B-2017-1816 CITY OF CUPERTINO BUILDING PERMIT -
BUILDING ADDRESS: CONTRACTOR: PERMIT NO:B-2017-1816
10285 COLBY AVE CUPERTINO,CA 95014-2421(316 29 028) HIGHLIGHT SOLAR
INC A CALIFORNIA
CORPORATION
SAN JOSE,CA 95117 .
OWNER'S NAME: MUKHERJEE DEBANJANAND DEEPANJANATRUSTEE DATE ISSUED: 10/24/2017
•
OWNER'S PHONE:408-802-2103 PHONE NO:(408)489-9273
LICENSED CONTRACTOR'S DECLARATION BUILDING PERMIT INFO:
License Class C-46 Lic.#960376
Contractor HIGHLIGHT SOLAR INC A CALIFORNIA CORPORATION Date X BLDG _ELECT _PLUMB
• 04/30/2019 _MECH X RESIDENTIAL_COMMERCIAL
•
I hereby affirm that I am licensed under-the provisions of Chapter 9(commencing
with Section 7000)of Division 3 of the Business&Professions Code and that my JOB DESCRIPTION:
license is in full force and effect.' (N) 13 PANEL ROOF MOUNTED PV SYSTEM(4.29 KW)
I hereby affirm under penalty of perjury one of the following two declarations: '
1. I have and will maintain a certificate of consent to self-insure for Worker's
Compensation,as provided for by Section 3700 of the Labor Code,for the
performance,of the work for which this permit is issued.
ti
00010.I have and will maintain Worker's Compensation Insurance,as provided for by '
Section 3700 of the Labor Code,for the performance of the work for which this Sq.Ft Floor Area: Valuation:$14520.00
permit is issued.
APPLICANT CERTIFICATION
I certify that I have read this application and state that the above APN Number: Occupancy Type: _
information is correct.I agree to comply with all city and county ordinances 316 29 028 ,
and state laws relating to building construction,and hereby authorize
representatives of this city to enter,upon the above mentioned property for , ;'
inspection purposes. (We)agree to save indemnify and keep harmless the PERMIT EXPIRES IF WORK IS NOT STARTED
City of Cupertino against liabilities,judgments,costs,and expenses which WITHIN 180 DAYS OF PERMIT ISSUANCE OR
may accrue against said City in consequence of the granting of this permit. -
Additionally,the applicant understands and will comply with all non-point 180 DAYS FROM LAST CALLED INSPECTION.
source regulatio s per the Cupertino Municipal Code,Section 9.18. ' 'I
�-' Issued by:Abby Ayende
� •
ture Date 10/24/2017 Date: 10/24/2017
OWNER-BUILDER DECLARATION RE-ROOFS:
I hereby affirm that I am exempt from the Contractor's License Law for one of the All roofs shall be inspected prior to any roofing material being installed.If a roof is
following two reasons: installed without first obtaining an inspection,I agree to remove all new materials for
1. I,as owner of the property,or my employees with wages as their sole inspection.'
compensation,will do the work,and the structure is not intended or offered.for
sale(Sec.7044,Business&Professions Code) • Signature of Applicant: .
2. I,as owner of the property,'am exclusively contracting with licensed Date: 10/24/2017 , 1
contractors to construct the,project(Sec.7044,Business&Professions Code). . ,
I hereby affirm under penalty of perjury one of the following three declarations: ALL ROOF COVERINGS TO BE CLASS"A"OR BETTER
1. I have and will maintain a Certificate of Consent to self-insure for Worker's
Compensation,as provided:forby Section 3700 of the Labor Code,for the HAZARDOUS MATERIALS DISCLOSURE
performance of the work fo'r which this permit is issued. I have read the hazardous materials requiridnments under Chapter 6.95 of the
2. I have and will maintain Worker's Compensation Insurance,as provided for by California Health&Safety Code,Sections 25505,25533,and 25534. I will
Section 3700 of the,Labor Code,for the performance of the work for which this maintain compliance with the Cupertino Municipal Code,Chapter 9.12 and the
permit is issued. Health&Safety Code,Section 25532(a)should I store or handle hazardous •
3. I certify that in the performance of the work for which this permit is issued,I
material. Additionally,should I use equipmetip'or devices which emit hazardous
shall not employ any person in any manner so as to become subject to the air contaminants as defined by the Bay l it Quality Management District I
will maintain compliance with the Cupertino tino Municipal Code,Chapter 9.12 and
Worker's Compensation laws of California. If,after making this certificate of the Health&Safety Code, ctions 25505,25533,and 25534.
exemption,I become subject to the Worker's Compensation provisions of the 1 '1
Labor Code,I must'forthwith comply with such provisions or this permit shall i,
'I
._r or authorized agent:
be deemed revoked. a e: 0/24/2017 I i'
• APPLICANT CERTIFICATION CONSTRUCTIO ENDING AGENCY
I certify that I have read this application and state that the above information is , I hereby affirm that there is a construction'lending agency for the performance
correct.I agree to comply with all city and county ordinances and state laws of work's for which this permit is issued'(Sec 3097,Civ C.)
relating to building construction,and hereby authorize representatives of this city Lender's Name i
to enter upon the above mentioned property for inspection purposes. (We)agree
to save indemnify and keep harmless the City of Cupertino against liabilities, Lender's Address .
judgments,costs,and expenses which may accrue against said City in
consequence of the granting of this permit. Additionally,the applicant understands ARCHITECT'S DECLARATION
and will comply with all non-point source regulations per the Cupertino Municipal I understand my plans shall be used as public,records.
Code,Section 9.18.
Licensed
Signature Date 10/24/2017 Professional
\\' ./ ALTERNATIVE ENERGY PERMIT APPLICATION AE
ri.: COMMUNITY DEVELOPMENT DEPARTMENT•BUILDING DIVISION
e.,,s, 10300 TORRE AVENUE•CUPERTINO,CA 95014-3255
(408)777-3228•FAX(408)777-3333•buildinq(a'�.cupertino.orq
CUPERTINO b-Zofl- rke
PROJECT ADDRESS 0 2 g5 col_
IA J _ APN# �1 r-^2.9-025
OWNER NAMI~�.P�2v\6-Zin —k`' ' PHONE /� .0;12,2�Q� EI Ole CtAI al_„• e r 4';0. 1
.^ Co STREET ADDRESS ^ 5i ' CITY,STATE,ZIP FAX
/
CONTACT NAME^ ev1 PHON$ 0Z 8.1 ci��s E ms!1 t1 p i %),,1 NAVs.Acx,
%),,1NVsqcr' c..
STREET ADDRESS .b52-f PC.r �2h A AVL CITY,STATE,ZIP�a� �� 0 FAX
o OWNER 0 OWNER-BUILDER 0,OWNER AGENT 0 CONTRACTOR 0 CONTRACTOR AGENT 0 ARCHITECT 0 ENGINEER 0 DEVELOPER 0 TENANT
CONTRACTOR NAME T e N'��I�\ LICENSE NUMB�/R��O �� LICENSE TYPE BUS.LIC#
COMPANY NAME (1Jl E-MAIL I I �` —1 FAX
11�,\fiSatc:, _III L rL relv,v bl- .L.
STREET ADDRESS CITY STATE PHONE
5 LI ' e• .,Na(A0 b0-la- CA cla ' '8 4'2)992
ARCHITECT/ENGINEER NAME LICENSE NUMBER , ( BUS.LIC#
COMPANY NAME E-MAIL FAX
STREET ADDRESS CITY,STATE,ZIP PHONE
USE OF cFD or Duplex 0`'Multi-Family PROJECT IN WILDLAND PROJECT IN ,
STRUCTURE: 0 Commercial URBAN INTERFACE AREA 0 Yes 0 No FLOOD ZONE ❑ Yes 0 No
SOLAR PANELS 0 ELECTRIC VEHICLE CHARGING STATION
0 SOLAR WATER HEATING 0 OTHER:
FOR SOLAR PANELS: NUMBER OF PANELS/UNITS: t KILOWATTS(COMMERCIAL ONLY): /. ,Z Ll' TOTAL VALUATION: /- 5 2'` 0-e,`7 /
-1.
DESCRIPTION OF WORKICD\Ctr Y rC l....1 —1...,„S re.,N\--i
•
• RECEIVED BY: " "}� �
- "V• �."+
Bymysignature below,I certify to each of the following: I am the property owner or authorized agent to act on the roe owner'sbeh lf. I ha read this
gfY g P P Y g property rtY
application and the information I have pr vided is correct. I have read'the Description of Work and verify it is accurate. I agree to comply with all applicable local
ordinances and state laws relating to buil 'ng construction. I authorize representatives of Cupertino to enter the d//above-identified p;opertyyffor inspection purposes.
' Signature of Applicant/Agent: Date: 1 f„29/// /7
SUPPL _ NTAL INFORMATION'REQUIRED OFFICE USE.ONLY
�,,A h\/\ W 0 OVER-THE COUNTER
('" ,q\*'"1 V U/ ❑ EXPRESS
\J
V ..
❑ STANDARD
•
❑ I ARGE,
e
0 MAJOR '
PVApp_2011.doc revised 03/16/11
s
SMOKE / CARBON MONOXIDE ALARMS
OWNER CERTIFICATE OF COMPLIANCE
COMMUNITY DEVELOPMENT DEPARTMENT • BUILDING DIVISION
10300 TORRE AVENUE • CUPERTINO, CA 95014-3255
(408) 777-3228 • FAX (408) 777-3333 • building(a)-cupertino.org
PERNIIT CA",OT BE�NALED :UNTIL THIS CERTIFICATE HAS ,BEEN:
CUMPLET'1ED; 94QaD_: AND RETURNED. TO TE,[E BUHbINQ I MSI0N
PURPOSE
This affidavit is a self -certification for the installation of all required Smoke and Carbon Monoxide Alarms for
compliance with 2016 CRC Section R314, R315, 2016 CSC Sections 420 6 and 907.2.11.2 where no interior access
for inspections are required.
GENERAL INFORMATION
Existing single-family and multi -family dwellings shall be provided with Smoke Alarms and Carbon
Monoxide alarms. When the valuation of additions, alterations, or repairs to existing dwelling units exceeds
$1000 00, CRC Section R314, R315, and CBC Sections 907.2.11.5 and 420 6 require that Smoke Alarms and/or
Carbon Monoxide Alarms be installed in the following locations.
AREA
SMOKE ALARM
CO ALARM
Outside of each separate sleeping area in the immediate vicinity of the
bedroom(s) - (Smoke alarms shall not be located within 3 feet of bathroom door)
X
X
On every level of a dwelling unit including basements and habitable attics
X
X
Within each sleeping room
X
Carbon Monoxide alarms are not required in dwellings which do not contain fuel -burning appliances and that
do not have an attached garage. Carbon monoxide alarms combined with smoke alarms shall comply with
CBC Section 420 6 and shall be approved by the Office of the State Fire Marshal.
Power Supply In dwelling units with no commercial power supply, alarm(s) may be solely battery operated.
In existing dwelling units, alarms are permitted to be solely battery operated where repairs or alterations do
not result in the removal of wall and ceiling finishes or there is no access by means of attic, basement or crawl
space. Refer to CRC Section R314 and CBC Sections 907.2.11 4 and 420.6.2. An electrical permit is required for
alarms which must be connected to the building wiring.
As owner of the above -referenced property, I hereby certify that the alarm(s) referenced above has/have been
installed m accordance with the manufacturer's instructions and in compliance with the California Building
and California Residential Codes. The alarms specified below have been tested and are operational, as of the
date signed below
Address ),,0')_0 -) C a Q V_(
Specify Number of Alarms
# Smoke Alarms
Permit No. R_ W 1'3-~iW
# Carbon Monoxide Detectors.
t have read and agree to comply with the terms and conditions of this statement
Agent's) Name:
O ner�(or Owner Ag
�
�f Y
tA,-i
Signature ... .. Date: .. ..
Contractor
ttNam .
r
Si nature Lic.# "(. .l. Date:
Smoke and COforin.doc revised 0111012017
VICINITY MAP
SCALE: NTS
SATELLITE VIEW
SCALE: NTS
PHOTOVOLTAIC SYSTEM SUMMARY
SYSTEM SIZE: DC STC: 4.29 KW
SYSTEM SIZE: AC CEC: 3.94 KW
SOLAR MODULES: (13) LG330N1C-A5
INVERTER: (1) SOLAR EDGE SE3800H-US
MOUNTING SYSTEM: IRONRIDGE ROOF MOUNT
ELECTRICAL INFORMATION:
EXISTING
MAIN SERVICE PANEL BUS SIZE: 125A
MAIN SERVICE BREAKER SIZE: 125A
BUILDING INFORMATION:
ONE STORY HOUSE
CONSTRUCTION TYPE: V-B
OCCUPANCY: R
ROOF: COMP. SHINGLE
TRUSSES: 2"x4" @ 24" O.C.
Highlight Solar Inc.
Address:
1624 Remuda Lane,
San Jose, CA 95112
Phone Number:
(866) 926-9997
Lic# 960376
Class C-46
INSTALLERSHEET INDEX
ADDRESS: 10285 Colby Ave, Cupertino, CA 95014
PROJECT NAME: Debanjan Mukherjee
STREET VIEW
SCALE: NTS
THE INSTALLATION OF SOLAR ARRAYS AND PHOTOVOLTAIC POWER
SYSTEMS SHALL BE IN ACCORDANCE WITH THE MOST RECENT CPC, CMC,
2016 CEC, 2016 CRC, 2016 CBC AND 2016 NEC. AS AMMENDED BY THE LOCAL
AHJ. STRUCTUAL CONNECTIONS SHALL BE TO 2016 IBC.
GENERAL NOTES
1. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED BY
REC OG N I ZED E L E CT R IC A L T E ST IN G L A B O R A TO RY
CUSTOM MADE EQUIPMENT SHALL HAVE COMPLETE TEST DATA
SUBMITTED BY THE MANUFACTURER ATTESTING TO ITS SAFETY
2. OUTDOOR EQUIPMENT SHALL BE AT LEAST NEMA 3R RATED
3. ALL METALLIC EQUIPMENT SHALL BE GROUNDED
4. ALL SPECIFIC WIRING IS BASED ON THE USE OF COPPER.
5. CONTRACTOR SHALL OBTAIN ELECTRICAL PERMITS PRIOR TO
INSTALLATION AND SHALL COORDINATE ALL INSPECTIONS, TESTING
COMMISSIONING AND ACCEPTANCE WITH THE CLIENT,
U T I L I T Y C O . A N D C I T Y I N S P E C T O R S A S N E E D E D .
6. THE ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT
LOCATIONS OF SERVICE POINTS AND SERVICE SIZES WITH THE
SERVING UTILITY COMPANY AND COMPLY WITH ALL UTILITY
COMPANIES REQUIREMENTS. IF THE SOLAR BACK FED BREAKER IS
OVER THE BUS SIZE 20% LIMIT, CONTRACTOR SHALL INCLUDE THE
COST TO REPLACE MAIN BREAKER OR ENLARGE MAIN CAPACITY.
7. DRAWINGS ARE DIAGRAMMATIC ONLY, ROUTING OF RACEWAYS
SHALL BE OPTION OF THE CONTRACTOR UNLESS OTHERWISE
NOTED AND SHALL BE COORDINATED WITH OTHER TRADES.
8. IF THE ROOF MATERIAL OR ROOF STRUCTURE NOT ADEQUATE
FOR PV INSTALLATION, CALL ENGINEER PRIOR TO INSTALL. THE
CONTRACTOR IS RESPONSIBLE TO VERIFY THAT THE ROOF IS
C A P A B L E O F W I T H S T A N D I N G T H E E X T R A W E I G H T .
9. IF THE DISTANCES FOR CABLE RUNS ARE DIFFERENT THAN
SHOWN, THE CONTRACTOR SHALL NOTIFY THE ELECTRICAL
ENGINEER TO VALIDATE THE WIRE SIZE. FINAL DRAWINGS
WILL BE RED-LINED AND UPDATED AS APPROPRIATE.
10. WHENEVER A DISCREPANCY IN QUALITY OF EQUIPMENT ARISES ON THE
DRAWING OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE
FOR PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED
BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS TO ENSURE COMPLETE COMPLIANCE AND LONGEVITY OF
THE OPERABLE SYSTEM REQUIRED BY THE ARCHITECT/ENGINEERS.
11. ALL BROCHURES, OPERATION MANUALS, CATALOGS, SHOP
DRAWINGS, ETC. SHALL BE HANDED OVER TO OWNER'S
REPRESENTATIVE AT THE COMPLETION OF WORK
PHOTOVOLTAIC NOTES:
1. ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES
SHALL BE TESTED, LISTED AND IDENTIFIED UL 1703.
2. SOLAR SYSTEM SHALL NOT COVER ANY PLUMBING OR MECHANICAL
VENTS
3. MODULES AND SUPPORT STRUCTURES SHALL BE GROUNDED.
5. REMOVAL OF AN INTERACTIVE INVERTER OR OTHER EQUIPMENT
SHALL NOT DISCONNECT THE BONDING CONNECTION BETWEEN THE
GROUNDING ELECTRODE CONDUCTOR AND THE PHOTOVOLTAIC
SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTORS.
4. SOLAR INVERTER MUST HAVE A MANUFACTURE
INSTALLED DISCONNECTING MEANS THAT PREVENTS
PARALLEL FEEDING UTILITY LINES DURING POWER OUTAGE.
6. ALL PV MODULES AND ASSOCIATED EQUIPMENT AND
WIRING SHALL BE PROTECTED FROM ANY PHYSICAL
DAMAGE.
7. LIVE PARTS OF PV SOURCE CIRCUITS AND PV OUTPUT
CIRCUITS OVER 150V TO GROUND SHALL NOT BE
ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS WHILE
ENERGIZED.
8. INVERTER IS EQUIPED W/ INTEGRATED GFDI, THUS
PROVIDING GROUND FAULT PROTECTION
9. ALL CONDUCTORS SHALL BE COPPER AND 90 DEG RATED
10. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY A
RECOGNIZED ELECTRICAL TESTING LABORATORY OR
APPROVED BY THE DEPARTMENT.
11. CONDUITS SHOULD BE PAINTED TO MATCH EXISTING
ROOF AND WALL COLORS
12. ALL WORK SHALL BE IN ACCORD WITH THE 2016 CBC, 2016
CEC AND 2016 NEC WITH SPECIAL EMPHASIS ON ARTICLE 690
13. THE OUTPUT OF A UTILITY INTERACTIVE-INVERTER SHALL
BE PERMITTED TO BE CONNECTED TO THE SUPPLY SIDE OF
THE SERVICE DISCONNECTING
MEANS AS PER 230.82(6)
14. A SINGLE CONDUCTOR SHALL BE PERMITTED TO BE USED
TO PERFORM THE MULTIPLE FUNCTIONS OF DC GROUNDING,
AC GROUNDING
AND BONDING BETWEEN AC AND DC SYSTEMS AS PER NEC
690.47(C) AND SIZED AS PER SEC 250.166
15. EQUIPMENT GROUND CONDUCTOR REQUIRED IN
RACEWAYS SIZED PER CEC 250-166.
16. PER ART 250.92. NON-CURRENT CARRYING METAL PARTS
OF EQUIPMENT SHALL BE EFFECTIVELY BONDED TOGETHER.
BOND BOTH ENDS OF RACEWAYS
ROOF PLAN
SINGLE LINE DIAGRAM
RACKING DATA SHEET
ATTACHMENT LAYOUT
CODE REQUIRED SIGNAGE
INVERTER DATA SHEET
P 1
MODULE DATA SHEET
MODULE & RACK CERTIFICATION
RACKING SPECS
ATTACHMENT DATA SHEET
OPTIMIZER DATA SHEET
DESIGNER NAME:
NAREK A.
DATE:
20 OCTOBER, 2017
SITE PLAN
C 1 COVER SHEET
P 2
P 3
P 4
P 5
P 6
P 7
P 8
P 9
P 10
P 11
P 12
C1
Abby Ayende
10/24/17
10/24/17
B-2017-1816
Abby Ayende
1
ROOF PLAN
Drawn By : Narek A.
CONTRACTOR
N
0°
S
180°
E
90°
W
270°
X
20 OCTOBER, 2017
10285 Colby Ave,
Cupertino, CA 95014
Debanjan Mukherjee
Lic# 960376
Highlight Solar Inc.
Address:
1624 Remuda Lane,
San Jose,
CA 95112
Phone Number:
(866) 926-9997
PV SYSTEM
AS INDICATED
PHOTOVOLTAIC ARRAY
(13) LG Electronics 330 W Solar Modules (LG330N1C-A5)
(1) Solar Edge 3.8 Kw Inverter (SE3800H-US)
(13) Solar Edge P400 Power Optimizers
EMT Type Conduit
MSP (E) 125A Main Service Panel
Solar Module
J/B (N) Junction Box
UNIT INDEX
Power Optimizer
MATERIAL LIST TABLE
Module : 13 x LG330N1C-A5
Optimizer : 13 x P400 Power Optimizers
Inverter : 1 x SE3800H-US
Rails : 7 x 168" Iron Ridge Rails
Attachment :x 26 Dual Jack Standoff
Ground Lug :x 4 Ironridge UFO Ground Lugs
End Clamp :x 8 Ironridge UFO End Clamps
Mid Clamp :x 22 Ironridge UFO Mid Clamps
Channel Strut: 13
Monitoring Gateway: x 1
INV (N) Solar Edge 3.8 KW Inverter
SCALE
0 5 10 ft1
FROM JUNCTION BOX TO ROOF EAVE EMT TYPE CONDUIT WILL RUN OVER
THE ROOF AT 1 1/2" HEIGHT, THEN UNDER THE EAVE TO PV EQUIPMENT
Note: This installation will provide verification at
time of inspectionthat 2016 CRC sections 314/315
(smoke and CO detectors) are in compliance.
1.UFO GROUNDING MID CLUMP
2.UFO END CLAMP
3.IRONRIDGE RAIL
4.UFO GROUND LUG
5.ONE LUG BETWEEN TWO SPLICES OF RAILS
6.ONE LUG AT THE END OF THE RAIL TO GO TO THE J-BOX
7. #6 BARE COPPER EGC
8.PV MODULES GROUNDING AND CLAMPING DETAIL
UL 2703 AND UL467 CERTIFIED
1
2
4
5
7
8 Colby Ave3' fire setback
3' fire setback
3' fire setback 3' fire setback1
8'' fire s
e
tb
a
c
k
18'' fire setbackMSP
INVJ/B
Solar Array
13 LG 330W Modules
13 P320 Optimizers
Pitch: 18 Deg
Orientation: 270 Deg
Abby Ayende
10/24/17
NEW SPLIT PHASE: 3W, 120/240V
BUSBAR RATING = 125A
MAIN SERVICE BREAKER = 125A END FEED
120% RULE:
MAX ALLOWED FEED: 150A
ACTUAL FEED:
125A "MSP" + 20A "SOLAR" = 145 A <= 150A MAX
MAIN PANEL RATING
All the photovoltaic systems wires that on the roof and
side of the building shall be protected against physical damage
2
SINGLE LINE
DIAGRAM
CONTRACTOR
X
20 OCTOBER, 2017
10285 Colby Ave,
Cupertino, CA 95014
Debanjan Mukherjee
Lic# 960376
Highlight Solar Inc.
Address:
1624 Remuda Lane,
San Jose,
CA 95112
Phone Number:
(866) 926-9997
PV SYSTEM
AS INDICATED
OUTPUT CALCULATIONS
PV ARRAY INFORMATION
PV MODULE RATINGS # STC
INVERTER RATING
13 LG ELECTRONICS 330WATT SOLAR MODULES
MODEL # LG330N1C-A5
1 SOLAR EDGE 3.8 KW INVERTER
MODEL # SE3800H-US
NUMBER OF STRINGS PER INVERTER: 1
NUMBER OF SERIES PER STRING: 13
MAX DC WATTAGE: 13 * 330W = 4,290W <= 5,700W
MAX DC VOLTAGE: 380V
EXISTING GROUND ROD
MAIN METER
UTILITY
EXISTING
125A MAIN
SERVICE PANEL
120/240V
1-PHASE, 3-WIRE
INSTALL 2P
20A CB(PV)
AT OPPOSITE END
OF BUS FROM
MAIN FEEDER CB
125A BUS125A END
FEED MAIN C/B
[DC.1] [DC.2][AC]
3/4" EMT
CONDUIT
2 FEET
#6 AWG EGC
COPPER WIRE
RAIL GROUNDING MID CLAMP
GROUNDING LUG
[ DC.1 ] FROM PV MODULES TO J-BOX
(2) #10 AWG PV WIRE + (1) #6 AWG BARE CU EGC
FREE IN THE AIR, 3/4" EMT TYPE CONDUIT BETWEEN PV ARRAYS
3/4" EMT
CONDUIT
30 FEET
Drawn By : Narek A.
SolarEdge Power Optimizer
P400
Rated DC Input Power - 400 watts
Maximum Input Voltage - 84 Vdc
MPPT Range - 8 to 84 Vdc
Maximum Input Current - 12.5 Adc
Maximum Output Current - 15 Adc
String Limitations - 8 to 25 Optimizers,
5700 watts STC per string maximum
NOTE:
Grounding specs:Ironridge has a UL1703 Listed integrated grounding.
No additional ground lugs and copper wire are needed
(See integrated grounding spec sheet on page #11)
The system is Rapid shut down ready by CEC 690.12
PV SYSTEM MAX DC OUTPUT:
13 * 330W = 4,290W
PV SYSTEM MAX AC OUTPUT:
(13) LG ELECTRONICS LG330N1C-A5
(1) SOLAR EDGE SE3800H-US
Pmax (PTC Rating) PER MODULE: 306.3W
306.3W * 13 = 3.98 KW
3.98 KW * 99.0% CEC INVERTER = 3.94 KW
PHOTOVOLTAIC ARRAY
1 STRING OF 13 MODULES
13 LG ELECTRONICS
330WATT MODULES,
13 P400 POWER
OPTIMIZERS
1 2 ... 13
JBOX
NEMA 3R
6" BY 6"
PEAK PWR TRACKING VOLTAGE = 380 V
CEC EFFICIENCY = 99.0 %
ENCLOSURE : NEMA 3R
MAXIMUM INPUT CURRENT = 10.5 A
MAXIMUM OUTPUT CURRENT = 16.0 A
MAXIMUM INPUT POWER = 5900 W
MAXIMUM OUTPUT POWER = 3800 W
SOLAR EDGE
3.8KW INVERTER
MODEL# SE3800H-US
WITH INTEGRATED RAPID SHUTDOWN
Max Input Voltage: 480V
[ DC.2 ] FROM J-BOX TO INVERTER
(2) #10 AWG THWN-2 + (1) #8 AWG CU EGC
3/4" EMT TYPE CONDUIT
MAXIMUM CURRENT : 13 * 330W / 380V = 11.3A
CONSIDERS CONTINUOUS: 11.3A * 1.25 = 14.1 A
SHORT CIRCUIT CURRENT: 14.1 A * 1.25 = 17.6A
RACEWAY HEIGHT FROM ROOF 1 1
2'' (TEMP - 39 + 22 = 61C)
TEMP. DERATE FACTOR - 197.6 A / 0.58 = 30.4A
WIRE SIZE FROM NEC TABLE 310.15(b)16 - 10 AWG
AMBIENT TEM FACTOR 0.58 PER NEC 310.15(b)(2)(a)
[ AC ] FROM INVERTER TO MAIN SERVICE PANEL
(3)#10 AWG THWN-2 + (1) #8 AWG CU EGC
3/4" EMT CONDUIT
MAXIMUM INVERTER OUTPUT CURRENT : 16.0 A
CONSIDERS CONTINUOUS: 16.0A * 1.25 = 20.0 A
TEMPERATURE ADJUSTMENT - 20.0 A / 0.91 = 21.97A
CONDUCTOR SIZE FROM NEC TABLE 310.16 - 10 AWG
SHORT CIRCUIT CURRENT I-SC = 10.45A
MAXIMUM POWER CURRENT I-MP = 9.80A
OPEN CIRCUIT VOLTAGE V-OC = 40.9V
MAXIMUM POWER VOLTAGE V-MP = 33.7V
Abby Ayende
10/24/17
CAUTION
Permanent directory or plaque providing location of
service disconnecting means and photovoltaic system
disconnecting means, if not located at the same location.
(Plaques shall be metal or plastic, with engraved or machine
printed letters, or electro-photo plating, in a contrasting color to
the plaque. Plaques shall be permanently attached to the
equipmenq or in the required location using an approved
method that is suitable to withstand the environment to which it
is exposed. Plaques and signage shall meet legibility,
defacemet, exposure and adhesion requirements of
Underwriters Laboratories marking and labeling system
969(UL969).
Plaques will have red background & white lettering.
1
2
(STICKER TO BE LOCATED ON
CONDUIT WITH DC CURRENT
EVERY 4' HORIZONTALLY OR
10' VERTICALLY AND 1' FROM
EACH SIDE OF A BEND)
3
4
WARNING!
ELECTRIC SHOCK HAZARD.
DO NOT TOUCH THE TERMINALS.
TERMINALS ON BOTH THE LINE AND
LOAD SIDES MAY BE ENERGIZED IN
THE OPEN POSITION.
5
(TO BE LOCATED ON
SUB-PANEL ONLY
WHEN SUB-PANEL IS
DEDICATED FOR PV ONLY)
6
7
8 THIS PANEL FED BY
MULTIPLE SOURCES
(UTILITY & SOLAR)
9 SOLAR
(STICKER LOCATED
INSIDE PANEL
NEXT TO SOLAR BREAKER)
WARNING
INVERTER OUTPUT CONNECTION. DO NOT
RELOCATE THIS OVERCURRENT DEVICE10
(STICKER LOCATED
INSIDE PANEL
BELOW PV BREAKER)
PV ARRAY
J BOX
INVERTER
INTEGRATED
DC DISCONNECT
PV SUB-PANEL
* if applicable
SUB-PANEL
* if applicable
AC
DISCONNECT
* if applicable
METER
MAIN SERVICE
PANEL
2
1
3
4 5
6
7
9
8
10
7
9
8
10
7
7
9
8
10
MARKINGS, LABELS AND WIRING SIGNS
A. Purpose: Provide emergency responders with appropriate warning and
guidance with respect to isolating solar electric system.
This can facilitate identifying energized electrical lines that connect solar panels
to the inverter, as these should not be cut when venting for smoke removal
B. Main Service Disconnect.
1. Residential buildings - The marking main be placed within the main service
disconnect. The marking shall be placed
outside cover if the main service disconnect is operable with the service panel
closed.
2. Commercial buildings - Tha marking shall be placed adjacent to the main
service disconnect clearly visible from the location where the level is operated
3. Markings: Verbiage, Format and Type of Material.
a. Verbiage: CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED
b. Format: White lettering on a red background. Minimum 3/8 inches letter
height. All letters shall be capitalized. Arial or similar font, non bold.
c. Material: Reflective, weather resistant material suitable for the environment
(use UL - 969 as standard for weather rating). Durable adhesive materials meet
this requirement.
C.Marking Requirements on DC conduit, raceways, enclosures, cable
assemblies, DC combiners and junction boxes:
1. Markings: Verbiage, Format and Type of Material.
a. Placement : Markings shall be placed every 10 feet on all interior and exterior
DC conduits, raceways, enclosures, and cable assemblies,
at turns, above and for below penetrations, all DC combiners and junction boxes
b. Verbiage: CAUTION: SOLAR CIRCUIT Note: The format and type of material
shall adhere to "V. V-3b, c" of this requirement.
c. Inverters are not required to have caution markings
1.Marking is required on all interior and exterior DC conduit
raceways,enclosures,cable assemblies,and junction boxes,combiner boxes and
disconnects.CFC 605.11.1
2.The materials used for marking shall be reflective,weather resistant material
suitable for the environment.
Minimum 3/8 "letter height; all upper case letters Arial or similar font; Red
background with white lettering. CFC 605.11.1.1
3.Marcking shall contain the words: WARNING : PHOTOVOLTAIC POWER
SOURCE. CFC 605.11.1.2
4.Marcking shall be placed adjacent to the main service disconnect in a location
clearly visible from the location where the disconnect is operated CFC 605.11.1.3
*if applicable
PV SUB-PANEL ONLYCAUTION
AUTHORIZED SOLAR
PERSONNAL ONLY!
CAUTION
SOLAR DC CURRENT PRESENT
DURING DAYLIGHT HOURS
AC DISCONNECT
AC PHOTOVOLTAIC POWER SOURCE
RATED AC OUTPUT CURRENT: 16 .0 A MAX
NOMINAL AC OPERATING VOLTAGE: 240 Vac
WARNING!
ELECTRIC SHOCK HAZARD.
IF GROUND FAULT IS INDICATED,
NORMALLY GROUNDED
CONDUCTORS MAY BE
UNGROUNDED AND ENERGIZED.
DC DISCONNECT
DC PHOTOVOLTAIC POWER SOURCE
RATED MAX POWER POINT CURRENT-9.80 AMPS
RATED MAX POWER POINT VOLTAGE- 380 VOLTS
MAXIMUM SYSTEM VOLTAGE- 480 VOLTS
SHORT CIRCUIT CURRENT- 17.6 AMPS
11
(STICKER LOCATED
ON THE PV SUB PANEL)
11
PV LOAD CENTER SIZED FOR PV
BREAKERS ONLY OR RENDERED UNABLE
TO ACCEPT ANY ADDITIONAL LOADS.
3
CODE REQUIRED
SIGNAGE
CONTRACTOR
X
20 OCTOBER, 2017
10285 Colby Ave,
Cupertino, CA 95014
Debanjan Mukherjee
Lic# 960376
Highlight Solar Inc.
Address:
1624 Remuda Lane,
San Jose,
CA 95112
Phone Number:
(866) 926-9997
PV SYSTEM
AS INDICATED
Drawn By : Narek A.
N
0°
S
180°
E
90°
W
270° POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECTS LOCATED AS SHOWN:
12
(STICKER LOCATED
ON THE MAIN SERVICE PANEL)
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH
RAPID SHUT DOWN
12
SERVICE POINT &
UTILITY METERING
SOLAR INVERTER
SOLAR PV ARRAY ON ROOF
Colby AveAbby Ayende
10/24/17
4
CONTRACTOR
X
20 OCTOBER, 2017
10285 Colby Ave,
Cupertino, CA 95014
Debanjan Mukherjee
Lic# 960376
Highlight Solar Inc.
Address:
1624 Remuda Lane,
San Jose,
CA 95112
Phone Number:
(866) 926-9997
PV SYSTEM
AS INDICATED
Drawn By : Narek A.
SITE PLAN
N
0°
S
180°
E
90°
W
270°
SCALE
0 5 10 20 ft
MSP (Е) Main Service Panel
Solar Module
UNIT INDEX
INV (N) Inverter
Power Optimizer
MSP
INV Colby AvePublic SidewalkDriveway
115'
70'
9'
41'
38'
63'
Abby Ayende
10/24/17
ATTACHMENT
LAYOUT
5
CONTRACTOR
20 OCTOBER, 2017
10285 Colby Ave,
Cupertino, CA 95014
Debanjan Mukherjee
Lic# 960376
Highlight Solar Inc.
Address:
1624 Remuda Lane,
San Jose,
CA 95112
Phone Number:
(866) 926-9997
PV SYSTEM
AS INDICATED
Drawn By : Narek A.
MODULE WEIGHT (lbs)
# OF MODULES
TOTAL MODULE WEIGHT (lbs)
RACK WEIGHT (lbs)
TOTAL SYSTEM WEIGHT (lbs)
# OF STANDOFFS
MAX SPAN BETWEEN STANDOFFS (in)
LOADING PER STANDOFF (lbs)
TOTAL AREA (sq.ft.)
LOADING (PSF)
FLASH MOUNTING DETAIL
39.7
13
516
103
641
26
48
24.7
2.74
234
EXISTING 2" BY 4" @24" O.C. ROOF TRUSSES
IRONRIDGE XR10 RAIL
OPTIMIZERS WEIGHT (lbs)22
ATTACHMENT DETAILS
L-FOOT
GF-1 FLASHING
5/16" * 3.5" HANGER BOLT
MIN. 2.5" EMBED INTO FRAMING MEMBER
FRAMING MEMBER
SHEATHING
EPDM WASHER
5/16" EPDM BONDED 304 18.8 SS WASHER
IRONRDIGE XR10 RAIL
X
5"
SOLAR MODULE
Existing Roof Trusses 2" BY 4" @ 24" O.C.
2"x6" Blocking
18°
2"x4" Purlin
ATTACHMENT
1. Ironridge Racking System
2. Eco Fasten Flashing Attachment
3. Racking loading calculations were performed for ASCE 7-10 wind speeds @ 110 mph for
B and C exposure categories and ASCE 7-10 Seismic Design Category E.
4. Roof attachment hardware to be mounted to existing structure (2"x4"@24" O.C.Trusses) at 48" O.C. rail spans or less.
5. Lag bolts are 5/16" X 3.5" stainless steel with 2.5" minimum embedment into the roof rafters.
6. Roof sheathed with 1/2" plywood and upper surface is faced with felt paper.
Finished roof surface is One Layer of Composition Shingle .
7. Mounts or/and mounting hardware will be sealed with Tremco Vulkem 116 Polyurethane Sealant or equivalent.
48"
24"
Abby Ayende
10/24/17
6
CONTRACTOR
X
20 OCTOBER, 2017
10285 Colby Ave,
Cupertino, CA 95014
Debanjan Mukherjee
Lic# 960376
Highlight Solar Inc.
Address:
1624 Remuda Lane,
San Jose,
CA 95112
Phone Number:
(866) 926-9997
PV SYSTEM
AS INDICATED
INVERTER
DATA SHEET
Drawn By : Narek A.
Abby Ayende
10/24/17
7
CONTRACTOR
X
20 OCTOBER, 2017
10285 Colby Ave,
Cupertino, CA 95014
Debanjan Mukherjee
Lic# 960376
Highlight Solar Inc.
Address:
1624 Remuda Lane,
San Jose,
CA 95112
Phone Number:
(866) 926-9997
PV SYSTEM
AS INDICATED
OPTIMIZER
DATA SHEET
Drawn By : Narek A.
Abby Ayende
10/24/17
MODULE
DATA SHEET
8
CONTRACTOR
X
20 OCTOBER, 2017
10285 Colby Ave,
Cupertino, CA 95014
Debanjan Mukherjee
Lic# 960376
Highlight Solar Inc.
Address:
1624 Remuda Lane,
San Jose,
CA 95112
Phone Number:
(866) 926-9997
PV SYSTEM
AS INDICATED
Drawn By : Narek A.
Abby Ayende
10/24/17
RACKING
CERTIFICATION
9
CONTRACTOR
X
20 OCTOBER, 2017
10285 Colby Ave,
Cupertino, CA 95014
Debanjan Mukherjee
Lic# 960376
Highlight Solar Inc.
Address:
1624 Remuda Lane,
San Jose,
CA 95112
Phone Number:
(866) 926-9997
PV SYSTEM
AS INDICATED
Drawn By : Narek A.
Abby Ayende
10/24/17
RACKING
DATA SHEET
10
CONTRACTOR
X
20 OCTOBER, 2017
10285 Colby Ave,
Cupertino, CA 95014
Debanjan Mukherjee
Lic# 960376
Highlight Solar Inc.
Address:
1624 Remuda Lane,
San Jose,
CA 95112
Phone Number:
(866) 926-9997
PV SYSTEM
AS INDICATED
Drawn By : Narek A.
Abby Ayende
10/24/17
RACKING
SPECS
11
CONTRACTOR
X
20 OCTOBER, 2017
10285 Colby Ave,
Cupertino, CA 95014
Debanjan Mukherjee
Lic# 960376
Highlight Solar Inc.
Address:
1624 Remuda Lane,
San Jose,
CA 95112
Phone Number:
(866) 926-9997
PV SYSTEM
AS INDICATED
Drawn By : Narek A.
Abby Ayende
10/24/17
ATTACHMENT
DATA SHEET
12
CONTRACTOR
X
20 OCTOBER, 2017
10285 Colby Ave,
Cupertino, CA 95014
Debanjan Mukherjee
Lic# 960376
Highlight Solar Inc.
Address:
1624 Remuda Lane,
San Jose,
CA 95112
Phone Number:
(866) 926-9997
PV SYSTEM
AS INDICATED
Abby Ayende
10/24/17