B-2017-0660CITY OF CUPERTINO BUILDING PERMIT
BUILDING ADDRESS:
CONTRACTOR:
PERMIT NO: B-2017-0660
20790 HANFORD DR CUPERTINO, CA 95014-1824 (326 30 065)
CLEAN SOLAR INC
SAN JOSE, CA 95112
OWNER'S NAME: VAN BUREN JUSTIN LU AND ZHANG YU
DATE ISSUED: 04/26/2017
OWNER'S PHONE: 408-830-7141
PHONE NO: (408) 217-8876
LICENSED ONTRA TOR'S DECLARATION
BUILDING PERMIT INFO:
License Class C -10/C-46 Lic, #910849
Contractor CLEAN SOLAR INC Date 02/28/2018
X BLDG _ELECT _PLUMB
I hereby affirm that I am licensed under the provisions of Chapter 9 (commencing
MECH X RESIDENTIAL COMMERCIAL
with Section 7000) of Division 3 of the Business & Professions Code and that my
license is in full force and effect.
JOB DESCRIPTION:
INSTALLATION OF ROOF MOUNTED SOLAR (14 MODULES)(5.04
I hereby affirm under penalty of perjury one of the following two declarations:
kVA
1. I have and will maintain a certificate of consent to self -insure for Worker's
as provided for by Section 3700 of the Labor Code, for the
erformance of the work for which this permit is issued.
4permCompensation,
have and will maintain Worker's Compensation Insurance, as provided for by
ection 3700 of the Labor Code, for the performance of the work for which this
it is issued.
Sq. Ft Floor Area:
Valuation: $27574.00
APPLICANT CERTIFICATION
I certify that I have read this application and state that the above
information is correct. I agree to comply with all city and county ordinances
APN Number:
Occupancy Type:
and state laws relating to building construction, and hereby authorize
326 30 065
representatives of this city to enter upon the above mentioned property for
inspection purposes. (We) agree to save indemnify and keep harmless the
City of Cupertino against liabilities, judgments, costs, and expenses which
PERMIT EXPIRES IF WORK IS NOT STARTED
may accrue against said City in consequence of the granting of this permit.
WITHIN 180 DAYS OF PERMIT ISSUANCE OR
Additionally, the appI't understands and will comply with all non -point
source regulationL-e-ftne Cupe�Mulode, Section 9.18.
180 DAYS FROM LAST CALLED INSPECTION.
Signature Date
Issued by: Phuong Devries
Date: 04/26/2017
OWNE -BLIWDER DECLARATION
I hereby affirm that I am exempt from the Contractor's License Law for one of the
RE -ROOFS:
following two reasons:
All roofs shall be inspected prior to any roofing material being installed. If a roof is
1. I, as owner of the property, or my employees with wages as their sole
installed without first obtaining an inspection, I agree to remove all new materials for
compensation, will do the work, and the structure is not intended or offered for
inspection.
sale (Sec.7044, Business & Professions Code)
2. I, as owner of the property, am exclusively contracting with licensed
Signature of Applicant:
contractors to construct the project (Sec.7044, Business & Professions Code),
Date:
I hereby affirm under penalty of perjury one of the following three declarations:
ALL ROOF COVERINGS TO BE CLASS "A" OR BETTER
1. I have and will maintain a Certificate of Consent to self -insure for Worker's
Compensation, as provided for by Section 3700 of the Labor Code, for the
performance of the work for which this permit is issued.
HAZARDOUS MATERIALS DISCLOSURE
2. I have and will maintain Worker's Compensation Insurance, as provided for by
I have read the hazardous materials requirements under Chapter 6.95 of the
Section 3700 of the Labor Code, for the performance of the work for which this
California Health & Safety Code, Sections 25505, 25533, and 25534. I will
permit is issued,
maintain compliance with the Cupertino Municipal Code, Chapter 9.12 and the
3. I certify that in the performance of the work for which this permit is issued, I
Health & Safety Code, Section 25532(x) should I store or handle hazardous
shall not employ any person in any manner so as to become subject to the
material. Additionally, should I use equipment or devices which a ardous
air contaminants as defined by the Bay Area Air Quality Management Di 'ct I
Worker's Compensation laws of California. If, after making this certificate of
will maintain compliance with the Cuper 'no Municipal Code, ter 9.1 and
exemption, I become subject to the Worker's Compensation provisions of the
the Health & Safety Code, Se ns 25505, 25533, a 2 34.
Labor Code, I must forthwith comply with such provisions or this permit shall
be deemed revoked.
Owner r authorized agent:~
APPLICANT CERTIFICATION
Date:
Date /7
I certify that I have read this application and state that the above information is
correct. I agree to comply with all city and county ordinances and state laws
CONS �CTJ,r�
I hereby affirm that there isa corl9truction lending agency for the performance
relating to building construction, and hereby authorize representatives of this city
of work's for which this permi s issued (Sec. 3097, Civ C.)
to enter upon the above mentioned property for inspection purposes. (We) agree
Lender's Name
to save indemnify and keep harmless the City of Cupertino against liabilities,
judgments, costs, and expenses which may accrue against said City in
Lender's Address
consequence of the granting of this permit. Additionally, the applicant understands
and will comply with all non -point source regulations per the Cupertino Municipal
ARCHITECT'S DECLARATION
1 understand my plans shall be used as public records.
Code, Section 9.18.
Licensed
Signature Date
Professional
rC�U� PERTINO
J�[J NEW CONSTRUCTION
CONSTRUCTION PERMIT APPLICATION
COMMUNITY DEVELOPMENT DEPARTMENT • BUILDING DIVISION
10300 TORRE AVENUE • CUPERTINO, CA 95014-3255 9. 11'7 -0�(D
(408) 777-3228 • FAX (408) 777-3333 • building(a)-cupertino.org �/
❑ ADDITION ❑ ALTERATION / TI ❑ REVISION / DEFERRED ORIGINAL PERMIT #
PROJECTADDRESS07 -7 al� n
APN # O -
OWNER NAME la
_ J (�
(�.,(•/p
P��' /O 71
Ef ®d ! o� 0. `' %�I
STREET AD{yDyRE
���
CHIT-aY, STATE, ZIP
AXE
CONTACT NAME ° a [ s pa��n'�
�
P f -6�- (0//W-/�� E-MAIL a � q j //7
T C✓
STREET ADDREs� ] JQ ` $ /'vr� ®„ ®� Cy"
s�qq//❑ L/OWNER4AGGEENT /CONTRACTOR
CITY, STATE, �"j �/e f
FFAX-
❑ OWNER ❑ OWNER -BUILDER ❑ CONTRACTOR AGENT ❑ ARCHITECT ❑ ENGINEER ❑ DEVELOPER ❑ TENANT
CONTRACTOR NAME d
LICE f% (�
`r /
LIC , SF�TPE C 41Z
�(�
BUS. LIC # { 2
g
COMPANY NAME.s,�
P
STREET ADDRESS � / '%
CITY; S yHTL�%LIPL//
-
L/fie
ARCHITECT/ENGINEER NAME
LICENSE NUMBER
BUS. LIC #
COMP AME
E-MAIL
FAX
T ET ADDRESS
CITY, STATE, ZIP
PHONE
DESCRIPTION OF WORK
`0
e'
KuJ" c,
EXISTING USE
PROPOSE E COTATR.
TYPE
FIV/l
# STORIES
USE
TYPE
OCC.
SQ.FT.
VALUATION ($)
EXISTG
AREA
NEW FLOOR
AREA
DEMO
AREA
TOTAL
NET AREA
n( y��
�/ / ���(((AAA
_
BATHROOM
REMODELAREA
KITCHEN
REMODELAREA
OTHER _
REMODELAREA
_
PORCH AREA
DECK AREA
TOTAL DECKIPORCH AREA
GARAGE AREA: DETACH
ATTACH
# DWELLING UNITS:
IS A SECOND UNIT []YES
BEINGADDED? ❑NO
SECOND STORY ❑YES
ADDITION? []NO
PRE -APPLICATION ❑ YES IF YES, PROVIDE COPY OF
PLANNING APPL # ❑ NO PLANNING APPROVAL LETTER
IS THE BLDG AN ❑ YES
EICHLER HOME? O
�
RECEIVED BY:
- -
TOTAL VALUATION:
/
�Y(�9 57
By my signature below-, I certify to each of the oll Ing: I& the property er or uthor'- d agent to act on the property owner's behalf. I hav ead thlis
application and the infonnation I have provi d is orrect. I have read the cription of Wo and verify it is accurate. I agree to comply with all applicable local
ordinances and state laws relating to buil ' nstruction. I au presentatives o upertino to enter the above-ide 'fled prope for inspectionvose .
Signature of Applicant/Agent: Date:
SUPPLEMEN ORMATION REQUIRED
PLAN CHECK TYPE -
ROUTING SLIP
❑ OVER-THE-COUNTER
❑ BUHAINGPLANREVIEW
_ New SFD or Multifamil ellings: Apply for demolition permit for
existing building(s). Demolition permit is required prior to issuance of building
permit for new building.
❑ EXPRESS
PLANNING PLAN REVIEW
_ Commercial Bldgs: Provide a completed Hazardous Materials Disclosure
❑ STANDARD
❑ PUBLIC WORKS
form if any Hazardous Materials are being used as part of this project.
❑ LARGE
❑ FIRE DEPT
_ Copy of Planning Approval Letter or Meeting with Planning prior to
El MAJOR
El SANITARY SEWER DISTRICT
submittal of Building Permit application.
-
I ❑ ENVIRONMENTAL HEALTH -
B1dgApp 2011.doc revised 06/21/11
JPH
G-1
SHEET NUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
LICENSE HOLDER'S
SIGNATURE
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
AERIAL MAP
PARCEL MAP
VICINITY MAP
NTS
NTS
NTS
INSTALLATION OF
(14) SUNPOWER SPR-X22-360-C-AC AC MODULES
STC RATING: 5.04 KW DC
CEC RATING: 4.49 KW AC
OCCUPANCY TYPE: R-3
CONSTRUCTION TYPE: V-B
AHJ: CITY OF CUPERTINO
APN: 326-30-065
PROJECT VALUATION: $27,574.00
G-1 SCOPE OF WORK; SHEET INDEX; VICINITY MAP
G-2 NOTES; PROPERTY PLAN
G-3 ROOF PLAN; EQUIPMENT LOCATIONS
S-1 ROOF FRAMING PLAN; ELEVATIONS; ATTACHMENT DETAILS
E-1 ELECTRICAL LINE DIAGRAM
E-2 ELECTRICAL CALCULATIONS
F-1 SIGNAGE
Z-1+ SPECIFICATIONS
SCOPE OF WORK SHEET INDEX
Van Buren, Elle
5.04 kW DC SOLAR PHOTOVOLTAIC SYSTEM
20790 Hanford Dr., Cupertino, CA 95014
SEAN HATCH
04/26/17
JPH
G-2
SHEET NUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
SCALE: 1/16" = 1'-0"
LICENSE HOLDER'S
SIGNATURE
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
BACK OF
RESIDENCE
FRONT OF
RESIDENCE
PROPERTY PLAN
PROPERTY
LINE
EXISTING
RESIDENCE
NOTES
ALL MATERIALS, EQUIPMENT, INSTALLATION AND WORK SHALL COMPLY
WITH THE FOLLOWING APPLICABLE CODES:
· 2016 CBC / 2015 IBC
· 2016 CRC / 2015 IRC
· 2016 CEC / 2014 NEC
· 2016 CMC / 2015 UMC
· 2016 CPC / 2015 UPC
· 2016 CFC / 2015 IFC
· 2016 BUILDING ENERGY EFFICIENCY STANDARDS
· 2016 CALIFORNIA ENERGY CODE TITLE 24
· 2016 CALIFORNIA HEALTH AND SAFETY CODE
· WHERE APPLICABLE, RULES OF THE PUBLIC UTILITIES COMMISSION
REGARDING SAFETY AND RELIABILITY
· THE AUTHORITY HAVING JURISDICTION
· MANUFACTURERS' LISTINGS AND INSTALLATION INSTRUCTIONS
· CEC ARTICLE 690
· CFC ARTICLE 605.11
· IEEE STANDARD 929
· UL STANDARD 1741
· OSHA 29 CFR 1910.269
· THE AUTHORITY HAVING JURISDICTION
1. DC WIRING METHODS SHALL NOT BE INSTALLED WITHIN 10" OF
THE ROOF DECKING OR SHEATHING EXCEPT WHERE COVERED BY
THE PV MODULES AND EQUIPMENT (CEC 690.31(E)(1))
2. AN ACCESS POINT SHALL BE PROVIDED THAT DOES NOT PLACE
THE GROUND LADDER OVER OPENINGS SUCH AS WINDOWS OR
DOORS ARE LOCATED AT STRONG POINTS OF BUILDING
CONSTRUCTION AND IN LOCATIONS WHERE THE ACCESS POINT
DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS
TREE LIMBS, WIRES, OR SIGNS (CRC R331.4.2)
3. ALL EQUIPMENT AND ASSOCIATED CONNECTIONS OF INVERTERS,
MODULES, PV SOURCE CIRCUITS, BATTERY CONNECTIONS, ETC.
AND ALL ASSOCIATED WIRING AND INTERCONNECTIONS SHALL BE
INSTALLED ONLY BY QUALIFIED PERSONNEL (CEC 690.4(E))
4. RAPID SHUTDOWN REQUIREMENTS: PV SYSTEMS INSTALLED ON
OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN FUNCTION.
PV SYSTEM CONDUCTORS OF MORE THAN 5 FT INSIDE A BUILDING,
OR MORE THAN 10 FT FROM A PV ARRAY, SHALL BE LIMITED TO
NOT MORE THAN 30 VOLTS AND 240 VA WITHIN 10 SECONDS OF
RAPID SHUTDOWN INITIATION, IN ACCORDANCE WITH CEC 690.12
GOVERNING CODES
HANFORD DR.
DRIVEWAY
51'-5"
135'-5"
125'-5"
75'-5"
22'-1"
56'-3"
5'-2"
SEAN HATCH
04/26/17
MP
AC
LC
JB
JB
JB
JPH
G-3
SHEET NUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
MP
AC
LC
SERVICE POINT &
UTILITY METERING
AC LOAD CENTER
CONDUIT RUN
FIRE ACCESS POINT
FOR ACCESS LADDER
PER CFC 605.11.3.2.1
(14) (N) SOLAR MODULES
PITCH: 18°
AZIMUTH (ARRAY A): 180°
AZIMUTH (ARRAYS B, C): 270°
TOTAL AREA OF ARRAY: 246 FT²
ROOF PLAN
SCALE: 3/32" = 1'-0"
EQUIPMENT LEGEND
JB JUNCTION BOX
(E) MAIN SERVICE PANEL +
(E) #4 UFER
(N) AC LOAD CENTER
(INSIDE GARAGE)
(N) WIRING TO BE INSTALLED
IN (E) ATTIC CONDUIT
LICENSE HOLDER'S
SIGNATURE
ROOF VENTS, OBSTRUCTIONS
EXISTING
RESIDENCE
CONDUIT TO BE RUN IN ATTIC; WIRING
METHODS SHALL NOT BE INSTALLED
WITHIN 10" OF THE ROOF DECKING OR
SHEATHING EXCEPT WHERE DIRECTLY
BELOW THE ROOF SURFACE COVERED
BY PV MODULES. CIRCUITS SHALL BE
RUN PERPENDICULAR TO THE ROOF
PENETRATION POINT TO SUPPORTS A
MINIMUM OF 10" BELOW THE ROOF
DECKING PER CEC 690.31(E)(1); DC
CONDUIT TO BE LABELED AT MAX 10'
INTERVALS
CONDUIT RUNS ARE APPROXIMATE AND
ARE TO BE DETERMINED IN THE FIELD BY
THE INSTALLERS
(E) #4 WATER PIPE BOND
2ND STORY
COMPOSITION SHINGLE ROOF
ARRAY A
ARRAY
B
ARRAY C
36"
18"
6"
SEAN HATCH
04/26/17
(1) 5/16" x 4-3/4" SS LAG BOLT
MIN. 2-1/2" EMBEDMENT
FLASHFOOT-2 ALUMINUM FLASHING
WITH INTEGRATED RUBBER BUSHING
CAPFOOT
NEOPRENE BONDED SEALING WASHER
GROUNDING MODULE CLAMP
IRONRIDGE XR10 RAIL
JPH
S-1
SHEET NUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
IRONRIDGE XR10
RAIL
LICENSE HOLDER'S
SIGNATURE
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
FOOTINGS
@ MAX. 72" OC
SCALE: 1/16" = 1'-0"
NTS NTS
ELEVATION DETAIL ATTACHMENT DETAIL
PARTIAL FRAMING PLAN
WEIGHT CALCULATIONS
COMPOSITION SHINGLE
24" EAVE OVERHANG
TRUSSED RAFTERS
2" x 6" @ 24" OC
EXTERIOR WALLS
3" - 6"
TRUSSED RAFTERS
2" x 6" @ 24" OC
13'-7"
10'-6"
17'-10"
56'-10"
16'-0"
SEAN HATCH
04/26/17
(N) JBOX
NEMA 3R
G
[A] Wires in free air
* (2) #12 AWG Wire &
** (1) #12 AWG EGC
in SunPower Type TC-ER AC Cable
[B] 1/2" EMT CONDUIT
* (4) #10 AWG THWN-2 WIRE
(1) #8 AWG THWN-2 EGC
BRANCH CIRCUIT 1:
(10) SUNPOWER SPR-X22-360-C-AC MODULES
BRANCH CIRCUIT 2:
(4) SUNPOWER SPR-X22-360-C-AC MODULES
G
(N) 125A 240V
AC LOAD CENTER
SQUARE D
HOM816L125RB
[C] 3/4" EMT CONDUIT
(3) #8 AWG THWN-2 WIRE
(1) #8 AWG THWN-2 EGC
(N) PV OCPD
2P 20A
(N) PV OCPD
2P 20A
(N) OCPD
2P 20A
(N) MONITORING SYSTEM
SUNPOWER
ACPV SUPERVISOR
1/2" EMT CONDUIT
(3) #12 AWG THWN-2 WIRE
(1) #12 AWG THWN-2 EGC
UTILITY SERVICE
120/240V 1ɸ
(E) MAIN METER
(E) SQUARE D HOMELINE
225A SERVICE PANEL
(E) 200A MAIN BREAKER
(E) LOADS
G
(N) OCPD
2P 40A
(E) #4 UFER +
(E) #4 WATER PIPE BOND
JPH
E-1
SHEET NUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
LICENSE HOLDER'S
SIGNATURE
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
ELECTRICAL LINE DIAGRAM
NOTES:
· MODULES ARE BONDED TO RAIL USING UL 2703 RATED BONDING SYSTEM - INTEGRATED BONDING MID-CLAMPS + DIRECT-BURIAL LAY-IN-LUGS; SEE ATTACHED FOR SPECIFICATIONS
· WHEN UTILIZING THE 120% RULE, BACKFED PV BREAKERS WILL BE INSTALLED AT OPPOSITE END OF THE BUS BAR FROM THE MAIN BREAKER. A PERMANENT WARNING LABEL TO BE INSTALLED PER SYSTEM
SIGNAGE, SHEET F-1
· PV DC SYSTEM IS UNGROUNDED
· BACKFED PV BREAKER WILL BE INSTALLED AT OPPOSITE END OF THE BUS BAR FROM THE MAIN BREAKER. A PERMANENT WARNING LABEL TO BE INSTALLED PER SYSTEM SIGNAGE, SHEET F-1
· WHEN PRESENT, THE GEC TO BE CONTINUOUS AS PER CEC 250.64(C) AND TO TERMINATE AT A GROUNDING ELECTRODE
· FOR ALL SYSTEMS OVER 250V, CONCENTRIC AND ECCENTRIC KNOCKOUTS SHALL BE PROPERLY BONDED
* EACH SUNPOWER AC MODULE INCLUDES A FACTORY-INTEGRATED MICROINVERTER (MI) THAT DOES NOT REQUIRE A NEUTRAL WIRE TO BE CONNECTED TO IT FOR OPERATION OR FOR COMPLIANCE WITH IEEE 1547.
POWER PRODUCED IS CONDUCTED ON THE L1–L2 240 VAC OR 208 VAC GRID CONNECTION. UTILITY INTERACTIVE FUNCTIONS IN THE MI CIRCUITRY HAVE BEEN EVALUATED TO IEEE 1547, AND USE THE GROUND WIRE
INSTEAD OF THE NEUTRAL TO DETERMINE GRID VALUES. THIS FUNCTIONALITY IS PART OF ITS UL LISTING.
** GROUND PATH IS AS FOLLOWS: ONLY AC EGC IS REQUIRED FOR AC MODULES - NO DC EGC OR GEC REQUIRED; INTEGRATED BONDING IN RACKING BONDS RACKING TO MODULE FRAMES;
MODULE FRAMES HAVE INTEGRATED BONDING TO CONNECT INTO AC CABLE; NO ADDITIONAL GROUNDING WIRES REQUIRED
SEAN HATCH
04/26/17
JPH
E-2
SHEET NUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
LICENSE HOLDER'S
SIGNATURE
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
ELECTRICAL CALCULATIONS SEAN HATCH
04/26/17
JPH
F-1
SHEET NUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
LICENSE HOLDER'S
SIGNATURE
CAUTION
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECTS LOCATED AS SHOWN:
20790 HANFORD DR.,
CUPERTINO, CA 95014
PV SOLAR ARRAY
K
AC LOAD CENTER
(PV BREAKERS LOCATION)
SIGNAGE FORMAT: ALL LETTERS SHALL BE CAPITALIZED, 3/8" WHITE LETTERING ON RED BACKGROUND, ARIAL OR SIMILAR FONT, NON-BOLD; REFLECTIVE, ON WEATHER- RESISTANT MATERIAL SUITABLE FOR THE
ENVIRONMENT (USE UL-969 AS STANDARD FOR WEATHER RATING) WILL BE USED; DURABLE ADHESIVE MATERIALS MEET THIS REQUIREMENT.
TO BE PLACED JUNCTION BOXES, DISCONNECTS, RACEWAYS,
ENCLOSURES AND CABLE ASSEMBLIES; MARKING SHALL BE PLACED
ON INTERIOR AND EXTERIOR DC CONDUIT, RACEWAYS, ENCLOSURES
AND CABLE ASSEMBLIES EVERY 10 FEET, WITHIN 1 FOOT OF TURNS
OR BENDS AND WITHIN 1 FOOT ABOVE AND BELOW PENETRATIONS
OF ROOF/CEILING ASSEMBLIES, WALLS OR BARRIERS:
WARNING: PHOTOVOLTAIC POWER SOURCE
CAUTION - PHOTOVOLTAIC AC DISCONNECT
PV SYSTEM DC DISCONNECT
RATED MAX POWER-POINT CURRENT - N/A
RATED POWER-POINT VOLTAGE - N/A
MAXIMUM SYSTEM VOLTAGE - N/A
SHORT CIRCUIT CURRENT - N/A
WARNING DUAL POWER SOURCES
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM
RATED AC OUTPUT CURRENT: 18.6 A
NORMAL OPERATING AC VOLTAGE: 240 V
B
TO BE INSTALLED AT THE MAIN ELECTRICAL SERVICE
AND SUBPANEL TIE-IN LOCATIONS:
TO BE INSTALLED AT THE MAIN SERVICE PANEL,
AC DISCONNECT, AND SUBPANEL TIE-IN LOCATIONS:
TO BE INSTALLED NEXT TO THE PV BREAKER AT THE
MAIN ELECTRICAL SERVICE AND SUBPANEL TIE-IN LOCATIONS:
C
A
WARNING: ELECTRIC SHOCK HAZARD
IF A GROUND FAULT IS INDICATED,
NORMALLY GROUNDED CONDUCTORS MAY BE
UNGROUNDED AND ENERGIZED
TO BE INSTALLED AT THE INVERTER
(GROUNDED SYSTEMS, NEAR GROUND FAULT INDICATOR):
F
TO BE INSTALLED AT THE DC DISCONNECT:
TO BE INSTALLED AT THE AC DISCONNECT:
WARNING: ELECTRIC SHOCK HAZARD. THE DC
CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM
ARE UNGROUNDED AND MAY BE ENERGIZED
IN THE OPEN POSITION
TO BE INSTALLED AT THE JUNCTION BOXES, INVERTER,
AND DC DISCONNECT (UNGROUNDED SYSTEMS):
G
D
I
J
ELECTRIC SHOCK HAZARD
NO USER SERVICEABLE PARTS INSIDE
CONTACT AUTHORIZED SERVICER FOR ASSISTANCE
TO BE INSTALLED AT THE JUNCTION BOXES:
E
WARNING - INVERTER OUTPUT CONNECTION. DO NOT
RELOCATE THIS OVERCURRENT DEVICE
TO BE INSTALLED AT THE ELECTRICAL SERVICE: A DIRECTORY
PLACARD INDICATING LOCATION OF SERVICE AND PV SYSTEM
DISCONNECTING MEANS IF NOT AT THE SAME LOCATION
WARNING: ELECTRIC SHOCK HAZARD - DO NOT TOUCH
TERMINALS - TERMINALS ON BOTH THE LINE AND THE
LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION
TO BE INSTALLED AT THE DC DISCONNECT:
H
SIGNAGE
SIGNAGE LOCATIONS - AC MODULE SYSTEM
PV ARRAY JUNCTION BOX PV LOAD CENTER
(WHEN PRESENT)
AC DISCONNECT
(WHEN PRESENT)
PV METER
(WHEN PRESENT)
MAIN SERVICE
PANEL
E
SUBPANEL
(WHEN PRESENT)
A A
A
B
C
C
C
C
D
D
D
D
I K
L
PHOTOVOLTAIC SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TO BE PLACED AT THE SERVICE DISCONNECT:
L
SERVICE POINT &
UTILITY METERING
SEAN HATCH
04/26/17
PHOTOVOLTAIC MODULE SPECIFICATIONS
JPH
Z-1.1
SHEET NUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
SEAN HATCH
04/26/17
JPH
Z-1.2
SHEET
NUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
AC MODULE UL LISTINGS SEAN HATCH
04/26/17
JPH
Z-1.3
SHEETNUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
AC MODULE UL LISTINGS SEAN HATCH
04/26/17
MONITORING SPECIFICATIONS
JPH
Z-2
SHEET NUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
SEAN HATCH
04/26/17
FOOTING SPECIFICATIONS
JPH
Z-3
SHEET NUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
SEAN HATCH
04/26/17
JPH
Z-4.1
SHEETNUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
RACKING SPECIFICATIONS
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
SEAN HATCH
04/26/17
JPH
Z-4.2
SHEET
NUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
RACKING ENGINEERING SEAN HATCH
04/26/17
JPH
Z-4.3
SHEETNUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
RACKING FIRE RATING RACKING ENGINEERING SEAN HATCH
04/26/17
JPH
Z-5.1
SHEETNUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
GROUNDING & BONDING SPECIFICATIONS
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
SEAN HATCH
04/26/17
JPH
Z-5.2
SHEET
NUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
GROUNDING & BONDING SPECIFICATIONS
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
SEAN HATCH
04/26/17
JPH
Z-6
SHEET NUMBER:
DRAWN BY:
DATE:
REV:
4/21/17
4/21/17
PROJECT:
CS PROJECT ID: 2840-MZ
VAN BUREN, ELLE
20790 HANFORD DR.,
CUPERTINO, CA 95014
(415) 830-7141
CLEAN
SOLAR INC.
1445 KOLL CIRCLE.,
SUITE 109
San Jose, CA. 95112
Cont. Lic # 910849
www. cleansolar.com
PV LOAD CENTER SPECIFICATIONS SEAN HATCH
04/26/17