Loading...
12080002-ENERGY BUILDING ENERGY ANALYSIS REPORT PROJECT: Smith Residence 10139 Byrne Ave. Cupertino, CA 95014 Project Designer: Britt-Rowe 108 N. Santa Cruz Ave. Los Gatos, CA 95030 408-354-6224 Report Prepared by: Nicholas L Bignardi R08-11-2009 FRI Energy Consultants, LLC 21 N. Harrison Ave Suite 210 Campbell, CA 95008 408-866-1620 Job Number: 0120296 Date: 12/4/2012 The EnergyPro computer program has been used to perform the calculations summarized in this compliance report.This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2008 Building Energy Efficiency Standards. This program developed by EnergySoft,LLC—www.energysoft.com. EnergyPro 5.1 by EnergySoft User Number.1315 RunCode:2012-12-04T09:39:06 ID:0120296 TABLE OF CONTENTS i i Cover Page 1 Table of Contents 2 Form CF-1 R Certificate of Compliance 3 Form MF-1 R Mandatory Measures Summary 9 HVAC System Heating and Cooling Loads Summary 12 i II it j LEnergyPro 5.1 by EnergySoft Job Number: ID:0120296,__ User Number.1315 PERFORMANCE CERTIFICATE: Residential Part 1 of 5) CF-1 R Project Name Building Type m Single Family ❑Addition Alone Date Smith Residence ❑Multi Family ❑Existing+Addition/Alteration 12/4/2012 Project Address California Energy Climate Zone Total Cond.Floor Area Addition #of Stories 10139 Byrne Ave. Cupertino CA Climate Zone 04 4,004 n/a 2 FIELD INSPECTION ENERGY CHECKLIST ❑ Yes ❑ No HERS Measures -- If Yes, A CF-4R must be provided per Part 2 of 5 of this form. ❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details. INSULATION Area Special Construction Type Cavity (ftp) Features (see Part 2 of 5) Status Floor Wood Framed w/Crawl Space R-19 2,349 New Wall Wood Framed R-19 3,256 New Roof Wood Framed Attic R-30 2,680 Radiant Barrier New Floor Wood Framed w/o Crawl Space R-19 341 New FENESTRATION U- Exterior Orientation Area(ft) Factor SHGC Overhang Sidefins Shades Status Front(E) 72.0 0.400 0.40 none none Bug Screen New Front(E) 115.1 0.350 0.30 none none Bug Screen New Right(N) 101.4 0.400 0.40 none none Bug Screen New Right(N) 69.5 0.350 0.30 none none Bug Screen New Rear(W) 299.2 0.400 0.40 none none Bug Screen New Rear(W) 69.0 0.350 0.30 none none Bug Screen New Left(S) 216.0 0.400 0.40 none none Bug Screen New Left(S) 158.5 0.350 0.30 none none Bug Screen New Skylight 10.0 0.420 0.32 none none None New HVAC SYSTEMS Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status 1 Central Furnace 90%AFUE Split Air Conditioner 14.0 SEER Setback New HVAC DISTRIBUTION Duct Location Heating Cooling Duct Location R-Value Status HVAC System Ducted Ducted Attic,Ceiling Ins, vented 6.0 New WATER HEATING Qty- Type Gallons Min. Eff Distribution Status 2 Instant Gas 0 0.84 Recirc/Switch New Ener Pro 5.1 by Ener Soft User Number:1315 RunCode:2012-12-04T09:39:06 ID. 0120296 Page 3 of 12 PERFORMANCE CERTIFICATE: Residential (Part 2 of 5) CF-1 R Project Name Building Type ®Single Family ❑Addition Alone Date Smith Residence ❑ Multi Family ❑ Existing+Addition/Alteration 12/4/2012 SPECIAL FEATURES INSPECTION CHECKLIST The enforcement agency should pay special attention to the items specified in this checklist.These items require special written justification and documentation,and special verification to be used with the performance approach.The enforcement agency determines the adequacy of the justification,and may reject a building or design that otherwise complies based on the adequacy of the special 'ustification and documentation submitted. A hot water recirculation systems has been modeled. Verification of type is required. The Roof R-30 Roof Attic w/Radiant Barrier includes credit for a Radiant Barrier that is Continuous meeting eligibility and installation criteria as specified in Residential Appendix RA4.2.2. HERS REQUIRED VERIFICATION Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a completed CF-4R form for each of the measures listed below for final to be given. Ener Pro 5.1 b Ener Soft User Number:1315 RunCode:2012-12-04T09:39:06 ID:0120296 Page 4 of 12 PERFORMANCE CERTIFICATE: Residential (Part 3 of 5) CF-1 R Project Name Building Type m Single Family ❑Addition Alone Date Smith Residence ❑ Multi Family ❑ Existing+Addition/Alteration 1214/2012 ANNUAL ENERGY USE SUMMARY Standard Proposed Margin TDV kBtu/ft2-yr Space Heating 22.88 19.06 3.83 Space Cooling 6.69 10.89 -4.20 Fans 4.61 5.84 -1.23 Domestic Hot Water 9.87 7.19 2.68 Pumps 0.00 0.08 -0.08 Totals 44.04 43.06 0.99 Percent Better Than Standard: 2.2 BUILDING COMPLIES - NO HERS VERIFICATION REQUIRED Fenestration Building Front Orientation: (E)90 deg Ext.Walls/Roof Wall Area Area Number of Dwelling Units: 1.00 (E) 837 187 Fuel Available at Site: Natural Gas (S) 1,487 375 Raised Floor Area: 2,690 (149 1,007 368 Slab on Grade Area: 0 (N) 1,027 171 Average Ceiling Height: 9.2 Roof 2,690 10 Fenestration Average U-Factor: 0.38 TOTAL: 1,111 Average SHGC: 0.36 Fenestration/CFA Ratio: 27.7 REMARKS STATEMENT OF COMPLIANCE This certificate of compliance lists the building features and specifications needed to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the Efficiency Standards of the California Code of Regulations. The documentation author hereby certifies that the documentation is accurate and complete. Documentation Author Company FRI Energy Consultants,LLC Address 21 N. Harrison Ave Suite 210 Name Nicholas L Bignardi R08-11-2009 . 12 012 Cit /State/Zip Campbell, CA 95008 Phone 408-866-1620 S�ned _ Date The individual with overall design responsibility hereby certifies that the proposed building design represented in this set of construction documents is consistent with the other compliance forms and worksheets, with t pecifications, and with any other calculations submitted with this permit application, and recognizes that cot pllan e i sing duct design, duct sealing,verification of refrigerant charge, insulation installation quality, and building envel pe ealing require installer testing and certification and field verification by an approved HERS rater. Designer or Owner (per Business & Professions Code) Company Britt-Rowe Address 108 N. Santa Cruz Ave. Name Mike Rowe City/State/Zip Los Gatos, CA 95030 Phone 408-354-6224 gned License# Date Ener Pro 5.1 by Ener Soft User Number:1315 RunCode:201 2-12-04 70 9:39:06 ID:0120296 Page 5 of 12 CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF-1 R Project Name Building Type m Single Family ❑Addition Alone Date Smith Residence ❑ Multi Family ❑Existing+Addition/Alteration 12/4/2012 OPAQUE SURFACE DETAILS Surface Ll- Insulation Joint Appendix Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments Floor 2,349 0.037 R-19 0 180 New 4.4.1-A4 1st Floor Wall 268 0.074 R-19 90 90 New 4.3.1-A5 1 st Floor Wall 449 0.074 R-19 0 90 New 4.3.1-A5 1 st Floor Wall 329 0.074 R-19 270 90 New 4.3.1-A5 1st Floor Wall 679 0.074 R-19 180 90 New 4.3.1-A5 1st Floor Roof 1,025 0.031 R-30 0 18 New 4.2.1-A20 1st Floor Floor 341 0.048 R-19 0 180 New 4.4.2-A4 2nd Floor Wall 382 0.074 R-19 90 90 New 4.3.1-A5 2nd Floor Wall 407 0.074 R-19 0 90 New 4.3.1-A5 2nd Floor Wall 310 0.074 R-19 270 90 New 4.3.1-A5 2nd Floor Wall 433 0.074 R-19 180 90 New 4.3.1-A5 2nd Floor Roof 1,655 0.031 R-30 270 18 New 4.2.1-A20 2nd Floor FENESTRATION SURFACE DETAILS ID Type Area LI-Factor SHGC Azm Status Glazing Type Location/Comments 1 Window 24.0 0.400 NFRC 0.40 1 NFRC 90 New Double Non Metal Clear Door Lc 1st Floor 2 Window 48.0 0.400 NFRC 0.40 NFRC 90 New Double Non Metal Clear Door Lc 1 st Floor 3 Window 70.0 0.350 NFRC 0.30 NFRC 90 New Milgard Tuscany Low-E 1st Floor 4 Window 80.0 0.400 NFRC 0.40 NFRC 0 New Double Non Metal Clear Door Lc 1st Floor 5 Window 21.4 0.400 NFRC 0.40 NFRC 0 New Double Non Metal Clear Door Lc 1st Floor 6 Window 29.5 0.350 NFRC 0.30 NFRC 0 New Milgard Tuscany Low-E 1st Floor 7 Window 72.0 0.400 NFRC 0.40 NFRC 270 New Double Non Metal Clear Door L 1st Floor 8 Window 80.0 0.400 NFRC 0.40 NFRC 270 New Double Non Metal Clear Door L 1st Floor 9 Wndow 21.4 0.400 NFRC 0.40 NFRC 270 New Double Non Metal Clear Door L 1st Floor 10 Window 48.0 0.400 NFRC 0.40 NFRC 270 New Double Non Metal Clear Door Lc 1st Floor 11 Window 30.0 0.350 NFRC 0.30 NFRC 270 New Milgard Tuscany Low-E 1st Floor 12 Window 136.0 0.400 NFRC 0.40 NFRC 180 New Double Non Metal Clear Door L 1st Floor 13 Window 80.0 0.400 NFRC 0.40 NFRC 180 New Double Non Metal Clear Door L 1st Floor 14 Window 37.0 0.350 NFRC 0.30 NFRC 180 New Milgard Tuscany Low-E 1st Floor 15 Window 33.0 0.350 NFRC 0.30 NFRC 180 New Milgard Tuscany Low-E 1st Floor 16 Skylight 10.0 0.420 NFRC 0.32 NFRC 0 New Velux Skylight 1st Floor (1) U-Factor Type: 116-A=Default Table from Standards,NFRC=Labeled Value (2) SHGC Type: 116-B=Default Table from Standards,NFRC=Labeled Value EXTERIOR SHADING DETAILS Window 0an Left Fin Right Fin ID Exterior Shade Type SHGC H t Wd Len H t LExt RExt Dist Len H t Dist Len H t 1 Bug Screen 0.76 2 Bug Screen 0.76 3 Bug Screen 0.76 _ 4 Bug Screen 0.76 5 Bug Screen 0.76 6 Bug Screen 0.76 7 Bug Screen 0.76 8 Bug Screen 0.76 9 Bug Screen 076 10 Bug Screen 0.76 11 Bug Screen 0.76 12 Bug Screen 0.76 13 Bug Screen 0.76 14 Bug Screen 0.76 15 Bug Screen 076 16 None 100 Ener Pro 5.1 by Ener Soft User Number:1315 RunCode:2 01 2-12-04 709:39:06 ID:0120296 Pe e 6 of 12 CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF-1 R Project Name Building Type m Single Family ❑Addition Alone Date Smith Residence ❑Multi Family ❑Existing+Addition/Alteration 12/4/2012 OPAQUE SURFACE DETAILS Surface U- Insulation Joint Appendix Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments FENESTRATION SURFACE DETAILS ID Type Area LI-Factor' SHGC2 Azm Status Glazing Type Location/Comments 17 Window 32.1 0.350 NFRC 0.30 NFRC 90 New Milgard Tuscany Low-E 2nd Floor 18 Window 13.01 0.350 1 NFRC 0.30 NFRC 90 New Milgard Tuscany Low-E 2nd Floor 19 Window 40.0 0.350 NFRC 0.30 NFRC 0 New Milgard Tuscany Low-E 2nd Floor 20 Window 17.8 0.400 NFRC 0.40 NFRC 270 New Double Non Metal Clear Door Lc 2nd Floor 21 Window 60.0 0.400 NFRC 0.40 NFRC 270 New Double Non Metal Clear Door Lc 2nd Floor 22 Window 39.0 0.350 NFRC 0.30 NFRC 270 New Milgard Tuscany Low-E 2nd Floor 23 Window 19.0 0.350 NFRC 0.30 NFRC 180 New Milgard Tuscany Low-E 2nd Floor 24 Window 49.5 0.350 NFRC 0.30 NFRC 180 New Milgard Tuscany Low-E 2nd Floor 25 Window 20.0 0.350 NFRC 0.30 NFRC 180 New Milgard Tuscany Low-E 2nd Floor (1) Ll-Factor Type: 116-A=Default Table from Standards,NFRC=Labeled Value 2 SHGC Type: 116-B=Default Table from Standards,NFRC=Labeled Value EXTERIOR SHADING DETAILS Window Ove hang Left Fin Right Fin ID Exterior Shade Type SHGC H t Wd Len H t LExt RExt Dist Len H t Dist Len H t 17 Bug Screen 0.76 18 Bug Screen 0.76 19 Bug Screen 0.76 20 Bug Screen 0.76 21 Bug Screen 0.76 22 Bug Screen 0.76 23 Bug Screen 0.76 24 Bug Screen 0.76 25 Bug Screen 0.76 Ener Pro 5.1 by Ener Soft User Number:1315 RunCode:2012-12-04T09:39:06 ID. 0120296 Pae 7 of 12 CERTIFICATE OF COMPLIANCE: Residential (Part 5 of 5) CF-,l R Project Name Building Type © Single Family ❑Addition Alone Date Smith Residence ❑ Multi Family ❑ Existing+Addition/Alteration 12/4/2012 BUILDING ZONE INFORMATION Floor Area ft System Name Zone Name New Existin Altered Removed Volume Year Built HVAC System 1st Floor 2,349 23,489 2nd Floor 1,655 13,241 Totals 1 4,0041 0 0 01 1 HVAC SYSTEMS System Name Qty. Heating Type Min. Eff. Coolin T e Min. Eff. Thermostat Type Status HVAC System 1 Central Furnace 90%AFUE Split Air Conditioner 14.0 SEER Setback New HVAC DISTRIBUTION Duct Ducts System Name Heating Cooling Duct Location R-Value Tested? Status HVAC System Ducted Ducted Attic, Ceiling Ins, vented 6.0 ❑ New El 13 13 WATER HEATING SYSTEMS Ext. Rated Tank Energy Standby Tank Input Cap. Factor Loss or Insul. R- S stem Name Qty. Type Distribution Btuh al or RE Pilot Value Status Takagi T-K2 2 Instant Gas RecirclSwitch 185,000 0 0.84 n/a n/a New MULTI-FAMILY WATER HEATING DETAILS HYDRONIC HEATING SYSTEM PIPING Hot Water Piping Length (ft) o Pipe Pipe Insul. Control Qty. HP Plenum Outside Buried Q— System Name Length Diameter Thick. Ener Pro 5.1 by Ener Soft User Number.1315 RunCode:2012-12-04T09:39:06 0:0120296 Pag,e 8 of 12 MANDATORY MEASURES SUMMARY: Residential Pae 1 of 3 MF-1 R Project Name Date Smith Residence 12/4/2012 NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the compliance approach used. More stringent energy measures listed on the Certificate of Compliance(CF-1 R,CF-1 R-ADD,or CF- 1 R-ALT Form)shall supersede the items marked with an asterisk(') below.This Mandatory Measures Summary shall be incorporated into the permit documents,and the applicable features shall be considered by all parties as minimum component performance specifications whether they are shown elsewhere in the documents or in this summary.Submit all applicable sections of the MF-1 R Form with plans. Building Envelope Measures: 116(a)l:Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage §116(a)4:Fenestration products(except field-fabricated windows) have a label listing the certified U-Factor,certified Solar Heat Gain Coefficient SHGC ,and infiltration that meets the requirements of 10-111(a). 117:Exterior doors and windows are weather-stripped;all joints and penetrations are caulked and sealed. 118(a): Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on CF-6R Form. §118(1):The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of§118(1)when the installation of a Cool Roof is specified on the CF-1 R Form. *§1 50 a :Minimum R-19 insulation in wood-frame ceiling orequivalent U-factor. 150(b): Loose fill insulation shall conform with manufacturer's installed design labeled R-Value. *§1 50 c :Minimum R-13 insulation in wood-frame wall or equivalent U-factor. *§1 50(d):Minimum R-13 insulation in raised wood-frame floor orequivalent U-factor. 150(f):Air retarding wrap is tested, labeled,and installed according to ASTM E1677-95 2000 when specified on the CF-1 R Form. 150 : Mandatory Vapor barrier installed in Climate Zones 14 or 16. §150(1):Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%;water vapor permeance rate is no clreater than 2.0perm/inch and shall be protected from physical damage and UV light deterioration. Fireplaces, Decorative Gas Appliances and Gas Log Measures: 150 e 1 A:Masonry or factory-built fireplaces have a closable metal or glass door covering the entire opening of the firebox. §150(e)1 B:Masonry or factory-built fireplaces have a combustion outside air intake,which is at least six square inches in area and is equipped with a with a readily accessible,operable,and tight-fitting damper and or a combustion-air control device. §150(e)2:Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket,when that indoor air is vented to the outside of the building, are prohibited. Space Conditioning, Water Heating and Plumbing System Measures: §110-§113: HVAC equipment,water heaters,showerheads,faucets and all other regulated appliances are certified by the Energy Commission. §113(c)5:Water heating recirculation loops serving multiple dwelling units and High-Rise residential occupancies meet the air release valve, backflow prevention,pump isolation valve,and recirculation loop connection requirements of§113(c)5. §115:Continuously burning pilot lights are prohibited for natural gas:fan-type central furnaces, household cooking appliances (appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt),and pool and spa heaters. 150(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACOA. §150(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c). §150(j)1A:Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped with insulation having an installed thermal resistance of R-12 or greater. §150(j)1 B:Unfired storage tanks,such as storage tanks or backup tanks for solar water-heating system,or other indirect hot water tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R-value is indicated on the exterior of the tank. §150(j)2: First 5 feet of hot and cold water pipes closest to water heater tank, non-recirculating systems,and entire length of recirculating sections of hot water pipes are insulated per Standards Table 150-B. §150(j)2:Cooling system piping (suction,chilled water, or brine lines),and piping insulated between heating source and indirect hot water tank shall be insulated to Table 150-B and Equation 150-A. §150(j)2:Pipe insulation for steam hydronic heating systems or hot water systems>15 psi,meets the requirements of Standards Table 123-A. 150 3A: Insulation is protected from damage, including that due to sunlight, moisture,equipment maintenance, and wind. §150(j)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retardant or is enclosed entirely in conditioned space. 150(j)4:Solar water-heating systems and/or collectors are certified by the Solar Rating and Certification Corporation. EnergyPro 5.1 by EnergySoft User Number. 1315 RunCode:2012-12-04 709:39:06 ID.0120296 Page 9 of 12 MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3) MF-1 R Project Name Date Smith Residence 12/4/2012 §150(m)1:All air-distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections 601, 602,603,604, 605 and Standard 6-5;supply-air and return-air ducts and plenums are insulated to a minimum installed level of R- 4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic,tape or other duct-closure system that meets the applicable requirements of UL 181, UL 181 A,or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings reater than 1/4 inch,the combination of mastic and either mesh or tape shall be used §150(m)1:Building cavities,support platforms for air handlers, and plenums defined or constructed with materials other than sealed sheet metal,duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts. §150(m)2D:Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tae is used in combination with mastic and draw bands. 150(m)7: Exhaust fans stems have back draft or automatic dampers. §150(m)8:Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers. §150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture,equipment maintenance,and wind. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material. 150 m 10:Flexible ducts cannot have porous inner cores. §150(0):All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings.Window operation is not a permissible method of providing the Whole Building Ventilation required in Section 4 of that Standard. Pool and Spa Heating Systems and Equipment Measures: §114(a):Any pool or spa heating system shall be certified to have:a thermal efficiency that complies with the Appliance Efficiency Regulations;an on-off switch mounted outside of the heater;a permanent weatherproof plate or card with operating instructions;and shall not use electric resistance heating ora pilot light. §114(b)1:Any pool or spa heating equipment shall be installed with at least 36"of pipe between filter and heater, or dedicated suction and return lines,or built-up connections for future solar heating. 114(b)2:Outdoor pools ors as that have a heat pump or gas heater shall have a cover. §114(b)3:Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or programmed to run only during off-peak electric demand periods. 150 : Residential pool systems orequipment meet the pump sizing,flow rate,piping,filters, and valve requirements of§150 Residential Lighting Measures: §150(k)1:High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies contained in Table 150-C and is not a low efficacy luminaire asspecified by§150(k)2. 150(k)3:The wattage of permanently installed luminaires shall be determined asspecified by§130(d). §150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than 20 kHz. §150(k)5:Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line-voltage socket or line- voltage lamp holder;OR shall be rated to consume no more than five watts of power as determined by§130(d), and shall not contain a medium screw-base socket. 150(k)6:Lighting integral to exhaust fans, in rooms other than kitchens,shall meet the applicable requirements of§150(k). 150(k)7:All switching devices and controls shall meet the requirements of§150(k)7. §150(k)8:A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy. EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts for dwelling units larger than 2,500 ft2 may be exempt from the 50%high efficacy requirement when:all low efficacy luminaires in the kitchen are controlled by a manual on occupant sensor, dimmer, energy management system (EMCS), or a multi-scene programmable control system;and all permanently installed luminaries in garages, laundry rooms,closets greater than 70 square feet,and utility rooms are high efficacy and controlled by a manual-on occupant sensor. §150(k)9:Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated cabinet. EnergyPro 5.1 by EnergySoff User Number. 1315 RunCode:2012-12-04T09:39:06 ID.0120296 Page 10 of 12 MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3) MF-1 R Project Name Date Smith Residence 1 12/4/2012 §150(k)10: Permanently installed luminaires in bathrooms,attached and detached garages, laundry rooms,closets and utility rooms shall be high efficacy. EXCEPTION 1:Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual-on occupant sensor certified to comply with the applicable requirements of§119. EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a manual-on occupancy sensor. §150(k)11:Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of§119, or by a manual- on occupant sensor that complies with the applicable requirements of§119. EXCEPTION 2: Lighting in detached storage building less than 1000 square feet located on a residential site is not required to comply with§150 k 11. §150(k)12:Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact(IC) by Underwriters Laboratories or other nationally recognized testing/rating laboratory;and have a label that certifies the lumiunaire is airtight with air leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283;and be sealed with a gasket or caulk between the luminaire housing and ceiling. §150(k)13: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more dwelling units, entrances, balconies,and porches,which are permanently mounted to a residential building or to other buildings on the same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor, and one of the following controls:a photocontrol not having an override or bypass switch that disables the photocontrol;OR an astronomical time clock not having an override or bypass switch that disables the astronomical time clock;OR an energy management control system(EMCS)not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2:Outdoor luminaires used to comply with Exceptionl to§150(k)13 may be controlled by a temporary override switch which bypasses the motion sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed luminaires in or around swimming pool,water features, or other location subject to Article 680 of the California Electric Code need not be high efficacy luminaires. §150(k)14: Internally illuminated address signs shall comply with Section 148;OR not contain a screw-base socket, and consume no more than five watts of power as determined according to§130(d). §150(k)15: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable requirements of Sections 130, 131, 134, and 146. §150(k)16:Permanently installed lighting in the enclosed, non-dwelling spaces of low-rise residential buildings with four or more dwelling units shall be high efficacy luminaires. EXCEPTION:Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by an occupant sensors certified to comply with the applicable requirements of 119. EnergyPro 5.1 by EnergySoft User Number. 1315 RunCode:2 01 2-12-04 70 9:39:06 ID.0120296 Page 11 of 12 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Date Smith Residence 12/4/2012 System Name Floor Area HVAC System 4,004 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL COOLING PEAK COIL HTG.PEAK Heating System CFM Sensible Latent CFM Sensible Output perSystem 54,000 Total Room Loads 2,020 42,096 1,838 1,217 47,300 Total Output(Btuh) 54,000 Return Vented Lighting 0 Output(Btuh/s ft) 13.5 Return Air Ducts 1,419 2,011 Cooling System Return Fan 0 0 Output perSystem 48,000 Ventilation 0 0 0 0 0 Total Output(Btuh) 48,000 Supply Fan 01 0 Total Output(Tons) 4.0 Supply Air Ducts 1,419 2,011 Total Output(Btuh/s ft) 12.0 Total Output s ft/Ton 1,001.0 TOTAL SYSTEM LOAD 44,934 1,838 51,323 Air System CFM perSystem 0 HVAC EQUIPMENT SELECTION Airflow cfm 0 90%AFUE(14 SEER) 45,611 0 54,000 Airflow(cfm/sgft) 0.00 Airflow(cfm/Ton) 0.0 Outside Air(%) 0-0% Total Adjusted System Output 45,611 0 54,000 Outside Air(cfm/s ft) 0.00 (Adjusted for Peak Design conditions) Note:values above given at ARI conditions TIME OF SYSTEM PEAK Aug 3 PM Jan 1 AM HEATING SYSTEM PSYCHROMETRICS(Airstream Temperatures at Time of Heating Peak) 28 IF 67 IF 105 IF 10-0 10 Outside Air — —� - 0 cfm Heating Coil .104 OF 8011 67 IF 68 IF COOLING SYSTEM PSYCHROMETICS(Airstream Temperatures at Time of Cooling Peak) 88/681F 76/62 IF 55/54 IF Outside Air 0 cfm Cooling Coil 56/54 OF 46.4% R00M 76/62 OF --- _ 75/61 IF EnergyPro 5.1 by EnergySoft User Number.1315 RunCode:2012-12-04T09:39:06 ID:0120296 Page 12 of 12