRE -FAB PRE -FABRICATED
PSF POUNDS PER SQUARE FOOT
PV PHOTOVOLTAIC
TL TRANSFORMERLESS
TYP TYPICAL
V VOLTS
W WATTS
V NAME DATE COMMENTS
TABLE OF CONTENTS
SATELLITE DISH
PV -1.0
1z
FIRE SETBACKS
SITE PLAN
PV -3.0
LAYOUT
This s
ID
HARDSCAPE
site du
alterati
— PL—
PROPERTY LINE
The at
SCALE: NTBId
A AMPERE BY
AC ALTERNATING CURRENT DATE
AFCI ARC FAULT CIRCUIT INTERRUPTER
AZIM AZIMUTH PERMIT
COMP COMPOSITION
DC DIRECTCURRENT
(E) EXISTING
EXT EXTERIOR
FIRM FRAMING
INT INTERIOR
LBW LOAD BEARING WALL
MAG MAGNETIC
MSP MAIN SERVICE PANEL
(N) NEW
NTS NOT TO SCALE
OC ON CENTER
PRE -FAB PRE -FABRICATED
PSF POUNDS PER SQUARE FOOT
PV PHOTOVOLTAIC
TL TRANSFORMERLESS
TYP TYPICAL
V VOLTS
W WATTS
V NAME DATE COMMENTS
TABLE OF CONTENTS
PAGE # DESCRIPTION
PV -1.0
COVER SHEET
PV -2.0
SITE PLAN
PV -3.0
LAYOUT
PV -4.0
ELECTRICAL
PV -5.0
SIGNAGE
COMMUNITY DEVELOPMENT DEPARTN
BUILDING DIVISION—CUPERTINO
APPROVED
plans and specifications MUST be kept at the
construction. It is unlawful to make any change
Tfrom theABuildine Official.
Ordinance or State Law.
CUSTOMER RESIDENCE:
JOHN WOOLFOLK
10123 HILLCREST ROAD,
CUPERTINO, CA, 95014
TEL. (408) 835-9892APN #'. 32616057
PROJECT NUMBER:
102R-123WOOL
DESIGNER:
DEREK CARTWRIGHT
DRAFTER:
DEREK CARTWRIGHT
SHEET
COVER SHEET
REV: A 3/3/2017
PAGE PV -1.0
SITE PLAN - SCALE = 1/16" = V-0" PITCH TRUE MAG PV AREA
AZIM AZIM (SOFT)
® AR -01 18° 1750 1610 86.7
AR -02 180 850 710 156
AR -03 180 850 710 346.7
(E) POOL
-
pL
- PL PL PL
32'-1 " r
(N) ARRAY AR -03
SM INV
®
13'-5—
(N) ARRAY AR -01
MP SUnrUn
39'_1 1 a.
(E)GATE
GILBERT CORREIA, C10, C46
(N) ARRAY AR -02 CA CL #750184
575DADO ST , SPIN JOSE, CA95131
PHONE 4S' 74 7 2487
FM 408 894 9294
FIRE SETBACKS
- , a (3. TYP) CUSTOMER RESIDENCE:
° JOHN WOOLFOLK
10123 HILLCREST ROAD,
a r CUPERTINO, CA, 95014
a °.a
7J TEL. (408) 835-9892APN #'. 32616057
1T-10" a° (n PROJECT NUMBER:
a a
a 4 4 102R-123WOOL
PL PL a ° <. , , p DESIGNER: ----
DEREK CARTWRIGHT
DRAFTER:
(E) GATE DEREK CARTWRIGHT
(E) RESIDENCE SHEET F91
CUPERTINO
Building Department SITE PLAN
REV: A 3/3/2017
REVIEWED FOR CODE COMPLIANCE PAGE PV -2.0
Reviewed By: Kim Dunbar
nnro- 03/08/17
Date: uaivai_i7
ROOF
FRAME
FRAME
MAX FRAME
OC
ROOF EDGE
MAX RAIL
MAX RAIL
DESIGN CRITERIA
ROOF TYPE
ATTACHMENT
ROOF HEIGHT
EXPOSURE
MATERIAL
FRAME TYPE
SIZE
SPAN
SPACING
ZONE
SPAN
OVERHANG
MODULES:
AR -01
COMP SHINGLE
FLASHED L FOOT. SEE PEN D01.
SINGLE STORY
ATTIC
WOOD
RAFTER
2 X 6
9'- 7"
24"
T- 0"
6'- 0"
2'- 8"
CANADIAN SOLAR: CS6P-265P
MODULE DIMS:
AR -02
COMP SHINGLE
FLASHED L FOOT. SEE PEN D01.
SINGLE STORY
ATTIC
WOOD
RAFTER
2 X 6
9'- 7"
24"
T- 0"
6'- 0"
2'- 8"
64.5" x 38.7" x 1.57"
AR -03
COMP SHINGLE
FLASHED L FOOT. SEE PEN D01.
SINGLE STORY
ATTIC
WOOD
RAFTER
2 X 6
9'- 7"
24"
T- 0"
6'- 0"
2'- 8"
MODULE CLAMPS:
D1 - AR -01 - SCALE: 3/16" = V-0"
D2 - AR -02 - SCALE: 1/8" = 1'-0"
Portrait: 13.39" - 16.14"
Landscape: 7.87" - 9.84"
PITCH: 18°
PITCH: 18°
MAX DISTRIBUTED LOAD: 3 PSF
AZIM:175'
AZIM:85°
SNOW LOAD: 0 PSF
®
®
WIND SPEED:
110 MPH 3 -SEC GUST.
LAG SCREWS:
10'-9"
16'-3"
—3'-5/16"x4.0":
2.5" MIN EMBEDMENT
—4--10"—
N OTE:
INSTALLERS TO VERIFY RAFTER
2 X 6 RAFTER 24"
OC
SIZE, SPACING AND SLOPED
SPANS, AND NOTIFY E.O.R. OF
ANY DISCREPANCIES BEFORE
3'
ri
PROCEEDING.
—I- �Ip �Iq
6'
TYP �" T
I I3
Q=6' TYP—
6._6"
sunrun
21'7"
2 X 6 RAFTER
24" OC
G I LB ERT GGRREIA, 110, 146
CA CL #750184
D3 - AR -03 - SCALE: 1/8" = 1'-0"
PITCH: 18°
aC"95131
AZIM: 85'
4088949 94
RIDGE BOARD
CUSTOMER RESIDENCE:
® 3'— 26'-1" T-8" 9'-9" —3'—
JOHN
5/16" X 4.0" LAG SCREW.
HILOLOCR ST ROAD,
��10123
3'
3'
1 BOLT PER PENETRATION
CUPERTINO, CA, 95014
COMP SHI NGLE ROOF
TEL. (408) 835-9892APN # 32616057
®
PROJECT NUMBER:
—6' TYP
SOLAR MODULE
102R-123WOOL
10'-101,
0
10'-10"
TOP PLATE
DESIGNER, DESIGNER ____
:
CARTWRIGHT
O
2X6 RAFTERS, 24" O.C.--//DEREK
DRAFTER:
/
0
—
TT�T—�r'T
LOAD BEARING WALLCUPERTINO
DEREK CARTWRIGHT
T2X6RAFTER24"OC
SHEETBuilding
LAYOUT
Department
\
REV: A 3/3/2017
REVIEWED
FOR CODE COMPLIANCE
PAGE
PV -3.0
Reviewed
By: Kim Dunbar
Date: uaivai_i7
120/240 VAC
SINGLE PHASE
SERVICE
OMETER#:
M PG&E 1009266877
UTILITY
GRID
SOLAREDGE TECHNOLOGIES: SE
760OA-US (240V)
7600 WATT INVERTER JUNCTION BOX
OR EQUIVALEN
3 1 A /-2
40A PV 250V METER SOCKET LOAD RATED DC DISCONNECT
BREAKER AS 125A CONTINUOUS & WITH INTEGRATED RAPID
FARAWAY FROM 240V METER SHUTDOWN & AFCI
MAIN BREAKER 200A, FORM 2S
AS POSSIBLE
PV MODULES
1 CANADIAN SOLAR: CS6P-265P
✓j (34) MODULES
(?� % OPTIMIZERS WIRED IN (1) SERIES OF (17)
`Y OPTIMIZERS AND (1) SERIES OF (17)
OPTIMIZERS
SOLAREDGE POWER OPTIMIZER
P300
CONDUIT SCHEDULE
EXISTING
#
CONDUIT
100A MAIN
NEUTRAL
GROUND
BREAKER
NONE
1
(CENTER FED)
(1) 10 AWG BARE COPPER
2
EXISTING (N) SUN RUN
(4) 10 AWG THHN/THWN-2
NONE
125A CENTRON 4G
FACILITY
3/4" EMT OR EQUIV.
MAIN METER
(1) 10 AWG THHN/THWN-2
LOADS
PANEL
3 O
SOLAREDGE TECHNOLOGIES: SE
760OA-US (240V)
7600 WATT INVERTER JUNCTION BOX
OR EQUIVALEN
3 1 A /-2
40A PV 250V METER SOCKET LOAD RATED DC DISCONNECT
BREAKER AS 125A CONTINUOUS & WITH INTEGRATED RAPID
FARAWAY FROM 240V METER SHUTDOWN & AFCI
MAIN BREAKER 200A, FORM 2S
AS POSSIBLE
PV MODULES
1 CANADIAN SOLAR: CS6P-265P
✓j (34) MODULES
(?� % OPTIMIZERS WIRED IN (1) SERIES OF (17)
`Y OPTIMIZERS AND (1) SERIES OF (17)
OPTIMIZERS
SOLAREDGE POWER OPTIMIZER
P300
CONDUIT SCHEDULE
#
CONDUIT
CONDUCTOR
NEUTRAL
GROUND
1
NONE
(4) 10 AWG PV WIRE
NONE
(1) 10 AWG BARE COPPER
2
3/4" EMT OR EQUIV.
(4) 10 AWG THHN/THWN-2
NONE
(1) 8 AWG THHN/THWN-2
3
3/4" EMT OR EQUIV.
(2) 8 AWG THHN/THWN-2
(1) 10 AWG THHN/THWN-2
(1) 8 AWG THHN/THWN-2
NOTES TO INSTALLER:
1. 17 VDC EXPECTED OPEN CIRCUIT STRING VOLTAGE.
2. INSTALL WATER BOND WITHIN 5 FT OF WHERE THE WATER MAIN ENTER THE
HOUSE.
3. REPLACE EXISTING MAIN BREAKER WITH 100 AMP MAIN BREAKER.
4. ADD 40 AMP PV BREAKER TO MAIN PANEL.
6-12 AWG BARE 5/16"-18 SS BOLT
COPPER WIRE SS SPLIT LOCK WASHER
— (TORQUE TO 16 FTLBS)
\
\ SNAPNRACK
\ GROUNDLUG
/tSSS
1iMODULE
CHARACTERISTICS
P300 OPTIMIZER CHARACTERISTICS:
(
ONDING
CHANNEL
CANADIAN SOLAR:
MIN INPUT VOLTAGE:
8 VDC
/CS6P-265P:
Nur
265 W
MAX INPUT VOLTAGE:
48 VDC
OPEN CIRCUIT VOLTAGE: 37.7 V
MAX INPUT ISC:
10 ADC
NDING
RAIL
MAX POWER VOLTAGE: 30.6 V
MAX OUTPUT CURRENT:
15 ADC
PINS
SHORT CIRCUIT CURRENT: 9.23 A
NorE.
. ALL HARDWARE IS INCLUDED FROM MANUFACTURER
• A MINIMUM OF ONE GROUND LUG IS TO BE INSTALLED ON EVERY
SYSTEM CHARACTERISTICS - INVERTER 1
CONTINUOUS ROW OF MODULES
• GROUNDING LUG MAY BE INSTALLED IN EITHER RAIL CHANNEL
SYSTEM SIZE:
9010 W
CUPERTINO
• GROUNDING LUG MAY BE INSTALLED SO GROUND WIRE IS PARALLEL
SYSTEM OPEN CIRCUIT VOLTAGE:
17V
OR PERPENDICULAR TO RAIL
SYSTEM OPERATING VOLTAGE:
350 V
\ Building Department
• ENSURE SPLIT LOCK WASHER IS INSTALLED ON TOP OF COPPER WIRE
MAX ALLOWABLE DC VOLTAGE:
500 V
SNAPNRACK GROUNDING SCALE: NTS
SYSTEM OPERATING CURRENT:
25.7 A
SYSTEM SHORT CIRCUIT CURRENT:
30 A
REVIEWED FOR CODE COMPLIANCE
Reviewed By: Kim Dunbar
,-- 03/08/17
LABEL LOCATION.
INVERTER(S), AC DISCONNECT(S), AC COMBINER PANEL
(IF APPLICABLE).
PER CODE(S): CEC 2016:690.17(E), NEC 2014:690.17(E),
NEC 2011: 690.17(4)
LABEL LOCATION.
INVERTER(S), ENPHASE ENVOY ENCLOSURE (IF
APPLICABLE).
PER CODE(S): CEC 2016:690.5(C), NEC 2014:690.5(C),
NEC 2011: 690.5(C)
LABEL LOCATION.
INVERTER(S), DC DISCONNECTS.
PER CODE(S): CEC 2016:690.35(F), NEC
2014: 690.35(F), NEC 2011: 690.35(F)
INVERTER1
LABEL LOCATION: o • 30
INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT, AT EACH TURN, ABOVE AND
BELOW PENETRATIONS, ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS. LABEL LOCATION.
PER CODE(S): CEC 2016: 690.31(G)(3), 690.31(G)(4), NEC 2014: 690.31(G)(3), INVERTER(S), DC DISCONNECT(S).
690.31(G)(4), NEC 2011: 690.31(E)(3), 690.31(E)(4), IFC 2012: 605.11.1.4 PER CODE(S): CEC 2016:690.53, NEC 2014:690.53, NEC
2011: 690.53
LABEL LOCATION:
UTILITY SERVICE ENTRANCE/METER, OR AS REQUIRED BY LOCAL AHJ.
PER CODE(S): CEC 2016: 690.12, NEC 690.56, NEC 2014: 690.12, NEC 690.56,
IFC 2012: 605.11.1
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PERCODE(S): CEC 2016: 690.54, NEC 2014:690.54, NEC
2011: 690.54
LABEL LOCATION:
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CoDE(S): CEC 2016: 705.12(D)(3),
NEC 2014: 705.12(D)(3), NEC 2011:
705.12(D)(4)
LABEL LOCATION.
ADJACENT TO PV BREAKER (IF
LABEL LOCATION:
PHOTOVOLTAIC AC COMBINER (IF
APPLICABLE).
APPLICABLE).
PER CODE(S): CEC 2016:
PER CODE(S): CEC 2016:
705.12(D)(2)(3)(b), NEC 2014:
705.12(D)(2)(3)(c), NEC 2014:
705.12(D)(2)(3)(b), NEC 2011: 705.12(D)(7) 705.12(D)(2)(3)(c), NEC 2011: 705.12(D)(4)
REVIEWED
LABEL LOCATION.
MAIN SERVICE PANEL ADJACENT TO MAIN SERVICE
BREAKER.
PER CODE(S): PER CODE(S): NEC 2014:
705.12(D)(2)(3)(c), NEC 2011: 705.12(D)(4)
NOTES AND SPECIFICATIONS:
• SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE CEC 2016 AND
NEC 2014ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED
BY SECTION 690, OR IF REQUESTED BY THE LOCAL AHJ.
• SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE
WORDS, COLORS AND SYMBOLS.
• LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING
METHOD AND SHALL NOT BE HAND WRITTEN, UNLESS PORTIONS OF LABELS OR
MARKINGS ARE VARIABLE, OR THAT COULD BE SUBJECT TO CHANGES, SHALL
BE PERMITTED TO BE HAND WRITTEN AND SHALL BE LEGIBLE.
• LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
INVOLVED.
• SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT SAFETY
SIGNS AND LABELS, UNLESS OTHERWISE SPECIFIED.
• DO NOT COVER EXISTING MANUFACTURER LABELS.
CAUTION
POWER TO THIS BUILDING IS
ALSO SUPPLIED FROM THE
FOLLOWING SOURCES WITH
DISCONNECTS AS SHOWN
r7
SOLAR PANELS ON ROOF
INVERTER LOCATION
SUNRUN METER
SERVICE ENTRANCE AND PV
CUPERTINO BREAKER DISCONNECT
ilding Department
10123 HILLCREST ROAD, CUPERTINO, CA, 95014
iD rnnD rnnn Di ienira
Reviewed By: Kim Dunbar
n-- 03/08/17