10080055 EnergyBUILDING ENERGY ANALYSIS REPORT d
PROJECT:
TWO STORY RESIDENCE
r 10160 Lockwood Drive
:.j Cupertino, CA RO
O bM � AL
Project Designer:
Parra Builders
5704 Cloud Water Drive
Castro Valley, CA 94552
510-8890102
Report Prepared by:
SSS Designs LLC
Job Number:
CIE�IX'ZD
SEP 2 0 2010
BRR - 0810 4LEAF, NC.
Date: CT 2 2 2010
9/1/2010 REVEWEO
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2008 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC—www.engrgysoft.com.
Energ Pro 5.1 by EnerqySoft User Number: 8129 RunCode: 2010-09-01 T13:54:42 ID: BRR - 0810
TABLE OF CONTENTS -I
Cover Page
Table of Contents
Form CF-1 R Certificate of Compliance
Form MF-1 R Mandatory Measures Summary
HVAC System Heating and Cooling Loads Summary
Room Load Summary
EnergyPro 5.1 by EnergySoft Job Number. ID: BRR - 0810 User Number. 8129
1
2
3
8
11
12
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF-1 R
Project Name
TWO STORY RESIDENCE
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ® Existing+ Addition/Alteration
Date
91112010
Project Address
10160 Lockwood Drive Cupertino
California Energy Climate Zone
CA Climate Zone 04
Total Cond. Floor Area
3,278
Addition
1,121
# of Stories
2
FIELD INSPECTION ENERGY CHECKLIST
❑ Yes ❑ No HERS Measures -- If Yes, A CF-413 must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION Area Special
Gonstruction Type Cavity (ft) Features (see Part 2 of 5) Status
Roof Wood Framed Attic R 22 1,121 Radiant Barrier Venting New
Wall Wood Framed R-13 1,265 New
Floor Wood Famed w/Crawl Space R-13 2,157 Altered
Wall Wood Framed R-13 841 Existing
Door Opaque Door None 86 New
Door Opaque Door None 20 Existing
Wall • Wood Framed R-13 797 Altered
FENESTRATION U- Exterior
Orientation Area(ft) Factor SHGC Overhang Sidefins Shades Status
Front (W) 165.0 0.340 0.33 none none Bug Screen
New
Rear (E) 211.0 0.340 0.33 none none Bug Screen
New
Left (N) 119.0 0.340 0.33 none none Bug Screen
New
Right (S) 152.0 0.340 0.33 none none Bug Screen
New
HVAC SYSTEMS
Ot . Heating Min. Eff Cooling Min. Eff Thermostat Status
1 Central Furnace 93% AFUE Split Air Conditioner 10.0 SEER Setback
New
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R-Value Status
FAU Ducted Ducted Attic, Ceiling Ins, vented 5.0
New
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
EnergyPro 5.1 by EnergySoft User Number: 8129 RunCode: 2010-09-01 T13:54.42 1D: BRR - 0810
Page 3
PERFORMANCE CERTIFICATE: Residential (Part 2 of 5) CF-1 R
Project Name
TWO STORY RESIDENCE
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ® Existing+ Addition/Alteration
Date
9111201 p
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the special justification and documentation submitted.
The DHW System A O SMITH FPSH-75 is a non-NAECA large storage gas water heater. Verify DHW details.
The Existing Water Heater A O SMITH FPSH-75 has an EF less than the Vintage Defaults. Field verification is required.
TFie HVAC System FAU must serve only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must be
controlled with a separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix RA-6 must be met.
This building incorporates an air retarding wrap which shall be installed to meet the requirements of Section 150 (f) of the Standards.
The Roof R-38 Roof Attic (b) includes credit for a Radiant Barrier that is Continuous meeting eligibility and installation criteria as specified in Residential
Appendix RA4.2.2.
The Roof R-38 Roof Attic (b) includes an Airgap below Roofing 11150 Vent Area requires verification.
HERS REQUIRED VERIFICATION
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
completed CF-413 form for each of the measures listed below for final to be given.
EnergvPro 5.1 by EnerqySoft User Number: 8129 RunCode: 2010-09-01 T13:54:42 ID: BRR - 0810 Pa e 4 of 12
PERFORMANCE CERTIFICATE: Residential Part 3 of 5 CF-1 R
projecl Name
Building Type m single Family ❑ Addltion}Ilone
Date
TWO STORY RESIDENCE
❑ Multi Family to E xA sbngt +9odditianMeraiion
9/1/2010
ANNUAL ENERGY USE SUMMARY
sfendard F%voaed Marpr?
TDV tuJft r
Space Heating 20.64 fT46 Ile
Space Cooling E34 2.57 5.77
Fans 5.02 1730 1.64
Dorr,,pstic Hot Water 14.83 14.83 0.00
puraps 0.00 0-0 0.00
Totals -46.63 38-25 10-M
Per-�ettt a tter Than , t ndard: 21. 7 %
BUILDING COMPLIES - NO HERS VERIFICATION REQUIRED
Fenestration
Building Front Orientation: iM 270 dag Ext walwRoof Wall Area Area
Number of Dwelling Units: 1 s5o 1s5
Fuel. Available at Site: Nat"WGes rAq 878 119
Raised Floor Area: Z157 214
Slab an Grade Area: 0 fs} 878 152
Average Geiling H60ht: - 93 1,121 0
Fenestration Average U-Factor 0.34 TOTAL: 647-
Avera , aSHGC: 0.3.3 Fenestration/CFA Ratio: 19-7 Yo
REMARKS
STATEMENT OF 00IVIPLIANCE
This-certlflcate of..c.ompliance lists -the building features and.specifications-needed
to. Comply with Titl�'24,: Parts I -the Administrative Regulations and Part 6 the
Efficiency Standards of the California Code of Regulations.
The documentation author hereby certifies that tha docurnentation is aracurate and Complete_
Documents tion Author
Company SSs L�srgns Ltd
Address -10 j1�-VRNPA1,' kw Name '5;l4 jiYwr" SAMIK 9P112b10
cl, Istartsp f4rj rN'l?°ithl ! : Phan !Z " 4-71 Si° ned Data
The individual with overaf , design responobiky. hereby certifles that the proposed building.desion.represented in this set
of construction doimrnenta is consistent.with the other compliance form and worksheets, '+irith the speciflcalm" MS, and
with any other calculations submitted with Oft permit abplicstlon, and recognlzes that compliance using duct design,
duct sealing, veifficatlon of"refrigerant charge, -.insulation ink6ilation quality; and building envelope sealing requ e
installer testing and Cartlfication and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code)
CoinlpsrYy panm 60ders
Address 5704 0oud Water Drive Name Rudy Parra � L►
CltylSt2ts 7jp Castro Valley, CA 94552 Phone 510-8809102 Slgrt License # Date
EfWayPro 5. i by Erae S ft Usar N 12 D. 8 4o pe s 5 of 42
CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF-1 R
Project Name
TWO STORY RESIDENCE
Building Type 10 Single Family ❑ Addition Alone
❑ Multi Family ® Existing+ Addition/Alteration
Date
911,12010
OPAQUE SURFACE
DETAILS
Surface
Type
Area
U-
Factor
Insulation
Azm I
Tilt
Status
Joint Appendix
4
Location/Comments
Cavity
Exterior
Frame
Interior
Frame
Roof
1,121
0.043
R-22
01
28
New
4.2 1 A6
SECOND FLOOR
Wall
313
0.102
R-13
270
90
New
4.3.1 A3
SECOND FLOOR
Wall
327
0.102
R-13
90
90
New
4.3.1-A3
SECOND FLOOR
Wall
334
0.102
R-13
0
90
New
14.3.1 A3
SECOND FLOOR
Wall
291
0.102
R-13
180
90
New
4.3.1-A3
SECOND FLOOR
Flao
2,157
0.046
R-13
0
180
Altered
4.4.1-A3 (E=4.4.1-A3)
FIRST FLOOR
Wall
436
0.102
R-13
270
90
Existing
4.3.1-A3
FIRSTFLOOR
Door
36
1.450
None
270
90
New
4.5.1-A1
FIRSTFLOOR
Wall
405
0.102
R-13
0
90
Existing
4.3.1-A3
FIRSTFLOOR
Door
20
1.450
None
0
90
Existing
14.5.1-A1
FIRSTFLOOR
Wall
402
0.102
R-13
180
90
Altered
4.3.1-A3 (E=4.3.1-A3)
FIRST FLOOR
Door
33
1.450
None
180
90
New
4.5.1-A1
FIRSTFLOOR
Wall
395
0.102
R-13
90
90
Altered
4.3.1-A3 ft4.3.1-A3
FIRSTFLOOR
Door
17
1.450
None
90
90
New
4.5.1-A1
FIRSTFLOOR
FENESTRATION
SURFACE
DETAILS
ID
Type
Area
U-Factor
SHGC
Azm
Status
Glazing Type
Location/Comments
1
Window
96.0
0.340
NFRC
0.33
1 NFRC
270
New Andersen
Permashield
SECOND FLOOR
2
Window
82.0
0.340
NFRC
0.33
NFRC
90
New Andersen
Permashield
SECOND FLOOR
3
Window
41.0
0.340
NFRC
0.33
NFRC
0
New Andersen
Permashield
SECOND FLOOR
4
Window
84.0
0.340
NFRC
0.33
NFRC
180
New Andersen
Permashield
SECOND FLOOR
5
Window
69.0
0.340
NFRC
0.33
NFRC
270
New 1 Andersen
Permashield
FIRSTFLOOR
6
Window
78.0
0.340
NFRC
0.33
NFRC
0
New Andersen
Permashield
FIRSTFLOOR
7
JWndow
68.0
0.340
NFRC
0.33
NFRC
180
New Andersen
Permashield
FIRSTFLOOR
8
Window
129.0
0.340
NFRC
0.33
NFRC
90
New Andersen
Permashie/d
FIRSTFLOOR
(1) U-Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR
SHADING DETAILS
ID
Exterior Shade Type
SHGC
Window
Overhan .
Left Fin
Rig ht Fin
Hcjt
Wd
Len
H t
LExt
RExt
Dist
Len
Hqt
Dist
Len
H t
1
Bug Screen
0.76
2
Bug Screen
0.76
3
Bug Screen
0.76
4
1Bug Screen
0.76
5
Bug Screen
0.76
6
Bug Screen
0.76
7
Bug Screen
0.76
8
Bug Screen
0.76
EnergyPro 5.1 by Ener Soft User Number. 8129 Run Code: 2010-09-01 T13:54:42 ID: BRR - 0810 Page 6 of 12
CERTIFICATE OF COMPLIANCE: Residential (Part 5 of 5) CF-1 R
Project Name
TWO STORY RESIDENCE
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ® Existing+ Addition/Alteration
Date
9/1/2010
BUILDING ZONE INFORMATION
System Name
Zone Name
Floor Area
Volume
Year Built
New
Existing
Altered
Removed
FAU
Second Floor
1,121
10,089
First Floor
Z 157
20,276
1985
Totals
1,1211
0
Z 1571
0
HVAC SYSTEMS
System Name
Ot .
Heating Ty e
Min. Eff.
Cooling Type
Min. Eff.
Thermostat Type
Status
FAU
1
Central Furnace
93% AFUE
Split Air Conditioner
10.0 SEER
Setback
New
HVAC DISTRIBUTION
System Name
Heating
Coolin
Duct Location
Duct
R-Value
Ducts
Tested?
Status
FAU
Ducted
Ducted
Attic, Ceiling Ins, vented
6.0
❑
New
WATER HEATING SYSTEMS
S stem Name
Ot .
Type
Distribution
Rated
Input
Btuh
Tank
Cap.
al
Energy
Factor
or RE
Standby
Loss or
Pilot
Ext.
Tank
Insul. R-
Value
Status
A O SMITH FPSH-75
1
Large Gas
Kitchen Pipe Ins
60,000
74
0.78
1.91 %
0.0
Existing
MULTI -FAMILY WATER
HEATING DETAILS
HYDRONIC
HEATING SYSTEM
PIPING
ControlPlenum
E
E
w 0
Hot Water Piping Length
ff
=
io
Q c
—
System Name
Pipe
Length
Pipe
Diameter
Insul.
Thick.
FH
Outside
Buried
❑
❑
1 10
❑
❑
❑
❑
❑
❑
EnemyPro 5.1 by EnergySoft User Number.- 8129 RunCode: 2010-09-01 T13:54:42 ID: BRR - 0810 Pa e 7 of 12
MANDATORY MEASURES SUMMARY: Residential (Page 1 of 3 MF-1 R
L7
Project Name
TWO STORY RESIDENCE
Date
9/9/2090
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF-1 R, CF-1 R-ADD, or CF-
1 R-ALT Form) shall supersede the items marked with an asterisk (') below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF-1 R
Form with plans.
Building Envelope Measures:
116 a 1: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§1 td(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U-Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of 10-111 (a).
117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
118 a : Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on CF-6R Form.
§118(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(i) when the
installation of a Cool Roof is specified on the CF-1 R Form.
* 150 a : Minimum R-19 insulation in wood -frame ceiling orequivalent U-factor.
150 b : Loose fill insulation shall conform with manufacturer's installed design labeled R-Value.
' 150 c : Minimum R-13 insulation in wood -frame wall orequivalent U-factor.
' 150 d : Minimum R-13 insulation in raised wood -frame floor or equivalent U-factor.
150 f : Air retarding wrap is tested, labeled, and installed according to ASTM El 677-95 2000 when specified on the CF-1 R Form.
150 : Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150(I): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance
rate is no greater than 2.0perm/inch and shall be protected from physical damage and UV light deterioration.
Fire laces, Decorative Gas Appliances and Gas Log Measures:
150 e 1 A: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150(e)l B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a with a readily accessible, operable, and tight -fitting damper and or a combustion -air control device.
§150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox. jacket, when that indoor air is vented to the
outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission.
§113(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve backflow prevention, pump isolation valve, and recirculation loop connection requirements of §113(c)5.
§115: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters.
150 h : Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA.
150 i : Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c).
§1500)1 A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are extemally wrapped
with insulation having an installed thermal resistance of R-12 or greater.
§1500)1 B: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water
tanks have R-12 external insulation or R-16 internal insulation where the intemal insulation R-value is indicated on the exterior of the
tank.
§1500)2: First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire length of
recirculating sections of hot water pipes are insulated per Standards Table 150-13.
§1506)2: Cooling system piping (suction, chilled water, or brine lines),and piping insulated between heating source and indirect hot
water tank shall be insulated to Table 150-B and Equation 150-A.
§1500)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards Table
123-A.
15Q ' 3A: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
§1500)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retardant or is enclosed entirely in
conditioned space.
150 ' 4: Solar water -heating systems and/or collectors are certified by the Solar Rating and Certification Corporation.
EnergyPro 5.1 by Ene►gySoft User Number. 8129 RunCode: 2010-09-01 T13.54.42 ID: BRR - 0610 Page 6 of 12
MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF-1 R
Project Name
Date
TWO STORY RESIDENCE
9/1/2010
§150(m)1: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections
601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-
4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the
applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is
used to seal openings reater than 1/4 inch, the combination of mastic and either mesh or tape shall be used
§150(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain duds. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross -sectional area
of the ducts.
§150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
unless such tape is used in combination with mastic and draw bands.
150 m 7: Exhaust fans stems have back draft or automatic dampers.
§150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
150 m 10: Flexible ducts cannot have porous inner cores.
§150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air
Quality in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation
required in Secfion 4 of that Standard.
Pool and Spa Heating Systems and Equipment Measures:
§114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on -off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating or a pilot light.
§114(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
and return lines, or built-up connections for future solar heating.
114 b 2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover.
§114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
programmed to run only during off-peak electric demand periods.
150 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150
Residential Lighting Measures:
§150(k)1: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies
contained in Table 150-C and is not a low efficacy luminaire as specified by §150(k)2.
150 k 3: The wattage of permanently installed luminaires shall be determined as specified by §130(d).
§150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than
20 kHz.
§150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain
only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line -voltage socket or line -
voltage lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a
medium screw -base socket.
150 k 6: Lighting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of 150 k .
150 k 7: All switching devices and controls shall meet the requirements of §150(k)7.
§150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 112 or 100 watts for dwelling units larger than 2,500 ft2 may be
exempt from the 50% high efficacy requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant
sensor, dimmer, energy management system (EMCS), or a multi -scene programmable control system; and all permanently installed
luminaries in garages, laundry rooms, closets greater than 70 square feet, and utility rooms are high efficacy and controlled by a
manual -on occupant sensor.
§150(k)9: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
illuminated cabinet.
Ene►gyPro 5.1 by EnergySoft User Number, 8129 RunCode: 2010-09-01 T13:54:42 ID: BRR - 0810 Page 9 of 12
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF-1 R
Project Name
Date
TWO STORY RESIDENCE
9/1/2010
§150(k)10: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms
shall be high efficacy.
EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual -on
occupant sensor certified to comply with the applicable requirements of §119.
EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a
manual -on occupancy sensor.
§150(k)11: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms,
closets, and utility rooms shall be high efficacy luimnaires_ EXCEPTION 1: Permanently installed low efficacy luminaires shall be
allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual -
on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less
than 1000 square feet located on a residential site is not required to comply with §150 k 11.
§150(k)12: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (1C) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air
leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be seated with a gasket or caulk between
the luminaire housing and ceiling.
§150(k)13: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more
dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the
same lot shall be high efficacy: EXCEPTION 1.: Permanently installed outdoor low efficacy luminaires shall be allowed provided that
they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor,
and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an
astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management
control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor
luminaires used to comply with Exceptionl to §150(k)13 may be controlled by a temporary override switch which bypasses the motion
sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed
luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not
be high efficacy luminaires.
§150(k)14. Internally illuminated address signs shall comply with Section 148; OR not contain a screw -base socket, and consume no
more than five watts of power as determined according to §130(d).
§150(k)15: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable
requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable
requirements of Sections 130, 131, 134, and 146.
§150(k)16: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more
dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided
that they are controlled by an occupant sensors certified to comply with the applicable requirements of 119.
EnergyPro 5.1 by EnergySoft User Number. 8129 RunCode., 2010-09-01 T13:54:42 ID: BRR - 0810 Page 10 of 12
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
TWO STORY RESIDENCE
Date
9/1/2010
System Name
FAU
Floor Area
3,278
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,217
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output perSystem
175,000
29,584
1,503
532
44,566
,*Total Output (Btuh)
175,000
0
Output Stuh/ ft
53.4
970
1,895
Cooling System
0
0
Output per System
28,000
0
0
0
0
Total Output Btuh
28,000
0
1,503
0
Total Output(Tons)
2.3
970
1,895
Total Output Btuh! ft
8.5
Total Output ftlron
1,404.9
1 31,523
48,356
Air System
CFM per S tem
2,045
HVAC EQUIPMENT SELECTION
Airflow cfm
2,045
Bryant
0
26,901
175,000
Airflow cfm/s ft)
0.62
Airflow cfm/Ton)
876.4
Outside Air 96
0.0 %
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
0
26,901
175,000
Outside Air cfm/
0.00
I
Note: values above given at ARt conditions
Aug 3 PM
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
28 OF 69 OF
Outside Air
0 ofrn Supply Fan
2,045 cfm
69 OF
69 IF 149 OF
Heating Col
148 OF
ROOM
70 OF
COOLING SYSTEM PSYCHROMETICS Airstream Tempntures at Time of Cooling Peak
88 / 68 OF 78 / 62 IF 78162 OF 55 / 54 OF
� Outside Air �
0 cfm Supply Fan Cooling Cod 55 / 54 OF
2,045 cfm
41.2 % 'ROOM
78 / 62 OF 78 / 62 OF
4 UELA 4
EnergyPro 5.1 by EnergySoft User Number. 8129 RunCode: 2010-09-01 T13:54:42 ID: BRR - 0810 Page 11 of 12
ROOM LOAD SUMMARY
Project Name Date
TWO STORY RESIDENCE 91112010
System Name Floor Area
FAU 3,278
ROOM LOAD SUMMARY
ROOM COOLING PEAK
Zone Name Room Name Mult. CFM Sensible .Latent
SECOND FLOOR Second Floor 1 575 13,962 767
F1F.ST FLOOR First Floor 1 643 15,622 736
PAGE TOTAL
TOTAL '
' Total includes ventilation load for zonal systems.
EnergyPro 5.1 by EnergySoft User Number: 8129 RunCode: 2010-09-01T13:54:42
COIL COOLING PEAK COIL HTG. PEAK
CFM Sensible I Latent CFM Sensible
575 13,962L 767 183 15,283
643 15,6221 736 3501 29,283
1,217
29,584
1,503
532
44,5
1,2171
29,5841
1,5031
532
44,5166]
1D: BRR - 0810
12