BLD-2021-2354 Product DataSpecifications subject to change without notice. Fig. 1 — 124ANS Unit NOTE: Images are for illustration purposes only. Actual models may differ slightly. Bryant air conditioners with Puron refrigerant provide a collection of features unmatched by any other family of equipment. The 124ANS has been designed utilizing Bryant’s Puron refrigerant. This environmentally sound refrigerant allows you to make a responsible decision in the protection of the earth’s ozone layer. NOTE: Ratings contained in this document are subject to change at any time. Always refer to the AHRI directory (www.ahridirec- tory.org) for the most up-to-date ratings information. TABLE OF CONTENTS INDUSTRY LEADING FEATURES / BENEFITS ........................1 MODEL NUMBER NOMENCLATURE........................................2 PHYSICAL DATA...........................................................................2 REFRIGERANT PIPING LENGTH LIMITATIONS.....................3 VAPOR LINE SIZING AND COOLING CAPACITY LOSS........5 ACCESSORIES................................................................................6 ELECTRICAL DATA......................................................................8 DIMENSIONS-ENGLISH...............................................................9 DIMENSIONS-SI.............................................................................10 TESTED AHRI COMBINATION RATINGS*...............................11 DETAILED COOLING CAPACITIES ...........................................12 CONDENSER ONLY RATINGS....................................................15 GUIDE SPECIFICATIONS.............................................................17 PRODUCTS .....................................................................................17 INDUSTRY LEADING FEATURES / BENEFITS Energy Efficiency • 14 SEER/11.7 - 12.2 EER (Based on tested combinations) Sound • Levels as low as 66 dBA Design Features • Small footprint • WeatherArmor cabinet - All steel cabinet construction - Mesh coil guard Reliability, Quality and Toughness • Scroll compressor • Factory-supplied filter drier • High pressure switch • Line lengths up to 250ft (76.2 m) • Low ambient operation (down to -20 F/-28.9 C with low ambient accessories) TM Product Data 124ANS PREFERREDTM SERIES AIR CONDITIONER WITH PURON REFRIGERANT 1-1/2 TO 5 NOMINAL TONS Arnold Hom 11/30/21 2 Specifications subject to change without notice. PDS124ANS-06 MODEL NUMBER NOMENCLATURE PHYSICAL DATA * Units are rated with 25 ft. (7.6 m) of lineset length. Review the VAPOR LINE SIZING AND COOLING CAPACITY LOSS section when using other lineset sizes and lengths of lineset. Note: Review the unit’s Installation Instructions for proper installation guidance. Liquid Line Sizing For Cooling Only Systems with Puron Refrigerant tables. 1 2 3 4 5 6 7 8 9 10 11 12 14 N N N A A/N N N N N A/N A/N N A 1 2 4 A N S 0 3 6 0 0 0 0A Product Family 1 = AC Tier 2 = Preferred SEER 4 = 14 SEER Variations S = Side Discharge Voltage N=208/230-1 P=208/230-3 E = 460-3 Variations S = Standard Cooling Capacity Open 0 = Not Defined Open 0 = Not Defined Open 0 = Not Defined Series A = Original Series UNIT SIZE-SERIES (VOLTAGE) 18-A (N)24-A(N) 30-A(N) 36-A (N,P,E) 48-A(N,P,E) 60-A (N,P,E) Compressor Type Scroll REFRIGERANT Puron® (R-410A) Charge lb (kg)6.40 (2.90) 6.50 (2.95) 8.60 (3.90) 8.90 (4.04) 9.00 (4.08) 10.60 (4.81) Cond Fan Propeller Type, Direct Drive Air Discharge Horizontal Air Qty (CFM)1285 1285 1900 2615 2615 2785 Motor HP 1/12 1/12 1/10 1/4 1/4 1/4 Motor RPM 800 800 800 800 800 800 Cond Coil Face Area (Sq ft)7.3 7.3 12.1 12.1 12.1 14.1 Fin s pe r In. 20 20 20 20 20 20 Rows 2 2 2 2 2 2 Circuits 3 3 3 3 3 4 Valve Connect. (In. ID) Vapor 5/8 3/4 3/4 7/8 7/8 7/8 Liquid 3/8 Refrigerant Tubes* (In. OD) Rated Vapor*5/8 3/4 3/4 7/8 7/8 1 1/8 Max Liquid Line 3/8 Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org. PDS124ANS-06 Specifications subject to change without notice. 3 REFRIGERANT PIPING LENGTH LIMITATIONS Liquid Line Sizing and Maximum Total Equivalent Lengths for Cooling Only Systems with Puron Refrigerant: The maximum allowable length of a residential split system depends on the liquid line diameter and vertical separation between the indoor and outdoor units. Review “Maximum Total Equivalent Length Outdoor Unit BELOW Indoor Unit,” for the liquid line sizing and maximum lengths. Maximum Total Equivalent Length Outdoor Unit BELOW Indoor Unit * Maximum actual length not to exceed 200 ft (61 m) Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details. -- = outside acceptable range Maximum Total Equivalent Length Outdoor Unit ABOVE Indoor Unit * Maximum actual length not to exceed 200 ft (61 m) Total equivalent length accounts for losses due to elbows or fitting. See “LONG-LINE APPLICATIONS,” for details. -- = outside acceptable range SIZE LIQUID LINE CONNECTION (IN. OD) LIQUID LINE DIAM. W/ TXV (IN. OD) AC WITH PURON REFRIGERANT MAXIMUM TOTAL EQUIVALENT LENGTH: OUTDOOR UNIT BELOW INDOOR VERTICAL SEPARATION FT (M) 0-5 (0-1.5) 6-10 (1.8-3.0) 11-20 (3.4-6.1) 21-30 (6.4-9.1) 31-40 (9.4-12.2) 41-50 (12.5-15.2) 51-60 (15.5-18.3) 61-70 (18.6-21.3) 71-80 (21.6-24.4) 018 AC with Puron 3/8 1/4 150 150 125 100 100 75 -- -- -- 5/16 250* 250* 250* 250* 250* 250* 250* 225* 150 3/8 250* 250* 250* 250* 250* 250* 250* 250* 250* 024 AC with Puron 3/8 1/4 75 75 75 50 50 -- -- -- -- 5/16 250* 250* 250* 250* 250* 225* 175 125 100 3/8 250* 250* 250* 250* 250* 250* 250* 250* 250* 030 AC with Puron 3/8 1/4 30 -- -- -- -- -- -- -- -- 5/16 175 225* 200 175 125 100 75 -- -- 3/8 250* 250* 250* 250* 250* 250* 250* 250* 250* 036 AC with Puron 3/8 5/16 175 150 150 100 100 100 75 -- -- 3//8 250* 250* 250* 250* 250* 250* 250* 250* 250* 048 AC with Puron 3/8 3/8 250* 250* 250* 250* 250* 250* 230 160 -- 060 AC with Puron 3/8 3/8 250* 250* 250* 225* 190 150 110 ---- SIZE LIQUID LINE CONNECTION (IN. OD) LIQUID LINE DIAM. W/ TXV (IN. OD) AC WITH PURON REFRIGERANT MAXIMUM TOTAL EQUIVALENT LENGTH: OUTDOOR UNIT ABOVE INDOOR VERTICAL SEPARATION FT (M) 25 (7.6) 26-50 (7.9-15.2) 51-75 (15.5-22.9) 76-100 (23.2-30.5) 101-125 (30.8-38.1) 126-150 (38.4-45.7) 151-175 (46.0-53.3) 176-200 (53.6-61.0) 018 AC with Puron 3/8 1/4 175 250*250*250*250*250*250*250* 5/16 250*250*250*250*250*250*250*250* 3/8 250*250*250*250*250*250*250*250* 024 AC with Puron 3/8 1/4 100 125 175 200 225* 250*250*250* 5/16 250*250*250*250*250*250*250*250* 3/8 250*250*250*250*250*250*250*250* 030 AC with Puron 3/8 1/4 30 -- -- -- -- -- -- -- 5/16 250*250*250*250*250*250*250*250* 3/8 250*250*250*250*250*250*250*250* 036 AC with Puron 3/8 5/16 225*250*250*250*250*250*250*250* 3/8 250*250*250*250*250*250*250*250* 048 AC with Puron 3/8 3/8 250*250*250*250*250*250*250*250* 060 AC with Puron 3/8 3/8 250*250*250*250*250*250*250*250* 4 Specifications subject to change without notice. PDS124ANS-06 REFRIGERANT CHARGE ADJUSTMENTS Units are factory charged for 15 ft (4.6 m) of 3/8” liquid line. The factory charge for 3/8” lineset 9 oz (266.16 g). When using other length or diameter liquid lines, charge adjustments are required per the REFRIGERANT CHARGE ADJUSTMENTS table. Charging Formula: [(Lineset oz/ft x total length) – (factory charge for lineset)] = charge adjustment Example 1: System has 15 ft of line set using existing 1/4 “liquid line. What charge adjustment is required? Formula: (.27 oz/ft x 15ft) – (9 oz) = (4.95) oz. Net result is to remove 4.95 oz of refrigerant from the system Example 2: System has 45 ft of existing 5/16” liquid line. What is the charge adjustment? Formula: (.40 oz/ft. x 45ft) – (9 oz.) = 9 oz. Net result is to add 9 oz of refrigerant to the system LONG-LINE APPLICATIONS An application is considered Long-Line, when the refrigerant level in the system requires the use of accessories to maintain acceptable refrigerant management for systems reliability. See ACCESSORY USAGE GUIDELINES on page 7 for the required accessories. Defining a system as long-line depends on the liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units. For air conditioner systems, the “AC WITH PURON REFRIGERANT LONG-LINE DESCRIPTION ft (m)” table shows when an application is considered long-line. AC WITH PURON REFRIGERANT LONG-LINE DESCRIPTION ft (m) Beyond these lengths, long line accessories are required LIQUID LINE SIZE (IN. OD)PURON CHARGE OZ/FT (G/M) 3/8 0.60 (17.74) (Factory charge for lineset = 9 oz / 266.16 g) 5/16 0.40 (11.83) 1/4 0.27 (7.98) LIQUID LINE SIZE (IN. OD)UNITS ON SAME LEVEL - FT (M) OUTDOOR BELOW INDOOR - FT (M)OUTDOOR ABOVE INDOOR - FT (M) 1/4 No accessories needed within allowed lengths No accessories needed within allowed lengths 175 (53.3) 5/16 120 (36.6)50 (15.2) vertical or 120 (36.6) total 120 (36.6) 3/8 80 (24.4)35 (10.7) vertical or 80 24.4) total 80 (24.4) PDS124ANS-06 Specifications subject to change without notice. 5 VAPOR LINE SIZING AND COOLING CAPACITY LOSS LONG LINE APPLICATION: An application is considered “long- line” when the total equivalent tubing length exceeds 80 ft. (24.4 m) or when there is more than 20 ft. (6.09 m) vertical separation between the indoor and outdoor units. These applications require additional accessories and system modifications for reliable system operation. The maximum allowable total equivalent length is up to 250 ft. (76.2 m). The maximum vertical separation is 200 ft. (60.96 m) when the outdoor unit is above the indoor unit, and up to 80 ft. (24.4 m) when the outdoor unit is below the indoor unit. Refer to the ACCESSORY USAGE GUIDELINES on page 7 for required accessories. See the Long-line Application Guideline for required piping and system modifications. Also, refer to the “Vapor Line Sizing and Cooling Capacity Losses — Puron Refrigerant 1-Stage Air Conditioner Applications” table for the vapor tube diameters based on the total length to minimize the cooling capacity loss. Vapor Line Sizing and Cooling Capacity Losses — Puron Refrigerant 1-Stage Air Conditioner Applications *Applications in this area may be long- line and may have height restrictions. See LONG-LINE APPLICATIONS on page 4. UNIT NOMINAL SIZE (BTUH) MAXIMUM LIQUID LINE DIAMETERS (IN. OD) VAPOR LINE DIAMETERS (IN. OD) COOLING CAPACITY LOSS (%) TOTAL EQUIVALENT LINE LENGTH FT. (M) 26-50 (7.9-15.2) 51-80 (15.5-24.4) 81-100 (24.7-30.5) 101-125 (30.8-38.1) 126-150 (38.4-45.7) 151-175 (46.0-53.3) 176-200 (53.6-61.0) 201-225 (61.3-68.6) 226-250 (68.9-76.2) 018 1 Stage AC with Puron 3/8 1/2 1 2 3 5 6 7 8 9 11 5/8 0 1 1 1 2 2 2 3 3 3/4 0 0 0 0 1 1 1 1 1 024 1 Stage AC with Puron 3/8 5/8 0 1 2 2 3 3 4 5 5 3/4 0 0 1 1 1 1 1 2 2 7/8 0 0 0 0 0 1 1 1 1 030 1 Stage AC with Puron 3/8 5/8 1 2 3 3 4 5 6 7 8 3/4 0 0 1 1 1 2 2 2 3 7/8 0 0 0 0 1 1 1 1 1 036 1 Stage AC with Puron 3/8 5/8 1 2 4 5 6 8 9 10 12 3/4 0 1 1 2 2 3 3 4 4 7/8 0 0 0 1 1 1 1 2 2 048 1 Stage AC with Puron 3/8 3/4 0 1 2 3 4 5 5 6 7 7/8 0 0 1 1 2 2 2 3 3 1 1/8 0 0 0 0 0 0 0 1 1 060 1 Stage AC with Puron 3/8 3/4 1 2 4 5 6 7 9 10 11 7/8 0 1 2 2 3 4 4 5 5 1 1/8 0 0 0 1 1 1 1 1 1 6 Specifications subject to change without notice. PDS124ANS-06 ACCESSORIES X = Accessory ACCESSORY THERMOSTATS KIT NUMBER KIT NAME UNIT SIZE (VOLTAGE/SERIES) 018 (30) 024 (30) 030 (30) 036 (30) 036 (50) 036 (60) 048 (30) 048 (50) 048 (60) 060 (30) 060 (50) 060 (60) KAACH1401AAA Crankcase Heater X X X X X KAACH1201AAA Crankcase Heater X X X X KAACH1501AAA Crankcase Heater X KAACH1901AAA Crankcase Heater X X KSAFT0101AAA Evaporator Freeze Stat X X X X X X X X X X X X KAATD0101TDR Time Delay Relay X X X X X X X X X X X X KAAWS0101AAA Winter Start Kit X X X X X X X X X X X X KSALA0801AAA Motor Master® 230v X X X X X X X X X KSALA0901AAA Motor Master® 460v X X X 53DS-900---087 Wind Baffle X X 53DS-900---071 Wind Baffle X X X X X X X 53DS-900---088 Wind Baffle X X X 53DS-900---076 Stacking Kit X X X X X X X X X X X X 53DS-900---077 Wall Mounting Kit X X 53DS-900---078 Wall Mounting Kit X X X X X X X X X X KAALP0401PUR Low Pressure Switch Kit X X X X X X X X X X X X KSASH2301COP Sound Blanket Kit X X X X X X KSASH2401COP Sound Blanket Kit X X X X X X KAALS0201LLS Solenoid Valve Kit X X X X X X X X X X X X KSAHS1501AAA Capacitor Relay Start Assist X X X X X X PART NUMBER DESCRIPTION EB-STATE5CR-01 ecobee SmartThermostat Pro with voice control powered by Bryant EB-STATE3LTCR-01 ecobee3 lite Pro Powered by Bryant T6-PRH01-A Programmable Relative Humidity Thermostat T6-PAC01 Programmable Thermostat T6-NRH01 Non-Programmable Relative Humidity Thermostat T6-NAC01 Non-Programmable Thermostat T2-WHS01 WiFi® Thermostat T2-PAC01 Programmable Thermostat-programmable Thermostat T2-NAC01 Non-programmable Thermostat T2-SNAC01 Non-programmable Standard Screen Thermostat THERMOSTAT ACCESSORIES T6-EXP edge™ EXP® Card T6Pxx,T6Nxx TSTATCCSEN01-B Outdoor Air Temperature Sensor T6-Pxx, T6-Nxx TSTATXXCNV10 Thermostat Conversion Kit (4 to 5 wire) - 10 pack All Bryant® branded thermostats TX-MBP01 Medium Decorative Backplate T2-Nxx TX-LBP01 Large Decorative Backplate T6-Pxx, T6-Nxx, T2-Pxx PDS124ANS-06 Specifications subject to change without notice. 7 ACCESSORY USAGE GUIDELINES * For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split-System Long line Application Guideline. ACCESSORY DESCRIPTION AND USAGE (LISTED ALPHABETICALLY) 1. Ball−Bearing Fan Motor A fan motor with ball bearings that permits speed reduction while maintaining bearing lubrication. Usage Guideline: Required on all units when using MotorMaster 2. Compressor Start Assist − Capacitor and Relay Start capacitor and relay gives a “hard” boost to compressor motor at each start up. Usage Guideline: Required for reciprocating compressors in the following applications: Long line Low ambient cooling Hard shut off expansion valve on indoor coil Liquid line solenoid on indoor coil Required for single−phase scroll compressors in the following applications: Long line Low ambient cooling Suggested for all compressors in areas with a history of low voltage problems. 3. Crankcase Heater An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes the chance of liquid slugging. Usage Guideline: Required in low ambient cooling applications. Required in long line applications. Suggested in all commercial applications. 4. Evaporator Freeze Thermostat An SPST temperature−actuated switch that stops unit operation when the evaporator reaches freeze−up conditions. Usage Guideline: Required when a low ambient kit has been added. 5. Low Pressure Switch Kit Optional added compressor protection against loss of refrigerant. The compressor cuts out the system at 50 PSI and allows operation again at 95 PSI. Used for commercial or “harsh” environment applications for extra protection. Not required for a Low−Ambient Cooling application. 6. MotorMaster Low−Ambient Controller A fan−speed control device activated by a temperature sensor, designed to control condenser fan motor speed in response to saturated condensing temperatures down to −20 F (−28.9 C), it maintains condensing temperature at 100 F +/ − 10 F (37.8 C +/ − 6 C). Usage Guideline: A MotorMaster Low−Ambient Controller must be used when the cooling operation is used at outdoor temperatures below 55 F (12.8 C). Suggested for all commercial applications. 7. Winter Start Kit The device is designed to alleviate nuisance opening of the low−pressure switch by bypassing it for the first 3 minutes of operation. A Winter Start control must be used where low evaporator temperatures, or nuisance tripping of low−pressure switch may be encountered. It is not required for low ambient cooling applications unless a low−pressure switch KAALP0401PUR is added. 8. Time Delay Relay Optional accessory for systems that do not have an integral blower time delay. ACCESSORY REQUIRED FOR LOW-AMBIENT COOLING APPLICATIONS (BELOW 55 F / 12.8 C) REQUIRED FOR LONG LINE APPLICATIONS* (OVER 80 FT. / 24.38 M) REQUIRED FOR SEA COAST APPLICATIONS (WITHIN 2 MILES / 3.22 KM) Ball Bearing Fan Motor Standard Standard Standard Compressor Start Assist Capacitor and Relay Yes Yes No Crankcase Heater Yes Yes No Evaporator Freeze Thermostat Yes No No Liquid Line Solenoid Valve No See Long-Line Application Guideline No Motor Master® Controller Yes No No 8 Specifications subject to change without notice. PDS124ANS-06 ELECTRICAL DATA LEGEND: FLA - Full Load Amps HACR - Heating, Air Conditioning, Refrigeration LRA - Locked Rotor Amps NEC - National Electrical Code RLA - Rated Load Amps (compressor) * Permissible limits of the voltage range at which the unit operates satisfactorily ** Time-Delay fuse. Complies with 2007 requirements of ASHRAE Standards 90.1 A−WEIGHTED SOUND POWER (dBA) NOTE: Tested in accordance with AHRI Standard 270-08 (not listed in AHRI). A−WEIGHTED SOUND POWER (dBA) WITH ACCESSORY SOUND SHIELD NOTE: Tested in accordance with AHRI Standard 270-08 (not listed in AHRI). SOUND PRESSURE LEVELS, (dBA) NOTE: Sound pressure data vs distance converted using AHRI 275 Standard under certain environmental and layout assumptions . CHARGING SUB−COOLING (TXV−TYPE EXPANSION DEVICE NOTE: The conversion is accurate only when all the assumptions are correct. UNIT SIZE - VOLTAGE, SERIES V/PH OPER VOLTS*COMPR FAN MCA MAX FUSE** OR CKT BRK AMPSMAX MIN LRA RLA FLA 18-30 208/230/1 253 197 56.3 9.0 0.50 11.8 20 24-30 62.9 10.9 0.50 14.1 25 30-30 73.0 14.1 0.70 18.3 30 36-30 77.0 14.1 1.20 18.8 30 48-30 124.0 18.5 1.20 24.3 40 60-30 152.5 23.7 1.45 31.1 50 36-50 208/230/3 253 197 71.0 9.0 1.20 12.5 20 48-50 83.1 13.7 1.20 18.3 30 60-50 110.0 15.9 1.45 21.4 35 36-60 460/3 506 414 38.0 5.6 0.60 7.6 15 48-60 41.0 6.2 0.60 8.4 15 60-60 52.0 7.1 0.80 9.7 15 UNIT SIZE STANDARD RATING (DBA)TYPICAL OCTAVE BAND SPECTRUM (DBA, WITHOUT TONE ADJUSTMENT) 125 250 500 1000 2000 4000 8000 18 69 50.5 57.0 59.5 64.5 60.5 53.5 43.0 24 66 50.5 58.5 60.5 59.5 56.5 51.0 41.5 30 68 55.5 59.5 61.5 63.5 60.0 58.0 49.5 36 71 59.5 59.5 62.0 65.5 63.5 62.0 55.0 48 70 57.5 59.5 64.0 66.0 63.0 60.5 54.5 60 73 60.0 61.5 64.5 67.0 66.0 65.5 58.0 UNIT SIZE STANDARD RATING (DBA)TYPICAL OCTAVE BAND SPECTRUM (DBA, WITHOUT TONE ADJUSTMENT) 125 250 500 1000 2000 4000 8000 18 68 52.5 58.0 58.5 64.5 59.5 52.5 42.5 24 65 54.5 57.5 59.5 59.0 56.0 50.5 40.5 30 68 55.0 60.0 61.5 62.5 60.0 58.0 49.5 36 71 59.5 59.5 62.5 65.0 63.0 61.5 55.0 48 70 57.5 59.5 63.0 65.0 62.5 60.0 54.0 60 73 61.0 62.0 64.0 67.0 65.5 65.5 57.5 UNIT SIZE AT DISTANCE 10' FROM UNIT AT DISTANCE 15' FROM UNIT AT DISTANCE 20' FROM UNIT 18 51.5 48.0 45.5 24 48.5 45.0 42.5 30 50.5 47.0 44.5 36 53.5 50.0 47.5 48 52.5 49.0 46.5 60 55.5 52.0 49.5 UNIT SIZE-SERIES REQUIRED SUBCOOLING °F (°C) 18 12 (6.7) 24 12 (6.7) 30 12 (6.7) 36 8 (4.4) 48 12 (6.7) 60 10 (5.6) PDS124ANS-06 Specifications subject to change without notice. 9 DIMENSIONS-ENGLISH Fig. 2 — Dimensions 1. Clearance Requirements: a. Single Unit Applications: With the coil facing the wall, allow 6in (152mm) minimum clearance on the coil side, the coil end, and allow 20in (508mm) minimum clearance on the fan side. With the fan facing the wall, allow 8in (203mm) minimum clearance on the fan side, 6in (152mm) on the coil end and 20in (508mm) minimum clearance on the coil side. b. Multi Unit Applications: Allow 24in (610mm) minimum clearance between the fan and the coil sides of the multiple units. Arrange the units so the discharge of one unit does not enter the inlet of the other unit. When two units are installed end to end with the coil ends facing each other allow 12in (305mm) in minimum clearance between the units. c. Compressor End Service Clearance: Allow 24in (610mm) minimum clearance on the compressor end when the units are stacked or there is less than 40 in. (1016mm) of clearance above the top of the unit. If there is 40 in. (1016mm) of clearance above the unit and top panel is accessible for removal, allow 8in (203mm) minimum clearance minimum clearance on the compressor end for service. IMPORTANT: When installing single or multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent recirculation of discharged air. 2. Minimum outdoor operating ambient in the COOLING mode is 55 F (13 C) and a maximum of 125 F (52 C). 3. Series designation is the 13th position of the unit model number 4. Center of gravity 5. All dimensions are in inches unless noted. Fig. 3 — Dimensions UNIT Series Electrical Characteristics A B C D E F G H J K L M N P Operating Weight (lbs) Shipping Weight (lbs) Shipping Dimensions (L x W x H) 124ANS018 0 X 0 0 0 31 1/8” 36 15/16” 14 9/16” 16” 23 7/16” 17 3/16” 23 1/8” 28 1/16” 13” 6 5/8” 11 1/4” 5/8” 2 7/8” 5 13/16” 146 166 42 15/16” x 18” x 34 1/8” 124ANS024 0 X 0 0 0 31 1/8” 36 15/16” 14 9/16” 16” 23 7/16” 17 3/16” 23 1/8” 28 1/16” 14” 6 3/4” 11 5/8” 3/4” 2 7/8” 5 13/16” 148 168 42 15/16” x 18” x 3 4 1/8” 124ANS030 0 X 0 0 0 37 1/8” 44 1/2” 17 1/16” 18 7/16” 30 1/2” 19 5/8” 29 1/8” 34 1/16” 13 11/16” 8 1/8” 15 7/8” 3/4” 3 3/8” 6 3/8” 183 213 50 1/2” x 20 1/2” x 40 1/8” 124ANS036 0 X 0 X X 37 1/8” 44 1/2” 17 1/16” 18 7/16” 30 1/2” 19 5/8” 29 1/8” 34 1/16 13 11/16” 8 1/8” 15 7/8” 7/8” 3 3/8” 6 3/8” 184 214 50 1/2” x 20 1/2” x 40 1/8” 124ANS048 0 X 0 X X 37 1/8” 44 1/2” 17 1/16” 18 7/16” 30 1/2” 19 5/8” 29 1/8” 34 1/16 14 1/2” 8 1/2” 18 7/8” 7/8” 3 3/8” 6 3/8” 213 243 50 1/2” x 20 1/2” x 40 1/8” 124ANS060 0 X 0 X X 43 1/8” 44 1/2” 17 1/16” 18 7/16” 30 1/2” 19 5/8” 35 1/8” 40 1/16” 14 1/2” 8 1/2” 18 7/8” 7/8” 3 3/8” 6 3/8” 245 275 50 1/2” x 20 1/2” x 46 1/8” 20 8 - 2 3 0 - 1 - 6 0 20 3 - 1 - 6 0 20 8 / 2 3 0 - 3 - 6 0 46 0 - 3 - 6 0 X = YES 0 = NO AIR 7 1/2” 2 1/2” 4 3/16” AIR 11/16” FIELD CONTROL SUPPLY WIRE ENTRY 7/8” HOLE W/GROMMET M VAPOR LINE CONN. FEMALE SWEAT CONN. JUNCTION BOX FOR POWER SUPPLY AND CONTROL CONNECTIONS 3/8’ LIQUID LINE FEMALE SWEAT CONN. 1 7/16” 8 1/16” 1 7/16” 4 1/12”1” FIELD POWER SUPPLY CONN HOLE SIZES PROVIDED: 7/8” HOLD WITH 1 1/8” KNOCKOUT AND 1 3/8” KNOCKOUT UNIT SIZE MINIMUM MOUNTING PAD DIMENSIONS 18,24 23” x 42” 30,36,48,60 24” x 50” 10 Specifications subject to change without notice. PDS124ANS-06 DIMENSIONS-SI Fig. 4 — Dimensions 1. Clearance Requirements: a. Single Unit Applications: With the coil facing the wall, allow 6in (152.4mm) minimum clearance on the coil side, the coil end and allow 20in (508mm) minimum clearance on the fan side. With the fan facing the wall allow 8in (203.2mm) minimum clearance on the fan side and 6in (152.4mm) on the coil end plus 20in (504.0mm) minimum clearance on the coil side. b. Multi Unit Applications: Allow 24in (609.6mm) minimum clearance between the fan and coil sides of the multiple units. Arrange the units so the discharge of one does not enter the inlet of another. When two units are installed end to end with the coil ends facing each other, allow 12in (304.8 mm) minimum clearance between the units. c. Compressor End Service Clearance: Allow 24in (609.6mm) minimum clearance on the compressor end when the units are stacked or there is less than 40in (1016mm) of clearance above the top of the unit. If there is 40in (1016mm) clearance above the unit and the top panel is accessible for removal, allow 8in (203.2mm) minimum clearance on the compressor end for service. IMPORTANT: When installing single or multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent recirculation of discharged air. 2. Minimum outdoor operating ambient in the COOLING mode is 12.8 F (12.8 C) and a maximum of 125 F (51.7 C) 3. Series designation is the 14th position of the unit model number 4. Center of gravity 5. All dimensions are in millimeters unless noted. Fig. 5 — Dimensions UNIT Series Electrical Characteristics A B C D E F G H J K L M N P Operating Weight (KG) Shipping Weight (KG) Shipping Dimensions (L x W x H) 124ANS018 0 X 0 0 0 790.4 938.0 370.0 406.0 595.5 436.0 587.6 712.2 330.2 168.3 285.8 15.9 73.0 148.2 66.2 75.3 1090.2 x 45.7 x 866.7 124ANS024 0 X 0 0 0 790.4 938.0 370.0 406.0 595.5 436.0 587.6 712.2 355.5 171.5 295.3 19.1 73.0 148.2 67.1 76.2 1090.2 x 45.7 x 866.7 124ANS030 0 X 0 0 0 942.8 1130.0 433.0 469.0 774.5 499.0 740.0 864.6 347.7 206.4 403.2 19.1 86.0 161.2 83.0 96.6 1282.7 x 520.7 x 1019.1 124ANS036 0 X 0 X X 942.8 1130.0 433.0 469.0 774.5 499.0 740.0 864.6 347.7 206.4 403.2 22.2 86.0 161.2 83.5 97.1 1282.7 x 520.7 x 1019.1 124ANS048 0 X 0 X X 942.8 1130.0 433.0 469.0 774.5 499.0 740.0 864.6 368.3 215.9 479.4 22.2 86.0 161.2 96.6 110.2 1282.7 x 520.7 x 1019.1 124ANS060 0 X 0 X X 1095.2 1130.0 433.0 469.0 774.5 499.0 892.4 1,017.0 368.3 215.9 479.4 22.2 86.0 161.2 245 124.7 1282.7 x 520.7 x 1717.5 20 8 - 2 3 0 - 1 - 6 0 20 3 - 1 - 6 0 20 8 / 2 3 0 - 3 - 6 0 46 0 - 3 - 6 0 AIR AIR 190.5 63.6 106.3 18.0 FIELD POWER SUPPLY CONN. HOLE SIZES PROVIDED: 22.23 HOLD WITH 28.58 KNOCKOUT AND 34.93 KNOCKOUT JUNCTION BOX FOR POWER SUPPLY AND CONTROL CONNECTIONS 36.2 36.6 204.1 114.325.0 FIELD CONTROL SUPPLY WIRE ENTRY 22.22 HOLE W/GROMMET M VAPOR LINE CONN. FEMALE SWEAT CONN. 9.53 LIQUID LINE FEMALE SWEAT CONN. UNIT SIZE MINIMUM MOUNTING PAD DIMENSIONS 18,24 584.2 x 1066.8 30,36,48,60 609.6 x 1270.0 PDS124ANS-06 Specifications subject to change without notice. 11 TESTED AHRI COMBINATION RATINGS* NOTE: Ratings contained in this document are subject to change at any time. For AHRI ratings certificates, please refer to the AHRI directory www.ahridirectory.org. Additional ratings and system combinations can be accessed via the Bryant database at: www.MyBryantRatings.com. For performance data at specific application &/or design conditions with various indoor unit combinations, the equipment performance calculator can be accessed at: http://rpmob.wrightsoft.com/. EER — Energy Efficiency Ratio SEER— Seasonal Energy Efficiency Ratio TXV — Thermostatic Expansion Valve NOTES: 1. Ratings are net values reflecting the effects of circulating fan motor heat. Supplemental electric heat is not included. 2. Tested outdoor/indoor combinations have been tested in accordance with DOE test procedures for central air conditioners. Ratings for other combinations are determined under DOE computer simulation procedures. 3. Determine actual CFM values obtainable for your system by referring to fan performance data in the fan coil or furnace coil literature. 4. Do not apply with capillary tube coils as performance and reliability are significantly affected. Outdoor Model Number - Series (voltage)Indoor Coil Model Number Furnace Model Number Capacity EER SEER 124ANS018-A (N) CNPV*3014AL*+TDR 18,000 12.2 14 124ANS024-A (N) CNPV*3117AL*+TDR 24,000 12.2 14 124ANS030-A (N) CNPV*3117AL*+TDR 29,600 12.2 14 124ANS036-A (N,P,E) CNPV*3717AL*+TDR 35,400 12.2 14 124ANS048-A (N,P,E) CNPV*6024AL*+TDR 45,000 12.2 14 124ANS060-A (N,P,E) CNPV*6124AL*+TDR 57,000 11.7 14 12 Specifications subject to change without notice. PDS124ANS-06 DETAILED COOLING CAPACITIES See the notes on page 13. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F (°C) 75 (23.9)85 (29.4)95 (35)105 (40.6)115 (46.1)125 (51.7) CFM EWB °F (°C) Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ 124ANS018-A Outdoor Section With CNPV*3014AL* Indoor Section 525 72 (22.2) 21.49 10.92 1.18 20.55 10.57 1.31 19.56 10.21 1.45 18.50 9.83 1.61 17.36 9.43 1.79 16.12 9.00 2.00 67 (19.4) 19.43 13.31 1.18 18.58 12.96 1.31 17.67 12.60 1.45 16.71 12.22 1.61 15.68 11.82 1.79 14.57 11.39 2.00 63 (17.2) 17.96 12.78 1.18 17.15 12.43 1.31 16.31 12.06 1.45 15.43 11.69 1.61 14.48 11.29 1.79 13.46 10.86 2.00 62 (16.7) 17.68 15.68 1.18 16.91 15.33 1.31 16.11 14.96 1.45 15.28 14.56 1.61 14.48 14.48 1.79 13.65 13.65 2.00 57 (13.9) 17.17 17.17 1.18 16.55 16.55 1.31 15.91 15.91 1.45 15.21 15.21 1.61 14.46 14.46 1.79 13.63 13.63 2.00 600 72 (22.2) 21.93 11.50 1.21 20.94 11.14 1.34 19.90 10.77 1.48 18.79 10.38 1.64 17.61 9.97 1.82 16.32 9.53 2.03 67 (19.4) 19.84 14.22 1.21 18.94 13.87 1.34 18.00 13.50 1.48 17.00 13.11 1.63 15.93 12.70 1.82 14.78 12.26 2.03 63 (17.2) 18.34 13.63 1.21 17.51 13.27 1.33 16.63 12.90 1.47 15.70 12.51 1.63 14.72 12.10 1.82 13.65 11.66 2.03 62 (16.7) 18.14 16.91 1.21 17.36 16.53 1.33 16.61 16.61 1.47 15.86 15.86 1.63 15.05 15.05 1.82 14.15 14.15 2.03 57 (13.9) 17.95 17.95 1.21 17.29 17.29 1.33 16.59 16.59 1.47 15.84 15.84 1.63 15.02 15.02 1.82 14.13 14.13 2.03 675 72 (22.2) 22.25 12.05 1.24 21.22 11.69 1.36 20.15 11.31 1.50 19.00 10.91 1.66 17.78 10.50 1.85 16.46 10.05 2.06 67 (19.4) 20.15 15.11 1.24 19.22 14.74 1.36 18.25 14.37 1.50 17.22 13.97 1.66 16.12 13.55 1.85 14.94 13.09 2.06 63 (17.2) 18.64 14.45 1.24 17.77 14.08 1.36 16.86 13.70 1.50 15.91 13.30 1.66 14.90 12.88 1.84 13.81 12.42 2.05 62 (16.7) 18.63 18.63 1.24 17.92 17.92 1.36 17.18 17.18 1.50 16.38 16.38 1.66 15.51 15.51 1.84 14.56 14.56 2.06 57 (13.9) 18.60 18.60 1.24 17.89 17.89 1.36 17.15 17.15 1.50 16.36 16.36 1.66 15.49 15.49 1.84 14.55 14.55 2.06 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F (°C) 75 °F (23.9°C)85 °F (29.4°C)95 °F (35°C) 105 °F (40.6°C) 115 °F (46.1°C)125 °F (51.7°C) CFM EWB °F (°C) Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ 124ANS024 - A Outdoor Section With CNPV*3117AL* Indoor Section 700 72 (22.2) 28.62 14.23 1.58 27.33 13.77 1.75 25.95 13.30 1.94 24.48 12.80 2.15 22.90 12.26 2.40 21.21 11.70 2.67 67 (19.4) 26.06 17.53 1.57 24.88 17.08 1.74 23.63 16.60 1.93 22.30 16.09 2.14 20.87 15.56 2.39 19.33 14.99 2.67 63 (17.2) 24.20 16.87 1.57 23.11 16.41 1.74 21.96 15.94 1.92 20.73 15.44 2.14 19.41 14.91 2.38 17.99 14.34 2.66 62 (16.7) 23.80 20.79 1.57 22.74 20.32 1.73 21.65 19.83 1.92 20.58 20.58 2.14 19.51 19.51 2.38 18.33 18.33 2.66 57 (13.9) 23.29 23.29 1.57 22.44 22.44 1.73 21.53 21.53 1.92 20.55 20.55 2.14 19.48 19.48 2.38 18.31 18.31 2.66 800 72 (22.2) 29.11 14.99 1.62 27.76 14.53 1.79 26.33 14.04 1.98 24.80 13.53 2.19 23.16 12.99 2.43 21.41 12.42 2.71 67 (19.4) 26.53 18.75 1.61 25.30 18.29 1.78 24.00 17.80 1.97 22.61 17.28 2.18 21.13 16.74 2.43 19.54 16.16 2.70 63 (17.2) 24.68 18.01 1.61 23.53 17.54 1.77 22.33 17.06 1.96 21.05 16.55 2.18 19.67 16.00 2.42 18.21 15.42 2.70 62 (16.7) 24.39 22.42 1.61 23.40 23.40 1.77 22.42 22.42 1.96 21.36 21.36 2.18 20.20 20.20 2.42 18.94 18.94 2.70 57 (13.9) 24.28 24.28 1.61 23.36 23.36 1.77 22.39 22.39 1.96 21.32 21.32 2.18 20.17 20.17 2.42 18.91 18.91 2.70 900 72 (22.2) 29.46 15.72 1.66 28.07 15.25 1.83 26.59 14.76 2.01 25.01 14.24 2.23 23.33 13.69 2.47 21.53 13.11 2.75 67 (19.4) 26.88 19.93 1.65 25.61 19.46 1.82 24.27 18.96 2.01 22.84 18.43 2.22 21.32 17.87 2.46 19.70 17.27 2.74 63 (17.2) 25.04 19.11 1.65 23.85 18.63 1.81 22.60 18.14 2.00 21.28 17.61 2.21 19.87 17.05 2.46 18.38 16.43 2.74 62 (16.7) 25.15 25.15 1.65 24.16 24.16 1.81 23.11 23.11 2.00 21.98 21.98 2.22 20.75 20.75 2.46 19.42 19.42 2.74 57 (13.9) 25.11 25.11 1.65 24.13 24.13 1.81 23.08 23.08 2.00 21.95 21.95 2.22 20.73 20.73 2.46 19.29 19.39 2.74 PDS124ANS-06 Specifications subject to change without notice. 13 DETAILED COOLING CAPACITIES (CONT.) EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F (°C) 75°F (23.9°C)85°F (29.4°C)95°F (35°C)105°F (40.6°C)115°F (46.1°C)125°F (51.7°C) CFM EWB °F (°C) Capacity MBtuh† Total System KW** Capacity MBtuh† Total System KW** Capacity MBtuh† Total System KW** Capacity MBtuh† Total System KW** Capacity MBtuh† Total System KW** Capacity MBtuh† Total System KW** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ 124ANS030-A Outdoor Section With CNPV*3117AL* Indoor Section 875 72 (22.2) 35.20 16.84 1.95 33.62 16.29 2.18 31.97 15.73 2.43 30.18 15.13 2.70 28.24 14.48 3.02 26.13 13.79 3.38 67 (19.4) 31.99 20.62 1.92 30.56 20.08 2.15 29.06 19.51 2.40 27.44 18.91 2.68 25.67 18.26 3.00 23.75 17.57 3.36 63 (17.2) 29.66 19.84 1.90 28.34 19.30 2.13 26.95 18.74 2.37 25.45 18.13 2.66 23.80 17.48 2.98 22.02 16.78 3.35 62 (16.7) 29.18 24.36 1.90 27.92 23.82 2.12 26.58 23.24 2.37 25.18 24.97 2.65 23.81 23.81 2.98 22.34 22.34 3.35 57 (13.9) 28.38 28.38 1.89 27.37 27.37 2.12 26.28 26.28 2.37 25.09 25.09 2.65 23.77 23.77 2.98 22.31 22.31 3.35 1000 72 (22.2) 35.90 17.73 1.98 34.26 17.17 2.21 32.52 16.59 2.46 30.66 15.98 2.74 28.65 15.32 3.05 26.46 14.62 3.41 67 (19.4) 32.65 22.03 1.95 31.17 21.48 2.18 29.60 20.90 2.43 27.91 20.28 2.71 26.08 19.62 3.03 24.10 18.91 3.39 63 (17.2) 30.30 21.15 1.93 28.93 20.60 2.16 27.48 20.02 2.40 25.91 19.41 2.69 24.21 18.74 3.01 22.36 18.02 3.37 62 (16.7) 29.94 26.26 1.93 28.66 25.66 2.15 27.43 27.43 2.41 26.15 26.15 2.69 24.73 24.73 3.01 23.17 23.17 3.38 57 (13.9) 29.65 29.65 1.93 28.56 28.56 2.15 27.39 27.39 2.40 26.11 26.11 2.69 24.70 24.70 3.01 23.14 23.14 3.38 1125 72 (22.2) 36.44 18.57 2.01 34.73 18.00 2.24 32.94 17.41 2.49 31.02 16.79 2.77 28.94 16.12 3.08 26.71 15.41 3.43 67 (19.4) 33.18 23.38 1.98 31.64 22.82 2.21 30.01 22.23 2.46 28.28 21.60 2.74 26.40 20.92 3.05 24.38 20.18 3.41 63 (17.2) 30.81 22.41 1.96 29.38 21.85 2.19 27.89 21.26 2.43 26.28 20.63 2.72 24.53 19.94 3.04 22.65 19.20 3.40 62 (16.7) 30.76 30.76 1.96 29.59 29.59 2.19 28.34 28.34 2.44 26.99 26.99 2.72 25.49 25.49 3.05 23.84 23.84 3.41 57 (13.9) 30.72 30.72 1.96 29.55 29.55 2.19 28.31 28.31 2.44 26.95 26.95 2.72 25.45 25.45 3.04 23.81 23.81 3.41 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F (°C) 75°F (23.9°C)85°F (29.4°C)95°F (35°C)105°F (40.6°C)115°F (46.1°C)125°F (51.7°C) CFM EWB °F (°C) Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ 124ANS036-A Outdoor Section With CNPV*3717AL* Indoor Section 1050 72 (22.2) 42.58 22.26 2.36 40.51 21.51 2.60 38.30 20.71 2.87 35.94 19.87 3.16 33.37 18.97 3.50 30.62 18.01 3.88 67 (19.4) 38.73 27.46 2.34 36.87 26.71 2.58 34.88 25.92 2.84 32.74 25.08 3.14 30.43 24.18 3.48 27.97 23.23 3.86 63 (17.2) 35.96 26.41 2.32 34.24 25.67 2.56 32.40 24.88 2.82 30.43 24.04 3.12 28.31 23.15 3.46 26.03 22.20 3.85 62 (16.7) 35.38 32.60 2.32 33.73 31.84 2.56 32.01 31.81 2.82 30.38 30.38 3.12 28.63 28.63 3.46 26.73 26.73 3.85 57 (13.9) 34.71 34.71 2.31 33.37 33.37 2.55 31.92 31.92 2.82 30.34 30.34 3.12 28.59 28.59 3.46 26.70 26.70 3.85 1200 72 (22.2) 43.29 23.46 2.42 41.13 22.69 2.66 38.84 21.88 2.93 36.37 21.02 3.22 33.71 20.10 3.56 30.85 19.13 3.94 67 (19.4) 39.43 29.38 2.40 37.47 28.61 2.64 35.40 27.80 2.90 33.18 26.94 3.20 30.79 26.02 3.53 28.26 25.05 3.92 63 (17.2) 36.64 28.20 2.38 34.83 27.43 2.62 32.92 26.62 2.88 30.87 25.77 3.18 28.67 24.85 3.52 26.33 23.88 3.91 62 (16.7) 36.27 36.05 2.38 34.77 34.77 2.62 33.20 33.20 2.89 31.50 31.50 3.19 29.61 29.61 3.53 27.57 27.57 3.92 57 (13.9) 36.17 36.17 2.38 34.71 34.71 2.62 33.15 33.15 2.89 31.45 31.45 3.19 29.57 29.57 3.53 27.54 27.54 3.91 1350 72 (22.2) 43.81 24.60 2.48 41.58 23.82 2.72 39.20 23.00 2.99 36.66 22.13 3.28 33.92 21.20 3.62 31.04 20.23 4.00 67 (19.4) 39.93 31.22 2.46 37.92 30.44 2.70 35.78 29.61 2.96 33.50 28.73 3.26 31.06 27.78 3.59 28.49 26.76 3.98 63 (17.2) 37.14 29.91 2.44 35.28 29.13 2.68 33.30 28.30 2.94 31.20 27.42 3.24 28.94 26.47 3.58 26.58 25.43 3.97 62 (16.7) 37.43 37.43 2.44 35.87 35.87 2.68 34.21 34.21 2.95 32.39 32.39 3.25 30.39 30.39 3.59 28.23 28.23 3.98 57 (13.9) 37.38 37.38 2.44 35.83 35.83 2.68 34.16 34.16 2.95 32.35 32.35 3.25 30.36 30.36 3.59 28.20 28.20 3.98 14 Specifications subject to change without notice. PDS124ANS-06 DETAILED COOLING CAPACITIES (CONT.) Total and sensible capacities are net capacities. Blower mower hear has been subtracted. ‡Sensible capacities shown are based on 80F (27C) entering air at the indoor coil. For sensible capacities at other than 80F (27C), deduct 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80F (27C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80F (27C). ** System kw is total of indoor and outdoor unit kilowatts. EWB — Entering Wet Bulb NOTES: 1. Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per AHRI standard 210/240-2008. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. 2. When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F (°C) 75°F (23.9°C)85°F (29.4°C)95°F (35°C)105°F (40.6°C)115°F (46.1°C)125°F (51.7°C) CFM EWB °F (°C) Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ 124ANS048-A Outdoor Section With CNPV*6024AL* Indoor Section 1400 72 (22.2) 54.32 28.47 3.22 51.89 27.57 3.53 49.29 26.62 3.88 46.43 25.59 4.29 43.30 24.47 4.76 39.89 23.27 5.30 67 (19.4) 49.54 35.14 3.19 47.35 34.25 3.49 45.00 33.30 3.85 42.43 32.28 4.25 39.60 31.16 4.72 36.51 29.95 5.26 63 (17.2) 46.06 33.82 3.16 44.05 32.94 3.47 41.89 32.00 3.82 39.52 30.98 4.22 36.90 29.87 4.69 34.04 28.66 5.23 62 (16.7) 45.44 41.73 3.15 43.53 40.82 3.46 41.48 39.82 3.81 39.37 39.37 4.22 37.22 37.22 4.70 34.80 34.80 5.24 57 (13.9) 44.54 44.54 3.15 42.97 42.97 3.46 41.24 41.24 3.81 39.32 39.32 4.22 37.17 37.17 4.70 34.76 34.76 5.24 1600 72 (22.2) 55.17 29.90 3.30 52.64 28.99 3.61 49.92 28.01 3.96 46.96 26.96 4.37 43.72 25.83 4.84 40.19 24.61 5.38 67 (19.4) 50.36 37.46 3.27 48.09 36.55 3.57 45.64 35.59 3.93 42.97 34.53 4.34 40.05 33.39 4.81 36.86 32.13 5.34 63 (17.2) 46.86 35.98 3.24 44.77 35.09 3.55 42.51 34.12 3.90 40.05 33.08 4.31 37.35 31.93 4.77 34.40 30.67 5.31 62 (16.7) 46.51 44.79 3.24 44.64 44.64 3.55 42.79 42.79 3.90 40.73 40.73 4.31 38.42 38.42 4.79 35.83 35.83 5.33 57 (13.9) 46.30 46.30 3.24 44.60 44.60 3.55 42.73 42.73 3.90 40.67 40.67 4.31 38.37 38.37 4.79 35.79 35.79 5.33 1800 72 (22.2) 55.79 31.25 3.38 53.16 30.32 3.69 50.36 29.34 4.04 47.31 28.27 4.45 43.97 27.12 4.92 40.37 25.89 5.46 67 (19.4) 50.98 39.68 3.35 48.62 38.75 3.65 46.10 37.76 4.01 43.37 36.69 4.42 40.37 35.50 4.89 37.14 34.18 5.42 63 (17.2) 47.47 38.04 3.32 45.30 37.12 3.63 42.98 36.13 3.98 40.45 35.06 4.39 37.69 33.87 4.86 34.70 32.54 5.39 62 (16.7) 47.80 47.80 3.32 45.99 45.99 3.63 44.00 44.00 3.99 41.81 41.81 4.40 39.36 39.36 4.88 36.64 36.64 5.42 57 (13.9) 47.74 47.74 3.32 45.93 45.93 3.63 43.95 43.95 3.99 41.76 41.76 4.40 39.32 39.32 4.87 36.60 36.60 5.41 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES °F (°C) 75°F (23.9°C)85°F (29.4°C)95°F (35°C)105°F (40.6°C)115°F (46.1°C)125°F (51.7°C) CFM EWB °F (°C) Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Capacity MBtuh Total Sys KW** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ 124ANS060-A Outdoor Section With CNPV*6124AL* Indoor Section 1750 72 (22.2) 68.86 34.68 4.09 65.73 33.57 4.48 62.37 32.40 4.93 58.68 31.12 5.45 54.65 29.75 6.04 50.21 28.26 6.71 67 (19.4) 62.81 42.85 4.03 60.01 41.76 4.42 57.00 40.60 4.87 53.69 39.34 5.39 50.05 37.96 5.98 46.03 36.46 6.65 63 (17.2) 58.41 41.24 3.99 55.85 40.17 4.38 53.11 39.03 4.82 50.06 37.78 5.34 46.70 36.41 5.93 42.98 34.90 6.59 62 (16.7) 57.61 50.93 3.98 55.17 49.82 4.37 52.58 48.59 4.82 49.93 49.93 5.34 47.15 47.15 5.94 44.00 44.00 6.61 57 (13.9) 56.53 56.53 3.97 54.53 54.53 4.37 52.32 52.32 4.82 49.86 49.86 5.34 47.09 47.09 5.94 43.94 43.94 6.61 2000 72 (22.2) 69.94 36.44 4.19 66.66 35.31 4.58 63.14 34.10 5.04 59.32 32.81 5.56 55.14 31.41 6.15 50.56 29.90 6.81 67 (19.4) 63.84 45.70 4.14 60.93 44.59 4.53 57.78 43.40 4.98 54.34 42.10 5.49 50.59 40.69 6.08 46.45 39.14 6.75 63 (17.2) 59.43 43.90 4.09 56.76 42.80 4.48 53.87 41.62 4.93 50.72 40.34 5.44 47.25 38.93 6.03 43.42 37.37 6.70 62 (16.7) 58.98 54.67 4.09 56.66 56.66 4.48 54.28 54.28 4.94 51.61 51.61 5.46 48.63 48.63 6.06 45.27 45.27 6.73 57 (13.9) 58.76 58.76 4.09 56.58 56.58 4.48 54.20 54.20 4.93 51.55 51.55 5.46 48.57 48.57 6.05 45.22 45.22 6.73 2250 72 (22.2) 70.70 38.10 4.29 67.30 36.94 4.68 63.68 35.72 5.14 59.73 34.41 5.66 55.44 32.99 6.25 50.77 31.46 6.91 67 (19.4) 64.61 48.42 4.24 61.59 47.28 4.63 58.35 46.06 5.08 54.82 44.74 5.59 50.98 43.27 6.18 46.79 41.64 6.85 63 (17.2) 60.18 46.42 4.19 57.41 45.29 4.58 54.45 44.09 5.03 51.21 42.77 5.55 47.66 41.31 6.13 43.79 39.65 6.80 62 (16.7) 60.66 60.66 4.20 58.34 58.34 4.59 55.79 55.79 5.05 52.96 52.96 5.57 49.81 49.81 6.17 46.25 46.25 6.84 57 (13.9) 60.58 60.58 4.20 58.27 58.27 4.59 55.72 55.72 5.05 52.90 52.90 5.57 49.75 49.75 6.17 46.20 46.20 6.84 PDS124ANS-06 Specifications subject to change without notice. 15 CONDENSER ONLY RATINGS See notes on page 15. SST °F (°C)CONDENSER ENTERING AIR TEMPERATURES °F (°C) 55 °F (12.78°C) 65 °F (18.33°C) 75 °F (23.89°C) 85 °F (29.44°C) 95 °F (35.0°C) 105 °F (40.56°C) 115 °F (46.11°C) 125 °F (51.67°C) 24AHA418A124ANS018-A30 30°F (-1.11°C) TCG 16.60 15.60 14.70 13.80 12.90 12.00 11.10 10.10 SDT 68.50 78.00 87.50 97.00 106.50 116.00 125.40 134.70 KW 0.76 0.87 0.99 1.11 1.25 1.40 1.59 1.80 35°F (1.67°C) TCG 18.30 17.20 16.30 15.30 14.30 13.30 12.30 11.20 SDT 69.70 79.20 88.70 98.20 107.60 117.00 126.30 135.50 KW 0.76 0.87 0.99 1.11 1.25 1.41 1.59 1.80 40°F (4.44°C) TCG 20.00 19.00 17.90 16.90 15.80 14.70 13.60 12.40 SDT 71.10 80.50 89.90 99.40 108.70 118.00 127.20 136.30 KW 0.77 0.88 0.99 1.11 1.25 1.41 1.59 1.80 45°F (7.22°C) TCG 22.00 20.80 19.70 18.50 17.40 16.20 14.90 13.60 SDT 72.50 81.90 91.30 100.60 109.80 119.00 128.20 137.20 KW 0.77 0.88 0.99 1.12 1.26 1.41 1.59 1.80 50°F (10.0°C) TCG 24.00 22.80 21.60 20.40 19.10 17.80 16.40 15.00 SDT 74.00 83.40 92.60 101.90 111.00 120.10 129.20 138.20 KW 0.77 0.88 0.99 1.12 1.26 1.41 1.59 1.80 55°F (12.78°C) TCG 26.30 25.00 23.60 22.30 20.90 19.50 18.00 16.40 SDT 75.60 84.80 94.10 103.20 112.30 121.30 130.30 139.20 KW 0.78 0.88 1.00 1.12 1.26 1.42 1.60 1.80 24AHA424A30 124ANS024-A 30°F (-1.11°C) TCG 21.40 20.20 19.00 17.80 16.60 15.40 14.20 12.90 SDT 71.90 81.30 90.70 100.00 109.30 118.50 127.70 136.80 KW 1.01 1.15 1.30 1.46 1.64 1.85 2.09 2.36 35°F (1.67°C) TCG 23.50 22.20 20.90 19.60 18.30 17.00 15.60 14.20 SDT 73.50 82.80 92.10 101.30 110.50 119.60 128.70 137.70 KW 1.02 1.16 1.30 1.47 1.65 1.86 2.09 2.37 40°F (4.44°C) TCG 25.70 24.40 23.00 21.60 20.20 18.70 17.20 15.60 SDT 75.10 84.30 93.50 102.60 111.80 120.80 129.80 138.80 KW 1.02 1.16 1.31 1.47 1.66 1.86 2.10 2.38 45°F (7.22°C) TCG 28.20 26.70 25.20 23.70 22.10 20.50 18.90 17.10 SDT 76.70 85.90 95.00 104.10 113.10 122.10 131.00 139.80 KW 1.03 1.17 1.32 1.48 1.66 1.87 2.11 2.39 50°F (10.0°C) TCG 30.80 29.20 27.50 25.90 24.20 22.40 20.60 18.70 SDT 78.50 87.50 96.60 105.60 114.60 123.40 132.20 140.90 KW 1.04 1.18 1.32 1.49 1.67 1.88 2.12 2.39 55°F (12.78°C) TCG 33.60 31.80 30.10 28.30 26.40 24.50 22.40 20.30 SDT 80.30 89.30 98.30 107.20 116.10 124.90 133.50 142.00 KW 1.05 1.18 1.33 1.50 1.68 1.89 2.13 2.40 24AHA430A30 124ANS030-A 30°F (-1.11°C) TCG 27.20 25.80 24.40 22.90 21.40 19.70 17.90 16.00 SDT 69.90 79.20 88.60 98.00 107.30 116.60 125.80 134.80 KW 1.22 1.39 1.57 1.77 2.00 2.27 2.58 2.94 35°F (1.67°C) TCG 30.10 28.50 27.00 25.40 23.70 21.90 20.00 17.90 SDT 71.20 80.60 89.90 99.20 108.50 117.70 126.80 135.80 KW 1.22 1.40 1.58 1.78 2.01 2.28 2.58 2.94 40°F (4.44°C) TCG 33.10 31.40 29.70 28.00 26.20 24.30 22.20 20.00 SDT 72.70 82.00 91.20 100.50 109.70 118.90 127.90 136.90 KW 1.23 1.41 1.59 1.80 2.03 2.29 2.59 2.94 45°F (7.22°C) TCG 36.50 34.50 32.70 30.80 28.80 26.80 24.50 22.10 SDT 74.30 83.50 92.70 101.90 111.00 120.10 129.10 137.90 KW 1.25 1.43 1.61 1.82 2.05 2.31 2.60 2.95 50°F (10.0°C) TCG 40.00 37.90 35.80 33.80 31.60 29.40 27.00 24.40 SDT 76.00 85.10 94.20 103.40 112.40 121.40 130.30 139.00 KW 1.27 1.45 1.64 1.84 2.07 2.33 2.62 2.95 55°F (12.78°C) TCG 43.80 41.40 39.20 36.90 34.60 32.10 29.50 26.70 SDT 77.90 86.90 95.90 104.90 113.90 122.80 131.50 140.20 KW 1.29 1.47 1.66 1.87 2.09 2.35 2.64 2.97 16 Specifications subject to change without notice. PDS124ANS-06 CONDENSER ONLY RATINGS (CONT.) * AHRI listing applies only to systems shown in Combination Ratings table. • KW - Outdoor Unit Kilowatts Only. • SDT - Saturated Temperature Leaving Compressor (°F) • SST - Saturated Temperature Entering Compressor (°F/°C) • TCG - Gross Cooling Capacity (1000 Btuh) SST °F (°C) CONDENSER ENTERING AIR TEMPERATURES °F (°C) 55°F (12.78°C) 65°F (18.33°C) 75°F (23.89°C) 85°F (29.44°C) 95°F (35.0°C) 105°F (40.56°C) 115°F (46.11°C) 125°F (51.67°C) 124ANS036-A 30°F (-1.11°C) TCG 31.40 29.80 28.20 26.40 24.60 22.70 20.60 18.50 SDT 68.70 78.10 87.50 96.80 106.20 115.50 124.70 134.00 KW 1.48 1.69 1.91 2.14 2.40 2.69 3.04 3.44 35°F (1.67°C) TCG 34.70 32.90 31.10 29.20 27.20 25.10 22.80 20.50 SDT 70.00 79.30 88.60 97.90 107.20 116.40 125.60 134.80 KW 1.48 1.70 1.91 2.15 2.41 2.70 3.05 3.45 40°F (4.44°C) TCG 38.20 36.20 34.20 32.10 29.90 27.60 25.20 22.60 SDT 71.30 80.50 89.80 99.10 108.30 117.40 126.50 135.60 KW 1.49 1.70 1.92 2.16 2.42 2.72 3.06 3.45 45°F (7.22°C) TCG 42.00 39.80 37.60 35.30 32.90 30.30 27.70 24.80 SDT 72.80 81.90 91.10 100.30 109.40 118.50 127.50 136.40 KW 1.50 1.72 1.94 2.18 2.44 2.73 3.07 3.46 50°F (10.0°C) TCG 46.00 43.60 41.10 38.60 36.00 33.20 30.20 27.20 SDT 74.40 83.40 92.50 101.60 110.60 119.60 128.50 137.30 KW 1.52 1.74 1.96 2.20 2.46 2.75 3.08 3.47 55°F (12.78°C) TCG 50.20 47.60 44.90 42.10 39.20 36.20 32.90 29.60 SDT 76.10 85.00 94.00 103.00 111.90 120.80 129.50 138.20 KW 1.54 1.76 1.98 2.22 2.48 2.77 3.10 3.48 124ANS048-A 30°F (-1.11°C) TCG 41.50 39.50 37.40 35.40 33.20 30.80 28.20 25.40 SDT 73.40 82.60 91.90 101.20 110.40 119.50 128.60 137.50 KW 2.05 2.30 2.57 2.87 3.21 3.60 4.05 4.56 35°F (1.67°C) TCG 45.70 43.40 41.20 38.90 36.50 33.90 31.10 28.10 SDT 75.10 84.30 93.40 102.60 111.70 120.80 129.70 138.60 KW 2.08 2.33 2.60 2.90 3.24 3.63 4.08 4.60 40°F (4.44°C) TCG 50.10 47.70 45.20 42.70 40.10 37.20 34.20 30.90 SDT 77.00 86.00 95.10 104.10 113.20 122.10 131.00 139.70 KW 2.12 2.36 2.63 2.93 3.27 3.67 4.12 4.64 45°F (7.22°C) TCG 54.80 52.20 49.50 46.70 43.80 40.70 37.40 33.80 SDT 78.90 87.80 96.80 105.80 114.70 123.50 132.20 140.80 KW 2.15 2.39 2.66 2.96 3.31 3.71 4.16 4.69 50°F (10.0°C) TCG 59.90 56.90 54.00 51.00 47.80 44.40 40.70 36.80 SDT 80.90 89.80 98.60 107.50 116.30 125.00 133.60 142.00 KW 2.19 2.43 2.70 3.00 3.34 3.74 4.20 4.72 55°F (12.78°C) TCG 65.20 62.00 58.80 55.40 51.90 48.20 44.20 39.90 SDT 83.10 91.80 100.50 109.30 117.90 126.50 134.90 143.20 KW 2.24 2.47 2.73 3.03 3.38 3.78 4.24 4.76 124ANS060-A 30°F (-1.11°C) TCG 53.00 50.30 47.70 45.10 42.40 39.40 36.00 32.40 SDT 76.00 85.10 94.30 103.50 112.70 121.70 130.60 139.40 KW 2.59 2.90 3.23 3.61 4.03 4.52 5.08 5.71 35°F (1.67°C) TCG 58.30 55.30 52.50 49.70 46.60 43.30 39.70 35.70 SDT 78.00 87.00 96.10 105.20 114.20 123.10 131.90 140.60 KW 2.64 2.94 3.28 3.65 4.08 4.58 5.14 5.78 40°F (4.44°C) TCG 63.90 60.70 57.60 54.50 51.10 47.50 43.60 39.30 SDT 80.00 88.90 97.90 106.90 115.80 124.70 133.30 141.90 KW 2.69 2.99 3.32 3.70 4.14 4.63 5.20 5.84 45°F (7.22 °C) TCG 70.00 66.50 63.10 59.60 55.90 51.90 47.60 42.90 SDT 82.20 91.00 99.90 108.80 117.60 126.30 134.80 143.20 KW 2.74 3.04 3.38 3.76 4.19 4.69 5.27 5.91 50°F (10.0°C) TCG 76.40 72.60 68.80 65.00 60.90 56.50 51.80 46.70 SDT 84.60 93.30 102.00 110.70 119.40 127.90 136.30 144.50 KW 2.80 3.10 3.43 3.81 4.25 4.76 5.33 5.97 55°F (12.78°C) TCG 83.30 79.10 74.90 70.60 66.10 61.30 56.10 50.60 SDT 87.00 95.60 104.20 112.80 121.20 129.60 137.80 145.80 KW 2.86 3.15 3.49 3.87 4.31 4.82 5.39 6.04 PDS124ANS-06 Specifications subject to change without notice. 17 GUIDE SPECIFICATIONS GENERAL SYSTEM DESCRIPTION Outdoor-mounted, air-cooled, split-system air conditioning unit suitable for ground or rooftop installation. Unit consists of a scroll- type hermetic compressor, an air-cooled coil, propeller-type condenser fan, and a control box. Unit discharges supply air horizontally as shown on contract drawings. Unit should be used in a refrigeration circuit to match up to a packaged fan coil or furnace. Quality Assurance — Unit is rated in accordance with the latest edition of AHRI Standard 210. — Unit is certified for capacity and efficiency, and listed in the latest AHRI directory. — Unit construction complies with latest edition of ANSI/ ASHRAE and with NEC. — Unit is constructed in accordance with UL standards and carries the UL label of approval. Unit has c-UL approval. — Unit cabinet is capable of withstanding Federal Test Method Standard No. 141 (Method 6061) 500-hr salt spray test. — Air-cooled condenser coils are leak tested and pressure tested — Unit is constructed in a ISO9001 approved facility. Delivery, Storage, and Handling — Unit is shipped as single package only and is stored and handled per unit manufacturer’s recommendations. Warranty (for inclusion by specifying engineer) — U.S. and Canada only. PRODUCTS Equipment — Factory assembled, single piece, air−cooled air conditioning unit. Contained within the unit enclosure is all factory wiring, piping, controls, compressor, refrigerant charge Puron (R−410A), and special features required prior to field start−up. Unit Cabinet — Unit cabinet is constructed of galvanized steel and bonderized. Fans — Condenser fan is direct−drive propeller type, discharging air horizontally AIR-COOLED, SPLIT-SYSTEM AIR CONDITIONER 124ANS 1-1/2 TO 5 NOMINAL TONS — Condenser fan motors are totally enclosed, 1-phase type with class B insulation and permanently lubricated bearings. Shafts are corrosion resistant. — Fan blades are statically and dynamically balanced. — Condenser fan openings are equipped with coated steel wire safety guards Compressor — Compressor is a scroll-type, hermetically sealed. — Compressor is mounted on rubber vibration isolators. Condenser Coil — Condenser coil is air cooled. — Coil is constructed of aluminum fins mechanically bonded to copper tubes which are then cleaned, dehydrated, and sealed. Refrigeration Components — Refrigeration circuit components include liquid-line front- seating shutoff valve with sweat connections, vapor-line front-seating shutoff valve with sweat connections, system charge of Puron (R-410A) refrigerant, and compressor oil. — Unit is equipped with high-pressure switch and filter drier for Puron refrigerant. Operating Characteristics — The capacity of the unit meets or exceeds ________________ Btuh at a suction temperature of _____ °F/°C. The power consumption at full load does not exceed _________ kW. — Combination of the unit and the evaporator or fan coil unit has a total net cooling capacity of _____ Btuh or greater at conditions of _____ CFM entering air temperature at the evaporator at _____ °F/°C wet bulb and _____ F/C dry bulb, and air entering the unit at _____ F/C. — The system has a SEER of _____ Btuh/watt or greater at DOE conditions. Electrical Requirements — Nominal unit electrical characteristics is _____ v, single phase, 60 hz. The unit is capable of satisfactory operation within voltage limits of _____ v to _____ v. — Nominal unit electrical characteristics is _____ v, three phase, 60 hz. The unit is capable of satisfactory operation within voltage limits of _____ v to _____ v. — Unit electrical power is a single point connection. — Control circuit is 24V. Special Features — Refer to the section of this literature identifying accessories and descriptions for specific features and available enhancements. Copyright 2020 Bryant Hearing and Cooling Systems D3300 Riverwood Parkway Atlanta GA, 30339 Edition Date: 05/20 Catalog No. PDS124ANS-06 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Replaces: PDS124ANS-05