B-2017-1657 CITY OF CUPERTINO BUILDING PERMIT
BUILDING ADDRESS: CONTRACTOR: PERMIT NO:B-2017-1657
20833 HANFORD DR CUPERTINO,CA 95014-1823(326 30 073) SLINGSHOT POWER
INC
LOS ALTOS,CA 94022
OWNER'S NAME: MANNE PRABHAKAR S AND LAXMI K DATE ISSUED:09/26/2017
OWNER'S PHONE:408-839-4074 PHONE NO:(650)308-9055
LICENSED CONTRACTOR'S DECLARATION BUILDING PERMIT INFO:
License Class C-46 Lic.#984488
Contractor SLINGSHOT POWER INC Date 06/30/2019 X BLDG _ELECT _PLUMB
MECH X RESIDENTIAL_COMMERCIAL
I hereby affirm that I am licensed under the provisions of Chapter 9(commencing
with Section 7000)of Division 3 of the Business&Professions Code and that my
license is in full force and effect. JOB DESCRIPTION:
(N)14-PANEL ROOF MOUNTED PV SYSTEM(4.55 KW);(N)EV
I hereby affirm under penalty of perjury one of the following two declarations: CHARGING STATION(50 AMPS)-GARAGE
1. 1 have and will maintain a certificate of consent to self-insure for Worker's
Compensation,as provided for by Section 3700 of the Labor Code,for the
rformance of the work for which this permit is issued.
itave and will maintain Worker's Compensation Insurance,as provided for by
Section 3700 of the Labor Code,for the performance of the work for which this
permit is issued. Sq.Ft Floor Area: Valuation:$15200.00
APPLICANT CERTIFICATION
I certify that I have read this application and state that the above
information is correct.I agree to comply with all city and county ordinances APN Number: Occupancy Type:
and state laws relating to building construction,and hereby authorize 326 30 073
representatives of this city to enter upon the above mentioned property for
inspection purposes. (We)agree to save indemnify and keep harmless the
City of Cupertino against liabilities,judgments,costs,and expenses which PERMIT EXPIRES IF WORK IS NOT STARTED
may accrue against said City in consequence of the granting of this permit. WITHIN 180 DAYS OF PERMIT ISSUANCE OR
Additionally,the applicant understands and will comply with all non-point
source regulations per the Cupertino Municipal Code,Section 9.18. 180 DAYS FROM LAST CALLED INSPECTION.
lure /I _ 1*•�'�!-i j��e ate 9/26/2017 Issued by:Abby Ayende
Date:09/26/2017
OWNER-BUILDER DECLARATION
I hereby affirm that I am exempt from the Contractor's License Law for one of the RE-ROOFS;
following two reasons: All roofs shall be inspected prior to any roofing material beingynstalled.If a roof is
1. I,as owner of the property,or my employees with wages as their sole installed without first obtaining an inspection,I agree to remove all new materials for
compensation,will do the work,and the structure is not intended or offered for inspection.
sale(Sec.7044,Business&Professions Code)
2. I,as owner of the property,am exclusively contracting with licensed Signature of Applicant:
contractors to construct the project(Sec.7044,Business&Professions Code). Date:9/26/2017
I hereby affirm under penalty of perjury one of the following three declarations: ALL ROOF COVERINGS TO BE CLASS"A"OR BETTER
1. 1 have and will maintain a Certificate of Consent to self-insure for Worker's
Compensation,as provided for by Section 3700 of the Labor Code,for the
performance of the work for which this permit is issued. HAZARDOUS MATERIALS DISCLOSURE
z. I have and will maintain Worker's Compensation Insurance,as provided for by I have read the hazardous materials requirements under Chapter 6.95 of the
Section 3700 of the Labor Code,for the performance of the work for which this California Health&Safety Code,Sections 25505,25533,and 25534. I will
permit is issued. maintain compliance with the Cupertino Municipal Code,Chapter 9.12 and the
3. I certify that in the performance of the work for which this permit is issued,I Health&Safety Code,Section 25532(a)should I store or handle hazardous
shall not employ any person in any manner so as to become subject to the material. Additionally,should I use equipment or devices which emit hazardous
air contaminants as defined by the Bay Area Air Quality Management District I
Worker's Compensation laws of California. If,after making this certificate of will maintain compliance with the Cupertino Municipal Code,Chapter 9.12 and
exemption,I become subject to the Worker's Compensation provisions of the the Health&Safety Code,Sections 25505,25533,and 25534.
Labor Code,I must forthwith comply with such provisions or this permit shall nn
be deemed revoked. '/ , 1 I, —....as--....—...----
�Mll�r or authorized agent:_ /Ail*��/ � �s
APPLICANT CERTIFICATION Date:9/26/2017
I certify that I have read this application and state that the above information is CONST' . e • ENDING AGENCY
correct.I agree to comply with all city and county ordinances and state laws I hereby affirm that there is a construction lending agency for the performance
relating to building construction,and hereby authorize representatives of this city of work's for which this permit is issued(Sec.3097,Civ C.)
to enter upon the above mentioned property for inspection purposes. (We)agree Lender's Name
to save indemnify and keep harmless the City of Cupertino against liabilities,
judgments,costs,and expenses which may accrue against said City in Lender's Address
consequence of the granting of this permit. Additionally,the applicant understands
and will comply with all non-point source regulations per the Cupertino Municipal ARCHITECT'S DECLARATION
Code,Section 9.18. I understand my plans shall be used as public records.
Signature Date 9/26/2017 Licensed
Professional
b-Loi - - lui l-
\ /�' ALTERNATIVE ENERGY PERMIT APPLICATION
(704 ,
ir COMMUNITY DEVELOPMENT DEPARTMENT•BUILDING DIVISIONAE
10300 TORRE AVENUE•CUPERTINO,CA 95014-3255
vS`,,,\
CUPERTINO (408)777-3228• FAX(408)777-3333•buildinq aacuoertino.orq
PROJECT ADDRESS APN#
20833 Hanford Drive ' 2.(.0.. `0 3
OWNER NAME Prabhakar Manne PHONE 408-839-4074 E-MAIL spmanne@gmail.com
STREET ADDRESS 20833 Hanford Drive CITY,sptino, CA 95014 FAX
CONTACT NAME Linda Dodge PHONE 669-213-9211 E-MAILldodge@slingshotpower.com
STREET ADDRESS 164 Main Street CITY,STATE,ZIP Los Altos, CA 94022 FAX 408-887-0345
❑OWNER 0 OWNER-BUILDER 0 OWNER AGENT 0 CONTRACTOR ❑;CONTRACTOR AGENT 0 ARCHITECT 0 ENGINEER 0 DEVELOPER 0 TENANT
CONTRACTOR NAME Ravi Chiruvolu ,IdCEJ'$gp(UMBER LICENSE TYPE C46 Bus.LIC#403538
COMPANY NAME Slingshot Power `Jj���{{��}}E-�jSMAIL ldodge@slingshotpower.com FAX650-887-0345
STREET ADDRESS 164 Main Street CITY,STATE,ZIP Los Altos, CA 94022 PHONE 650-209-0171
ARCHITECT/ENGINEER NAME LICENSE NUMBER BUS.LIC#
COMPANY NAME E-MAIL FAX
STREET ADDRESS CITY,STATE,ZIP PHONE
USE OF Cf SFD or Duplex 0 Multi-Family PROJECT IN PROJECT IN
STRUCTURE: 0 Commercial� ELECWILDLANURBAN 0 Yes 13 No FLOOD ZONE 0 Yes No
7 SOLAR PANELS ar TRIC VEHICLE CHARGING STATION 0 SOLAR WATER HEATING 0 OTHER:
FOR SOLAR PANELS: NUMBER OF PANELS/UNITS: i Lt KILOWATTS(COMMERCIAL ONLY): TOTAL VALUATION: $15,200.00
DESCRIPTION OF WORK Installation of(14) Panasonic VBHN325SA16 Modules and (1) Solar Edge 5000/P300 inverter
mounted on the Roof of the Residence Size of project 4.32 KW
1 a\GVI Tl() Gt ov1 ( awl )
RECEIVED BY: /��� y-
4k...
1
By my signature below,I certify to each of the following: I am the property owner or authorized agent to act on the property ownb all. I have read this
application and the information I have provided is correct. I have read the Description of Work and verify it is accurate. I agree to comply with all applicable local
ordinances and state laws relating to building construction. I authorize representatives of Cupertino to enter the above-identified property for inspection purposes.
Signature of Applicant/Agent: . . Date: 9/25/17
SUPPLEMENTAL INFORMATION REQUIRED OFFICE USE ONLY
y 0 OVER-THE-COUNTER
Q.
F 0 EXPRESS
U
0 STANDARD
U
0 LARGE
a.
0 MAJOR
PVApp_2011.doc revised 03/16/11
Fl
SMOKE / CARSON MONOXIDE ALARMS 11
OWNER CERTIFICATE OF COMPLIANCE
COMMUNITY DEVELOPMENT DEPARTMENT• BUILDING DIVISION
CUPERTINO 10300 TORRE AVENUE•CUPERTINO,CA 95014-3255
(408)777-3228•FAX(408)777-3333•buildinq(�cupertino.orq
PERMIT CANNOT BE FINALED UNTIL THIS CERTIFICATE.HAS BEEN
',-:':;?-`'`.;'!';' ''''-:COMPLETED;SIGNED,AND RETURNED TO THE BUILDINFG DIVISION• (
PURPOSE
.This affidavit is a self-certification for the installation of all required Smoke and Carbon Monoxide Alarms for
compliance with 2016 CRC Section R314,R315,2016 CBC Sections 420.6 and 907.2.11.2 where no interior access
for inspections are required.
GENERAL INFORMATION
Existing single-familyand multi-family dwellings shall be provided with Smoke Alarms and Carbon
Monoxide alarms. When the valuation of additions, alterations,or repairs to existing dwelling units exceeds
$1000.00, CRC Section R314,R315, and CBC Sections 907.2.11.5 and 420.6 require that Smoke Alarms and/or
Carbon Monoxide Alarms be installed in the following locations:
AREA SMOKE ALARM CO ALARM
Outside of each separate sleeping area in the immediate vicinity of the X X
bedroom(s)-(Smoke alarms shall not be located within 3 feet of bathroom door)
On every level of a dwelling unit including basements and habitable attics X X
Within each sleeping room X
Carbon Monoxide alarms are not required in dwellings which do notcontain fuel-burning appliances and that
do not have an attached garage. Carbon monoxide alarms combined with smoke alarms shall comply with
CBC Section 420.6 and shall be approved by the Office of the State Fire Marshal.
Power Supply:In dwelling units with no commercial power supply, alarrn(s)may be solely battery operated.
In existing dwelling units, alarms are permitted tobe solely battery operated where repairs or alterations.do ..
not result in the removal of wall and ceiling finishes or there is no access by means of attic,basement or crawl•
space.Refer to CRC Section R314 and CBC Sections 907.2.11.4 and 420.6.2.An electrical permit is required for:
alarms which must be connected to the building wiring.
As ownerof the above-referenced property,I hereby certify that the alarm(s)referenced above has/have been
installed in accordance with the manufacturer's instructions and in compliance with the California Building .. .
and California Residential Codes.The alarms specified below have been tested and are operational, as of the
date signed Blown 1/2
Address: 0 `� k--kai,\ Og--)
Permit No. /3-20-3-. - /
(05q —
Specify Number of Alarms: #Smoke Alarms: I1 . #Carbon Monoxide Detectors: _
• /have read and agree to comply with the terms and conditions of this statement
Owner(or Owner Agent's)Name: �p� J%
v ! (�/� Signature/�f'.TQ( .4.R (c, Date:
'ontracfor Name:`
S I I i1(i Wii. pot P✓ Signature is" -� Lic.# Date: 7/7// /
Smoke and COform.doc revised 01/10/2017
GENERAL NOTES
1. THIS SYSTEM IS GRID-TIED WITH A UL LISTED
POWER CONDITIONING INVERTER
2. THIS SYSTEM HAS NO BATTERIES. NO UPS
3. ALL WORK SHALL COMPLY WITH THE 2016
CALIFORNIA BUILDING CODE AND THE 2016
CALIFORNIA RESIDENTIAL CODE
4. ALL WORK SHALL COMPLY WITH THE 2014
NATIONAL ELECTRIC CODE AS AMENDED BY THE
2016 CALIFORNIA ELECTRIC CODE
5. LOCAL UTILITY SHALL BE CONTACTED PRIOR TO
ENERGIZATION OF THE SYSTEM
ELECTRICAL NOTES
1. A NATIONALLY RECOGNIZED TESTING LABORATORY SHALL LIST ALL EQUIPMENT IN COMPLIANCE WITH ART
110.3
2. ALL EXTERIOR EQUIPMENT SHALL BE RAIN TIGHT AND APPROVED FOR USE IN WET CONDITIONS
3. BACKFEED BREAKER MUST BE LOCATED AT THE OPPOSITE END OF BREAKER OR LUGS PROVIDING POWER
FROM THE UTILITY
4. DC CONDUCTORS ENTERING A BUILDING WILL BE RUN IN METALLIC RACEWAYS TO THE FIRST ACCESSIBLE
MEANS OF DISCONNECTION PER ART 690.31(E)
5. ALL CONDUCTORS SHALL BE PROVIDED WITH STRAIN RELIEF UPON ENTRY INTO ENCLOSURES.
6. EACH UNGROUNDED CONDUCTOR SHALL BE IDENTIFIED BY PHASE AND SYSTEM PER ART 210.5
7. WHERE ALL TERMINALS OF THE DISCONNECTING MEANS SHALL REMAIN ENERGIZED IN THE OPEN POSITION,
A WARNING SIGN SHALL BE PROVIDED PER ART 690.17
8. THE DC GROUNDING ELECTRODE CONDUCTOR SHALL BE SIZED PER ART 690.47 AND 250.66(B)
9. MODULE FRAMES SHALL BE GROUNDED AT THE UL-LISTED LOCATION PROVIDED BY THE MANUFACTURER
USING UL-LISTED HARDWARE
10.ALL METALLIC COMPONENTS SHALL BE GROUNDED VIA ELECTRIC GROUNDING CONDUCTORS AND
GROUNDED AT THE MAIN SERVICE
11.2014 NEC 690.12 RAPID SHUTDOWN COMPLIANT
ABBREVIATIONS
A AMPERE
AC ALTERNATING CURRENT
ART ARTICLE
BLDG BUILDING STRUCTURE
CONC CONCRETE
DC DIRECT CURRENT
EGC EQUIPMENT GROUNDING CONDUCTOR
(E) EXISTING
EMT ELECTRIC METALLIC TUBING
GALV GALVANIZED
GEC GROUNDING ELECTRODE CONDUCTOR
GND GROUND
HDG HOT DIPPED GALVANIZED
I CURRENT
Icont CONTINOUS CURRENT
Imp MAX POWER CURRENT
Isc SHORT CIRCUIT CURRENT
kVA KILOVOLT AMPERE
kW KILOWATT
LBW LOAD BEARING WALL
MAX MAXIMUM
MIN MINIMUM
N NEUTRAL
NEC NATIONAL ELECTRIC CODE
NTS NOT TO SCALE
(N) NEW
OC ON CENTER
PL PROPERTY LINE
POI POINT OF INTERCONNECTION
PTC PVUSA TEST CONDITIONS
PV PHOTOVOLTAIC
PVC POLYVINYL CHLORIDE
SCH SCHEDULE
SS STAINLESS STEEL
STC STANDARD TES CONDITIONS
TYP TYPICAL
UPS UNINTERRUPTIPLE POWER SUPPLY
V VOLT
Vmp MAX POWER VOLTAGE
Voc OPEN CIRCUIT VOLTAGE
W WATT
SHEET INDEX
PV01 COVER SHEET
PV02 SITE PLAN
PV03 ARRAY DETAILS
PV04 LINE DIAGRAM
PV05 ELECTRICAL CALCULATIONS
LBLS LABELS
DATA SHEETS ATTACHED
OPTIMIZER NOTES
1. SYSTEM IS UNGROUNDED
2. OUTPUT CHARACTERISTICS ARE INDEPENDENT OF TEMPERATURE
3. INVERTER INPUT VOLTAGE IS CONSTANT AT 350V
4. INVERTER INPUT CURRENT IS CALCULATED WITH OHMS LAW WITH VOLTAGE CONSTANT AT 350V AND POWER
FROM THE ARRAY'S Pstc
5. INVERTER INPUT CURRENT MAX IS 15A BASED ON OPTIMIZER TOPOLOGY
VICINITY 4.55 kW DC PV SYSTEMPRABHAKAR MANNE RESIDENCE20833 HANFORD DRIVECUPERTINO, CA 95014408-839-4074
(14) PV MODULESPANASONIC VBHN325SA16PV INVERTERSOLAREDGE SE 3800 H-USEVEREST EVERFLASHEVEREST 48S RAILPV01JOB #: 17031790DESIGN BY: RDELGADO DATE# REVISION 01/12/170 Original 3/24/17 A Plan Check #1 9/25/17 B Panel and Inverter change ----C --------D ---- COVER PAGE
SCOPE OF WORK
SLINGSHOT POWER IS TO INSTALL A ROOF MOUNTED
PV SOLAR ARRAY(S) INCLUDING A NEMA 14-50R
OUTLET FOR FUTURE EV CHARGING STATION.
CONTRACTOR ADDRESS
SLINGSHOT POWER
164 MAIN ST
LOS ALTOS, CA 94022
800.887.9414
CSLB #C-46 984488
AHJ: CITY OF FREMONT
UTILITY: PG&E
HOA: N/A
Abby Ayende
09/26/17
09/26/17
B-2017-1657
Abby Ayende
MP3
MP2
00 0
INV
AC
M
B
HANFORD DR
DRIVEWAY
FRONT OF THE HOUSE
EV
SITE PLAN4.55 kW DC PV SYSTEMPRABHAKAR MANNE RESIDENCE20833 HANFORD DRIVECUPERTINO, CA 95014408-839-4074
(14) PV MODULESPANASONIC VBHN325SA16PV INVERTERSOLAREDGE SE 3800 H-USEVEREST EVERFLASHEVEREST 48S RAILPV02JOB #: 17031790DESIGN BY: RDELGADO DATE# REVISION 01/12/170 Original 3/24/17 A Plan Check #1 9/25/17 B Panel and Inverter change ----C --------D ---- CONDUIT RUN ON THE ROOF IN
COMPLIANCE WITH 2016 CEC 690.31 & 2016
CRC R331.3 (EXACT RUN TBD AT INSTALL).
Scale: 3/32" = 1'
SITE PLANA
N
W
S
E
2014 NEC 690.12 RAPID SHUTDOWN COMPLIANT
Abby Ayende
09/26/17
MP3
MP2
00 0
INV
AC
M
B
6'
20'-10"
3ft FSB 18in FSB18in FSB27'-10"
EV
(E) 2x RAFTER
(E) DECKING
(N) 5/16" SS
LAG SCREW
2_1/2" EMBED. MIN
(N) EVEREST COMP
EVERFLASH
(N) L-FOOT
EVEREST
(N) SOLAR RAIL
EVEREST CR-48S
(N) SOLAR MODULE WITH
EVEREST CLAMPS
ARRAY DETAILS
Scale: 1/8" = 1'
ARRAY PLANA
Scale: NTS
ARRAY DETAILB
4.55 kW DC PV SYSTEMPRABHAKAR MANNE RESIDENCE20833 HANFORD DRIVECUPERTINO, CA 95014408-839-4074
(14) PV MODULESPANASONIC VBHN325SA16PV INVERTERSOLAREDGE SE 3800 H-USEVEREST EVERFLASHEVEREST 48S RAILPV03JOB #: 17031790DESIGN BY: RDELGADO DATE# REVISION 01/12/170 Original 3/24/17 A Plan Check #1 9/25/17 B Panel and Inverter change ----C --------D ---- PV METER
(N) INVERTER
STANDOFF / ROOF ANCHOR
LOCKED GATE
PVM
(N) SUB-PANEL
AC DISCO
INV
SP
AC
DC DISCODC
INTERIOR EQUIPMENT IS DASHED---
X
UNLOCKED GATE0
PV RAIL
INTERIOR CONDUIT
CONDUIT
(E) MAIN SERVICE PANELM
JUNCTION / COMBINER BOXB
LEGEND
MP2
ROOF PITCH: 4 : 12 ( 18 ° ) AZI: 180 °
MATERIAL: Comp Shingle STORY: 1
TOTAL: 6 MODULES 8 MOUNTS
MP3
ROOF PITCH: 4 : 12 ( 18 ° ) AZI: 270 °
MATERIAL: Comp Shingle STORY: 1
TOTAL: 8 MODULES 12 MOUNTS
A
PV06
B
PV06
(N) NEMA 14-50R WALL OUTLET
FOR FUTURE EV CHARGER
2014 NEC 690.12 RAPID SHUTDOWN COMPLIANT
Abby Ayende
09/26/17
EGC
DC-
DC+
N
L2
L1
EGC
GEC
AB C
N
G
(1) INVERTER
3800W, 240V, 99% EFF
SOLAREDGE SE3800H-US
2014 NEC 690.12 COMPLIANT
N
G
(1) AC DISCONNECT
30A, 240V, 2P, NEMA 3R
EATON DG221URB
M
240/120V
SINGLE PHASE
UTILITY SERVICE
(E) MAIN SERVICE
200A, 240/120V, 1ɸ, 3W
MURRAY
OVERHEAD SERVICE FEED
Meter No.: 1007368204
A B
(N) 20A/2P
(E) 200A/2P
(E) LOADS
+ -+ - + - + - 14 MODULE
STRING
(14) PV MODULES
325 W, 306.5 W PTC
PANASONIC VBHN325SA16
(14) PV OPTIMIZERS
400W, 15Amax, 80Vmax
SOLAREDGE P400
CEC-AC RATING: 3.248 kW
(2) #10 TYPE PV, (1) #6 BARE EGC N/A A
B
C
CONDUCTORS CONDUIT #
2'
LENGTH
DC: Vmax=500, Vmp=350, Imax=15, Imp=13
PROPERTIES
DC: Vmax=500, Vmp=350, Imax=15, Imp=133/4" EMT 50' (2) #10 THWN-2, (1) #8 EGC
NOTES
SEE ELECTRICAL NOTES AND OPTIMIZER NOTES ON PAGE 1
2014 NEC 690.12 RAPID SHUTDOWN COMPLIANT
(2) #10 THWN-2, (1) #10 N, (1) #8 EGC/GEC 3/4" EMT 5' AC: V=240, I=16
C
JUNCTION BOX(S)
NEMA 3R
(N) 50A/2P
TO (N) NEMA 14-50
RECEPTACLE FOR
FUTURE EV CHARGER
D
D (3) #8 THWN-2, (1) #8 EGC/GEC 3/4" EMT 5'
N G
LINE DIAGRAM4.55 kW DC PV SYSTEMPRABHAKAR MANNE RESIDENCE20833 HANFORD DRIVECUPERTINO, CA 95014408-839-4074
(14) PV MODULESPANASONIC VBHN325SA16PV INVERTERSOLAREDGE SE 3800 H-USEVEREST EVERFLASHEVEREST 48S RAILPV04JOB #: 17031790DESIGN BY: RDELGADO DATE# REVISION 01/12/170 Original 3/24/17 A Plan Check #1 9/25/17 B Panel and Inverter change ----C --------D ---- 120% RULE (MSP):
MAINS RATING = 200A
200A * 1.2 = 240 AMPS ALLOWABLE
TOTAL OF BREAKERS FEEDING BUS BAR = 220A
120% OF BUS NOT EXCEEDED (NEC 705.12(D)(2))
GEC BONDED DIRECTLY TO
(E) GROUNDING ELECTRODE.
ALL AVAILABLE ELECTRODES
SHOULD BE USED PER CEC 250.50 Abby Ayende
09/26/17
ELEC CALCS4.55 kW DC PV SYSTEMPRABHAKAR MANNE RESIDENCE20833 HANFORD DRIVECUPERTINO, CA 95014408-839-4074
(14) PV MODULESPANASONIC VBHN325SA16PV INVERTERSOLAREDGE SE 3800 H-USEVEREST EVERFLASHEVEREST 48S RAILPV05JOB #: 17031790DESIGN BY: RDELGADO DATE# REVISION 01/12/170 Original 3/24/17 A Plan Check #1 9/25/17 B Panel and Inverter change ----C --------D ---- Abby Ayende
09/26/17
9'-3"7'-10"
18°
3' FIRE SETBACK MIN
2X6 @ 24 O.C.
2X6 PURLING;
SUPPORTS @ 6' O.C.
8' 10'-9"
3' FIRE SETBACK MIN
18°
2X6 @ 24 O.C.
2X6 PURLING;
SUPPORTS @ 6' O.C.
ARRAY DETAILS
Scale: NTS
MP3 SECTIONB 4.55 kW DC PV SYSTEMPRABHAKAR MANNE RESIDENCE20833 HANFORD DRIVECUPERTINO, CA 95014408-839-4074
(14) PV MODULESPANASONIC VBHN325SA16PV INVERTERSOLAREDGE SE 3800 H-USEVEREST EVERFLASHEVEREST 48S RAILPV06JOB #: 17031790DESIGN BY: RDELGADO DATE# REVISION 01/12/170 Original 3/24/17 A Plan Check #1 9/25/17 B Panel and Inverter change ----C --------D ---- Scale: NTS
MP2 SECTIONA
Abby Ayende
09/26/17
LABELS
REQ. BY NEC 690.17
APPLY TO:
DISCONNECTS
PV LOAD CENTERS
COMBINER BOXES
1
PHOTOVOLTAIC POWER SOURCE
REQ. BY NEC 690.31 (E)(3)
APPLY TO:
EXPOSED RACEWAYS, CABLE TRAYS COVERS
OR ENCLOSURES OF JUNCTION BOXES
11
THIS ELECTRIC SERVICE IS
ALSO SERVED BY A
PHOTOVOLTAIC SYSTEM
REQ. BY NEC 705.1 2(D)(4) APPLY TO:
MAIN SERVICE PANEL 8
WARNING
INVERTER OUTPUT CONNECTION.
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
690.64(B)(7)-705.12(D)(7)
REQ. BY NEC 705.12 (D)(7) APPLY TO:
PV SYSTEM BREAKER 6
SOLAR AC DISCONNECT
REQ. BY 690.13 (B)
APPLY TO:
AC DISCONNECT
7
SOLAR DC DISCONNECT
REQ. BY 690.13 (B)
APPLY TO:
DC DISCONNECT
10
WARNING
ELECTRIC SHOCK HAZARD IF A GROUND
FAULT IS INDICATED.
NORMALLY GROUNDED CONDUCTORS
MAY BE UNGROUNDED AND ENERGIZED!
690.5(c)
REQ. BY NEC 690.5 (C) APPLY TO:
INVERTER 4
PV SYSTEM AC DISCONNECT
RATED AC OUTPUT CURRENT - ____ AMPS
AC NORMAL OPERATING VOLTAGE - 240 VOLTS
690.15, 690.54
REQ. BY NEC 690.54 APPLY TO:
PV SYSTEM DISCONNECT 5
PV SYSTEM DC DISCONNECT
RATED MAX POWER POINT CURRENT - ____ ADC
RATED MAX POWER POINT VOLTAGE - _____ VDC
MAXIMUM SYSTEM VOLTAGE - _____ VDC
SHORT CIRCUIT CURRENT - _____ ADC
690.14(C)(2), 690.15, 690.53
REQ. BY NEC 690.53 APPLY TO:
INVERTER 3
WARNING
DUAL POWER SOURCES
SECOND SOURCE IS PHOTOVOLTAIC SYSTEM
THE SECOND POWER SOURCE IS LOCATED ON
WALL NEXT TO SUBPANEL
RATED AC OUTPUT CURRENT - ____ AMPS
AC NOMINAL OPERATING VOLTAGE - 240 VOLTS
690.54 - 705.10
REQ. BY NEC 690.54
APPLY TO:
MAIN SERVICE PANEL
2
WARNING: PHOTOVOLTAIC
POWER SOURCE
REQ. BY CRC R331.7 APPLY TO:
MAIN SERVICE DISCONNECTS 9
SIGNAGE REQUIREMENTS:
1. RED BACKGROUND
2. WHITE LETTERING
3. MIN. 3/8" LETTER HEIGHT
4. ALL CAPITAL LETTERS
5. ARIAL OR SIMILAR FONT
6. WEATHER RESISTANT MATERIAL, PER UL
969
WARNING - ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION
690.17
PHOTOVOLTAIC SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
REQ. BY NEC 690.56(C) AND 690.12
APPLY TO: INVERTERS 9
LABELS4.55 kW DC PV SYSTEMPRABHAKAR MANNE RESIDENCE20833 HANFORD DRIVECUPERTINO, CA 95014408-839-4074
(14) PV MODULESPANASONIC VBHN325SA16PV INVERTERSOLAREDGE SE 3800 H-USEVEREST EVERFLASHEVEREST 48S RAILLBLSJOB #: 17031790DESIGN BY: RDELGADO DATE# REVISION 01/12/170 Original 3/24/17 A Plan Check #1 9/25/17 B Panel and Inverter change ----C --------D ---- Abby Ayende
09/26/17
Abby Ayende
09/26/17
Abby Ayende
09/26/17
Abby Ayende
09/26/17
Abby Ayende
09/26/17
Abby Ayende
09/26/17
Abby Ayende
09/26/17
MP3
MP2
00 0
INV
AC
PRABHAKAR MANNE
20833 HANFORD DRIVE
17031790
LAYOUT MAP - INSTALL CREW PAGE
INVERTER SERIAL No.:
----------------------------------------------------------------------------------------------
Abby Ayende
09/26/17