14090064 } 1686 2nd.St.Livermore,CA 94550 Test, Adjust & Balance Report PROJECT:Apple I1-1.1N Minor Tl ADDRESS: 1 Infinite Loop Cupertino,CA 95014 ARCHITECT: Hayes Group Architects r ENGINEER: Silicon Valley Mechanical +IN GENERAL CONTRACTOR: XL Construction HVAC CONTRACTOR: Silicon Valley Mechanical LEAD BALANCE TECHNICIAN:Stephen Perry DATE: 10/21/2014 r 1av11YrN TNS�rvlA+oti9• 1686 2nd.St.Livermore,CA 94550 AIR SYMBOL SHEET DATE: 10/21/2014 PROJECT: Apple ILl.1N PAGE: 1 CFM Cubic Feet Per Minute FPM Feet Per Minute RPM Revolutions Per Minute HP Horse Power BHP Brake Horse Power FLA Full Load Amps SF Service Factor "W.G. Inches of Water gauge SP Static Pressure TSP Total Static Pressure ESP External Static Pressure AP Differential Pressure AT Differential Temperature °F Degree Fahrenheit °C Degree Celcius CD Ceiling Diffuser CS Ceiling Supply CR Ceiling Return WS Wall Suppy WR Wall Return CE Ceiling Exhaust WE Wall Exhaust EDS Exposed Duct Supply ODUCT Open Duct DSOX Duct Sox LSD Linear Slot Diffuser HEPA High Efficiency Particulate Air Filter FP-NEPA Fan Powered-High Efficiency Particulate Air Filter DNA Data Not Available DNL Data Not Listed NA Not Applicable LOA Lack of Access NI Not Installed AIR SYMBOL 1686 2nd.St.Livermore,CA 94550 GENERAL NOTES DATE: 10/21/2014 PROJECT: Apple IL1.1N PAGE: 2 1 Unless otherwise noted,indicated CFM(Cubic Feet per Minute)is a standard condition. 2 Unless otherwise noted,indicated GPM(Gallons per Minute)is a standard condition. 3 Unless otherwise noted,all sizes are measured in inches. NOTE 1686 2nd.St.Livermore,CA 9455D DUAL DUCT VAV DISTRIBUTION REPORT PROJECT: Apple VAN DATE: 10/21/2014 SYSTEM: Existing AC&HF PAGE: 3 OUTLET I INLET HEATING BOX COOLING BOX AREA SERVED DESIGN FINAL DESIGN DESIGN PRE. FINAL FINAL NOTE NO. TYPE SIZE MAX MAX MIN MAX MAX MIN MAX D120 1 CD 10 83 250 265 D122 2 CD 10 96 250 225 D124 3 CD 10 1 100 1 250 235 D110 4 CD 10 82 250 245 VAV-3 TOTAL 370 361 200 1000 208 970 D118 1 CD 10 140 250 225 D110 2 CD 10 160 250 240 VAV-4 TOTAL 300 300 100 500 110 465 D112 1 CD 10 93 250 205 D106 2 CD 10 92 250 210 D105 3 CD 10 97 250 195 D101 4 CD 10 105 250 215 VAV-5 TOTAL 410 387 200 1000 211 825 t REMARKS: (1)Final cooling maximum airflow measured with the unit damper 100%open. VAV2 !Sh 1686 2nd.St.Livermore,CA 94550 DUAL DUCT VAV DISTRIBUTION REPORT PROJECT: Apple IL1.1N DATE: 10/21/2014 SYSTEM: Existing AC&HF PAGE: 4 OUTLET I INLET HEATING BOX COOLING BOX AREA SERVED DESIGN FINAL DESIGN DESIGN PRE. FINAL FINAL NOTE NO. TYPE SIZE MAX MAX MIN MAX MAX MIN MAX D116 1 CD 8 130 140 D114 2 CD 8 130 130 VAV-18A TOTAL NA NA 52 260 55 270 D116 1 CD 8 130 120 D114 2 CD 8 130 130 VAV-18A 3 CD 8 190 190 VAV-19A TOTAL NA NA 90 450 96 440 D104 1 CD 8 130 125 D103 2 CD 8 130 125 D102 3 CD 8 130 140 VAV-20A TOTAL NA NA 78 390 76 390 REMARKS: VAV2 Tow "Y.o+1V1�G�rFrw�.�i.ficc�rwl' 1686 2nd.St.Livermore,CA 94550 DUAL DUCT VAV DISTRIBUTION REPORT PROJECT: Apple VAN DATE: 10/20/2014 SYSTEM: Existing AC&HF PAGE: 5 OUTLET/INLET HEATING BOX COOLING BOX AREA SERVED DESIGN FINAL DESIGN DESIGN PRE. FINAL FINAL NOTE NO. TYPE SIZE MAX MAX MIN MAX MAX MIN MAX A123 1 CD 8 130 130 A122 2 CD 8 130 130 A120 3 CD 10 1 250 265 A120 4 CD 10 250 225 VAV-10 TOTAL NA NA 152 760 150 750 A126 1 CD 6 130 120 A125 2 CD 6 130 140 A124 3 CD 6 130 120 VAV-11 NA NA 78 390 84 380 A113 1 CD 8 135 135 VAV-13 TOTAL NA NA 27 135 25 135 A117 1 CD 8 130 125 A118 2 CD 8 130 140 VAV-21A TOTAL NA NA 52 260 56 265 REMARKS: VAV2 1686 2nd.St.Livermore,CA 94550 DUAL DUCT VAV DISTRIBUTION REPORT PROJECT: Apple ILl.1N DATE: 10/20/2014 SYSTEM: Existing AC&HF PAGE: 6 OUTLET I INLET HEATING BOX COOLING BOX AREA SERVED DESIGN FINAL DESIGN DESIGN PRE, FINAL FINAL NOTE NO. TYPE SIZE MAX MAX MIN MAX MAX MIN MAX A119 1 CD 10 275 270 VAV-22A TOTAL 150 140 55 275 58 270 A121 1 CID 10 145 275 265 VAV-23A TOTAL 275 145 55 275 56 265 1 A127 1 CD 10 93 300 270 A127 2 CID 10 110 300 325 A127 3 CD 10 110 300 270 A127 4 CD 10 97 300 315 VAV-24A TOTAL 600 410 600 1200 605 1180 1 REMARKS: (1)Final heating maximum airflow measured with the unit damper 100%open. VAV2 1686 2nd.St.Livermore,CA 94550 JCI DDC VAV DATA REPORT PROJECT: Apple U.1N DATE: 10/21/2014 SYSTEM: Existing AC&HF PAGE: 7 HEATING BOX COOLING BOX UNIT ADDRESS SIZE/AREA FLOW GAIN DPO SIZE 1 AREA FLOW GAIN DPO VAV-3 27 14/1.07 3.509 0.73 14/1.07 2.651 2.05 VAV-4 26 10/0.55 2.33 0.44 10/0.55 2.09 -0.93 VAV-5 28 10/0.55 2.38 0.03 10/0.55 2.717 -2.55 VAV-18A 19 NA NA NA 8/0.35 3.081 -2.85 VAV-19A 17 NA NA NA 8/0.35 2.932 1.87 VAV-20A 15 NA NA NA 8/0.35 3.969 -1.38 VAV-10 64 NA NA NA 10/0.55 2.144 -2.57 VAV-11 63 NA NA NA 8/0.35 2.408 -2.20 VAV-13 61 NA NA NA 6/0.20 2.675 -1.78 VAV-21A 62 NA NA NA 6/0.20 3.107 1.53 VAV-22A 33 6/0.20 2.73 0.89 6/0.20 2.858 -1.14 VAV-23A 66 6/0.20 2.60 0.52 6/0.20 2.909 -1.75 VAV-24A 65 10/0.55 2.60 -0.01 10/0.55 2.909 -1.23 REMARKS: JCDATA