Loading...
BLD-2021-1082 PlansArnold Hom 06/16/21 06/16/21 BLD-2021-1082 Haley McKee Maximum roof load:2.68 lbs/ft² Maximum point load:32.4 lbs/attachment Model: Longi Solar LR6-60HPB-310M Weight: 40.12 Lbs Width: 39 Inches Length: 65 Inches ROOF LOADS Arnold Hom 06/16/21 Nom Voltage 240 V Max Current 1 A Branch Circuits 1 Modules per Branch 10 Number of Inverters 10 Record low temp 19°F Max AC Output Current 10 A Operating AC Voltage 240 V Operating AC Power 2400 W Operating AC Frequency 60 Hz Max OCPD Rating 15 A Enphase IQ7-60-2-US 240V CONFIGURATION AC SYSTEM SPECIFICATIONS UL 1741, NEMA 3R, IEEE 1547 40.3 Voc, 33.3 Vmp, 20 Vnom 9.86 Isc, 9.3 Imp JUNCTION BOX 600 V, UL E42728, NEMA 1,2,3,4,4x,6,12,13 INVERTER PHOTOVOLTAIC MODULE Longi Solar LR6-60HPB-310M UL1703 Power 310 W Calculations for Current Carrying Conductors: Note: Conduit shall be Installed Min 1-1/2" above roof surface Max Branch AC required conductor ampacity (1)(10)(1.25) = 12.5A AWG #10, derated ampacity: (40)(0.71)(1) = 28.4A 28.4A > 12.5A , therefore AC wire size is valid. Arnold Hom 06/16/21